background image

English

i

Safety considerations

Read these Safety considerations for Installation carefully be-
fore installing an air conditioner or heat pump. After complet-
ing the installation, make sure that the unit operates properly 
during the startup operation.
Instruct the customer on how to operate and maintain the 
unit.
Inform customers that they should store this Installation 
Manual with the Operation Manual for future reference.
Always use a licensed installer or contractor to install this 
product.
Improper installation can result in water or refrigerant leak-

age, electrical shock, fire, or explosion.

Meanings of 

DANGER

WARNING

CAUTION

, and 

NOTE

Symbols:

DANGER   .  .  .  .  .  .  .  .

Indicates an imminently hazardous 
situation which, if not avoided, will 
result in death or serious injury.

WARNING   .  .  .  .  .  .  .

Indicates a potentially hazardous 
situation which, if not avoided, 
could result in death or serious 
injury.

CAUTION  .  .  .  .  .  .  .  .

Indicates a potentially hazardous 
situation which, if not avoided, 
may result in minor or moderate 
injury. It may also be used to alert 
against unsafe practices.

NOTE   .  .  .  .  .  .  .  .  .  .  .

Indicates situations that may result 
in equipment or property-damage 
accidents only.

INFORMATION   .  .  .

This symbol identifies useful tips 

or additional information.

 DANGER

• 

Refrigerant gas is heavier than air and replaces oxygen. A 
massive leak will result in oxygen depletion, especially in 
basements, and an asphyxiation hazard will result in seri

-

ous injury or death.

•  Do not ground units to water pipes, gas pipes, telephone 

wires, or lightning rods as incomplete grounding will result 
a severe shock hazard resulting in severe injury or death. 
Additionally, grounding to gas pipes will result a gas leak 

and potential explosion resulting in severe injury or death.

•  If refrigerant gas leaks during installation, ventilate the 

area immediately. Refrigerant gas will result in producing 

toxic gas if it comes into contact with fire. Exposure to this 

gas will result in severe injury or death.

•  After completing the installation work, check that the re-

frigerant gas does not leak throughout the system.

• 

Do not install unit in an area where flammable materials 
are present due to risk of explosions that will result in seri

-

ous injury or death.

•  Safely dispose all packing and transportation materials 

in accordance with federal/state/local laws or ordinances. 
Packing materials such as nails and other metal or wood 
parts, including plastic packing materials used for trans-
portation will result in injuries or death by suffocation.

 WARNING

• 

Only qualified personnel must carry out the installation 

work. Installation must be done in accordance with this 
installation manual. Improper installation could result in 

water leakage, electric shock, or fire.

•  When installing the unit in a small room, take measures to 

keep the refrigerant concentration from exceeding allow

-

able safety limits. Excessive refrigerant leaks, in the event 

of an accident in a closed ambient space, could result in 

oxygen deficiency.

• 

Use only specified accessories and parts for installation 
work. Failure to use specified parts could result in water 
leakage, electric shocks, fire, or the unit falling.

•  Install the air conditioner or heat pump on a foundation 

strong enough that it can withstand the weight of the unit. 

A foundation of insufficient strength could result in the unit 

falling and causing injuries.

•  Take into account strong winds, typhoons, or earthquakes 

when installing. Improper installation could result in the 
unit falling and causing accidents.

•  Make sure that a separate power supply circuit is pro-

vided for this unit and that all electrical work is carried 

out by qualified personnel according to local, state and 
national regulations. An insufficient power supply capacity 

or improper electrical construction could result in electric 

shocks or fire.

• 

Make sure that all wiring is secured, that specified wires 
are used, and that no external forces act on the terminal 

connections or wires. Improper connections or installation 

could result in fire.

• 

When wiring, position the wires so that the control box 

cover can be securely fastened. Improper positioning of 

the control box cover could result in electric shocks, fire, or 

the terminals overheating.

•  Before touching electrical parts, turn off the unit. 
•  This equipment can be installed with a Ground-Fault Cir-

cuit Interrupter (GFCI). Although this is a recognized mea-
sure for additional protection, with the grounding system in 
North America, a dedicated GFCI is not necessary.

•  Securely fasten the unit terminal cover (panel). If the 

terminal cover/panel is not installed properly, dust or 

water may enter the outdoor unit and could result in fire or 

electric shock.

•  When installing or relocating the system, keep the refriger-

ant circuit free from substances other than the specified 

refrigerant (R410A) such as air. Any presence of air or oth-
er foreign substance in the refrigerant circuit could result 
in abnormal pressure rise or rupture, resulting in injury.

•  Do not change the setting of the protection devices. If the 

pressure switch, thermal switch, or other protection device 
is shorted and operated forcibly, or parts other than those 

specified by Daikin are used, fire or explosion could result.

01_EN_01_PL_3P734038-2.indd   1

01_EN_01_PL_3P734038-2.indd   1

2023/05/29   11:57:55

2023/05/29   11:57:55

Summary of Contents for RELQ72TBTJ Series

Page 1: ...the event of conflicting information the online instructions are to be used Veuillez visiter http www daikinac com content resources manuals pour obtenir la version la plus r cente des instructions d...

Page 2: ...tion work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric shock or fire When installing the unit in a small room take...

Page 3: ...ed either outdoors or indoors This unit is for indoor use Do not install the air conditioner or heat pump in the fol lowing locations a Where a mineral oil mist or oil spray or vapor is pro duced for...

Page 4: ...18 9 Field wiring 19 9 1 Power circuit safety device and cable requirements 20 9 2 Wiring connection example for whole system 20 9 3 Leading wire procedure 20 9 4 Transmission wiring connection proce...

Page 5: ...and right where RELQ 144 240 consists of multiple RELQ 72 120 single modules as indicated 72 96 120 RELQ72TBTJ TBYD TBYC 1 RELQ96TBTJ TBYD TBYC 1 RELQ120TBTJ TBYD TBYC 1 RELQ144TBTJ TBYD TBYC 2 RELQ1...

Page 6: ...TJ TBYD TBYC 168 312 NOTE Higher capacity than the above table can be selected this may affect heating and cooling capacity For additional information see technical engineering data 1 4 Scope of the m...

Page 7: ...he unit Installation location is flat to prevent vibrations and noise generation and to have sufficient stability The space around the unit is adequate for maintenance and servic ing refer to 5 2 Serv...

Page 8: ...lt in the unit turning over 4 2 Weather related precautions Be sure that the air inlet of the unit is not positioned towards the main wind direction Frontal wind will disturb the operation of the unit...

Page 9: ...the possibilities a b a c d a b a e d e c a b a e d f c a b a e b d c a b a e d f c 1 2 3 5 4 ABCD Sides along the installation site with obstacles Suction side A B C D A B 1 a 3 8 10 b 11 3 4 300 c...

Page 10: ...ngineering Data Book 6 Inspecting handling and unpacking the unit 6 1 Inspection At delivery the unit must be checked and any damage must be re ported immediately to the carrier s claims agent 6 2 Han...

Page 11: ...gth remains 13 16 in 20 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor units in the case of the multi system Se...

Page 12: ...ng work is complete do not under any circumstances open the stop valve until 9 Field wiring on page 19 and 12 Checking of device and installation conditions on page 25 are complete Do not use flux whe...

Page 13: ...Branch Selector units C Choose from the following table in accordance with the indoor unit total capacity connected downstream Do not let the connection pip ing exceed the refrigerant piping size chos...

Page 14: ...P25M33H9 KHRP25M33HA KHRP26M22H9 KHRP26M22HA maximum 4 indoor units or KHRP26M33H9 KHRP26M33HA maximum 8 indoor units 72 111 KHRP26M33H9 KHRP26M33HA 111 230 KHRP25M72H9 KHRP25M72HA KHRP26M72H9 KHRP26M...

Page 15: ...m to the below length when calculating an equivalent length to each indoor unit connected to BSF Q54T Total capacity of the indoor units to be connected down stream Equivalent length BSF4Q54T BSF6Q54T...

Page 16: ...he figure below referring to the table below Do not upsize the high low pressure gas pipe and the suction gas pipe Outdoor unit capacity type Liquid pipe Main pipe Upsize the liquid pipe First refrige...

Page 17: ...pe and lines that are not upsized should not be doubled a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p q r s 1640 ft 500 m 3 The actual piping length from each indoor units to the nearest refriger ant bran...

Page 18: ...m ad versely affects valves and compressors in the refrigerating system and prevents proper operation The Dry Nitrogen pressure should be set to 2 9 psi 0 02 MPa i e just enough so it can be felt on t...

Page 19: ...op valve Suction gas pipe stop value Protective plate Stop valves mounting plate High low pressure gas pipe stop valve 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool...

Page 20: ...ller field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor units system To connect the piping between outdoor units an optional multi connection piping kit BHFP2...

Page 21: ...eader so that it branches horizontally 2 Installation of the multi connection piping kit 1 B 1 C D 15 15 A C 4 3 4 in 120 mm D 19 11 16 in 500 mm Install the joints horizontally so that the caution la...

Page 22: ...lve Check for refrigerant leaks after tightening the service port cover 9 Field wiring NOTE All field wiring and components must be installed by a licensed elec trician and must comply with relevant l...

Page 23: ...RELQ96TBYD RELQ120TBYD RELQ144TBYD RELQ192TBYD RELQ240TBYD f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz f3 60Hz 460V 460V 460V 460V 460V 460V 28 1 39 8 43 4 28 1 28 1 39 8 39 8 43 4 43 4 35 45 50 35 35 45...

Page 24: ...ation work onsite settings and so on are done by operating the printed circuit board A1P of Master unit NOTE Do not connect the power wiring to terminals for the transmission wiring Doing so would des...

Page 25: ...ctions See the figure below Crimp style terminal Insulating sleeve Power wire For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the t...

Page 26: ...r the air tightness test Absolutely do not open the stop valve until the main power circuit insulation measurement has been completed Measuring after the stop valve is opened will cause the insulation...

Page 27: ...ns vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 500 microns or less vacuum drying If the system cannot be evacuated to 500 microns within 2 hours re...

Page 28: ...ccess you can remove the service window cover see figure Now you can open the inspection door of the control box cover see figure You can see 3 push buttons and 3 seven segment displays and DIP switch...

Page 29: ...cted to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function push BS1 one time you will return to the default situation...

Page 30: ...refrigerant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Page 31: ...2 Indoor units FXSQ type 12 2 FXMQ type 15 2 18 5 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft f f1 4 5 ft k f3 8 10 ft p f3 8 15 ft u f3 8 10 ft b f3 4 10 ft g f1 4 5 ft f3 8 10 ft q f1 4 10...

Page 32: ...it in gas form may cause the refrigerant composition to change preventing normal operation Before charging check whether the refrigerant cylinder is equipped with a siphon tube or not If a siphon tube...

Page 33: ...valve C Make sure that all outdoor unit stop valves as well as valves A and C are closed 1 2 3 4 5 6 B 9 8 11 11 12 10 14 13 15 16 A C 7 1 Pressure reducing valve 2 Nitrogen 3 Measuring instrument 4...

Page 34: ...the refrigerant Operating with the stop valves closed will damage the compressor 15 Start up and configuration INFORMATION It is important that all information in this chapter is read sequentially by...

Page 35: ...low noise operation based on an external input For this operation an optional acces sory is required 1 2 shows the status of power consumption limitation operation 1 unit is currently operating under...

Page 36: ...nal external control adaptor DTA104A61 62 is installed Default value 0 To activate this function change 2 12 1 2 18 Fan high static pressure setting In order to increase the static pressure the outdoo...

Page 37: ...or is required to perform power consumption limitation If the system always needs to run under power consump tion limitation conditions this setting activates and defines the level power consumption l...

Page 38: ...lt 2 Quick 3 Powerful Change 2 81 0 1 2 or 3 in function of required limitation This setting is used in conjunction with setting 2 8 and 2 47 In the case of 2 81 0 the original refrigerant temperature...

Page 39: ...X Heater is not allowed to energize when the outdoor ambient temp is recovered by differential below above the AUX Heater Max Allowable Temp AUX Heater Max Allowable temp Release differential Fahrenhe...

Page 40: ...ary or secondary heat source to be automatically energized in the event of a system failure Error codes capable of auto backup are listed in the table below Please be aware that the error codes that a...

Page 41: ...feeling for the customer The selection method of indoor units is important and has to be considered as the available capacity is not the same as under basic operation For details concerning to Hi sens...

Page 42: ...t from the indoor units becomes more moderate the system will eventually go to the steady state condition which is defined by the operation method above The start up condition is different from the po...

Page 43: ...air purge etc See installation manual of the Branch Selector units and the indoor units for details CAUTION Do not insert fingers rods or other objects into the air inlet or outlet When the fan is ro...

Page 44: ...pressor 4 Make sure the default idle situation is existing see 13 2 Operat ing the push buttons and DIP switches on the printed circuit board on page 25 Push BS2 for 5 seconds or more The unit will st...

Page 45: ...it board or actuator 31 36 Electronic expansion valve malfunction 208 230 460V Y6E A6P X10A 575V Y6E A7P X10A Check connection on printed circuit board or actuator 32 37 Electronic expansion valve mal...

Page 46: ...function open circuit S1NPL A1P X31A Check connection on printed circuit board or actuator 07 09 Low pressure sensor malfunction short circuit S1NPL A1P X31A Check connection on printed circuit board...

Page 47: ...ring to the wiring diagram for Branch Selector units and correct if there are any errors Check that the DIP switches settings are correct referring to the installation manual enclosed in Branch Selec...

Page 48: ...s due to strong wind it may store electricity in the capacitor or in the main circuit and cause electric shock 5 After the service is finished plug the junction connector back in Otherwise the malfunc...

Page 49: ...event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration level The maximum charge of refrigerant and the calculation of the max...

Page 50: ...3P734038 2 EM23A007 2311 SP Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P734038 2 indd 2 00_CV_3P734038 2 indd 2 2023 05 29 11 57 22 2023 05 29 11 57 22...

Reviews: