When turning on the power supply, the display flashes on and off. First 
checks of the power supply are executed (1-2 minutes).

When no trouble occurs: lighted as indicated (8-10 minutes).

Ready for operation: blank display indication as indicated.

When above situation cannot be confirmed after 12 minutes, the mal-
function code can be checked on the indoor unit user interface and the 
outdoor unit segment display. Solve the malfunction code accordingly. 
The communication wiring should be checked at first.

 INFORMATION

Be sure to turn the power on at least 6 hours before operation in order 
to have power running to the crank case heater.

Accessing modes

BS1 is used to change the mode you want to access.

• 

Access mode 1
Push BS1 one time. Segment indication changes to:

• 

Access mode 2
Push BS1 for at least 5 seconds. Segment indication changes to:

 INFORMATION

If you get confused in the middle of the process, push BS1.
Then it returns to idle situation (no indication on segment displays: 
blank, refer to Functions of the push button switches which are located 
on the main printed circuit board (A1P) on page 25).

Mode 1

Mode 1 is used to set basic settings and to monitor the status of the 
unit (15.2. Monitoring function and field settings on page 32).

• 

Changing and access the setting in mode 1:
Once mode 1 is selected (push BS1 one time), you can select the 
wanted setting. It is done by pushing BS2. Accessing the selected 
setting’s value is done by pushing BS3 one time.

• 

To quit and return to the initial status, press BS1.

Example

:

Checking the content of parameter [1-10] (to know how many indoor 
units are connected to the system).

[A-B]=C in this case defined as: A=1; B=10; C=the value we want to 
know/monitor:

• 

Make sure the segment indication is displayed in operational default 
mode as shipped from factory.

• 

Push BS1 one time; result segment display:

Result: mode 1 is accessed.

• 

Push BS2 10 times; result segment display:

Result: mode 1 setting 10 is addressed.

• 

Push BS3 one time; the value which is returned (depending on the 
actual field situation), is the amount of indoor units which are con-
nected to the system.
Result: mode 1 setting 10 is addressed and selected, return value is 
monitored information.

• 

To leave the monitoring function, push BS1 one time, you will return 
to the default situation when shipped from factory.

Mode 2

Mode 2 is used to set field settings of the outdoor unit and system.

• 

Changing and access the setting in mode 2:
Once mode 2 is selected (push BS1 for more than 5 seconds), you 
can select the wanted setting. It is done by pushing BS2.
Accessing the selected setting’s value is done by pushing BS3 one 
time.

• 

To quit and return to the initial status, press BS1.

• 

Changing the value of the selected setting in mode 2:

 

- Once mode 2 is selected (push BS1 for more than 5 seconds) 

you can select the wanted setting. It is done by pushing BS2.

 

- Accessing the selected setting’s value is done by pushing BS3 

one time.

 

- Now BS2 is used to select the required value of the selected 

setting.

 

- When the required value is selected, you can define the change 

of value by pushing BS3 one time.

 

- Press BS3 again to start operation according to the chosen value.

Example:

Checking the content of parameter [2-18] (to define the high static 
pressure setting of the outdoor unit’s fan).

[A-B]=C in this case defined as: A=2; B=10; C=the value we want to 

know/change

Make sure the segment indication is as during normal operation (de-
fault situation when shipped from factory).

• 

Push BS1 for over 5 seconds; result segment display:

Result: mode 2 is accessed.

• 

Push BS2 18 times; result segment display:

Result: mode 2 setting 18 is addressed.

• 

Push BS3 one time; the value which is returned (depending on the 
actual field situation), is the status of the setting. In the case of [2-
18], default value is 0, which means the function is not active.
Result: mode 2 setting 18 is addressed and selected, return value is 
the current setting situation.

• 

To change the value of the setting, push BS2 till the required value 
appears on the segment indication. When achieved, define the set-
ting value by pushing BS3 one time. To start operation according to 
the chosen setting, confirm again by pushing BS3.

• 

To leave the monitoring function, push BS1 two times, you will 
return to the default situation when shipped from factory.

01_EN_03_3P734038-2.indd   25

01_EN_03_3P734038-2.indd   25

2023/05/29   11:59:55

2023/05/29   11:59:55

Summary of Contents for RELQ72TBTJ Series

Page 1: ...the event of conflicting information the online instructions are to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instructions d...

Page 2: ...tion work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room take...

Page 3: ...ed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced for...

Page 4: ...18 9 Field wiring 19 9 1 Power circuit safety device and cable requirements 20 9 2 Wiring connection example for whole system 20 9 3 Leading wire procedure 20 9 4 Transmission wiring connection proce...

Page 5: ...and right where RELQ 144 240 consists of multiple RELQ 72 120 single modules as indicated 72 96 120 RELQ72TBTJ TBYD TBYC 1 RELQ96TBTJ TBYD TBYC 1 RELQ120TBTJ TBYD TBYC 1 RELQ144TBTJ TBYD TBYC 2 RELQ1...

Page 6: ...TJ TBYD TBYC 168 312 NOTE Higher capacity than the above table can be selected this may affect heating and cooling capacity For additional information see technical engineering data 1 4 Scope of the m...

Page 7: ...he unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Serv...

Page 8: ...lt in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit...

Page 9: ...the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c...

Page 10: ...ngineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2 Han...

Page 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Page 12: ...ng work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 19 and 12 Checking of device and installation conditions on page 25 are complete Do not use flux whe...

Page 13: ...Branch Selector units C Choose from the following table in accordance with the indoor unit total capacity connected downstream Do not let the connection pip ing exceed the refrigerant piping size chos...

Page 14: ...P25M33H9 KHRP25M33HA KHRP26M22H9 KHRP26M22HA maximum 4 indoor units or KHRP26M33H9 KHRP26M33HA maximum 8 indoor units 72 111 KHRP26M33H9 KHRP26M33HA 111 230 KHRP25M72H9 KHRP25M72HA KHRP26M72H9 KHRP26M...

Page 15: ...m to the below length when calculating an equivalent length to each indoor unit connected to BSF Q54T Total capacity of the indoor units to be connected down stream Equivalent length BSF4Q54T BSF6Q54T...

Page 16: ...he figure below referring to the table below Do not upsize the high low pressure gas pipe and the suction gas pipe Outdoor unit capacity type Liquid pipe Main pipe Upsize the liquid pipe First refrige...

Page 17: ...pe and lines that are not upsized should not be doubled a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p q r s 1640 ft 500 m 3 The actual piping length from each indoor units to the nearest refriger ant bran...

Page 18: ...m ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt on t...

Page 19: ...op valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool...

Page 20: ...ller field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP2...

Page 21: ...eader so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Page 22: ...lve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant l...

Page 23: ...RELQ96TBYD RELQ120TBYD RELQ144TBYD RELQ192TBYD RELQ240TBYD f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 28 1 39 8 43 4 28 1 28 1 39 8 39 8 43 4 43 4 35 45 50 35 35 45...

Page 24: ...ation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would des...

Page 25: ...ctions See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the t...

Page 26: ...r the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is opened will cause the insulation...

Page 27: ...ns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours re...

Page 28: ...ccess you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switch...

Page 29: ...cted to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situation...

Page 30: ...refrigerant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Page 31: ...2 Indoor units FXSQ type 12 2 FXMQ type 15 2 18 5 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft f f1 4 5 ft k f3 8 10 ft p f3 8 15 ft u f3 8 10 ft b f3 4 10 ft g f1 4 5 ft f3 8 10 ft q f1 4 10...

Page 32: ...it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube...

Page 33: ...valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B 9 8 11 11 12 10 14 13 15 16 A C 7 1 Pressure reducing valve 2 Nitrogen 3 Measuring instrument 4...

Page 34: ...the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this chapter is read sequentially by...

Page 35: ...low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 unit is currently operating under...

Page 36: ...nal external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the outdoo...

Page 37: ...or is required to perform power consumption limitation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumption l...

Page 38: ...lt 2 Quick 3 Powerful Change 2 81 0 1 2 or 3 in function of required limitation This setting is used in conjunction with setting 2 8 and 2 47 In the case of 2 81 0 the original refrigerant temperature...

Page 39: ...X Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable temp Release differential Fahrenhe...

Page 40: ...ary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table below Please be aware that the error codes that a...

Page 41: ...feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi sens...

Page 42: ...t from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the po...

Page 43: ...air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is ro...

Page 44: ...pressor 4 Make sure the default idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 25 Push BS2 for 5 seconds or more The unit will st...

Page 45: ...it board or actuator 31 36 Electronic expansion valve malfunction 208 230 460V Y6E A6P X10A 575V Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve mal...

Page 46: ...function open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure sensor malfunction short circuit S1NPL A1P X31A Check connection on printed circuit board...

Page 47: ...ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation manual enclosed in Branch Selec...

Page 48: ...s due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise the malfunc...

Page 49: ...event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the max...

Page 50: ...3P734038 2 EM23A007 2311 SP Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P734038 2 indd 2 00_CV_3P734038 2 indd 2 2023 05 29 11 57 22 2023 05 29 11 57 22...

Reviews: