AG 31-011 • REFRIGERANT PIPING DESIGN 8
www.DaikinApplied.com
shows an indoor chiller with a remote air-cooled
condenser on the roof.
1. The discharge gas line runs from the discharge side of
the compressor to the inlet of the condenser.
2. The liquid line connects the outlet of the condenser to a
TX valve at the evaporator.
3.
The hot gas bypass line on the circuit runs from the
discharge line of the compressor to the liquid line
connection at the evaporator.
Figure 4: Indoor Chiller with Remote Air-cooled Condenser
Air Cooled
Condenser
Discharge line
inverted trap
(can be replaced
with a check valve)
Discharge
Line
Liquid
Line
Riser
Discharge
riser trap
only at base
Hot gas bypass
top connection
to avoid refrigerant
collection
Sight
Glass
TX
Valve
Solenoid
Valve
Filter-
Drier
Chiller