AG 31-011 • REFRIGERANT PIPING DESIGN 42 www.DaikinApplied.com
Table 7: R-22 Refrigerant Line Sizing (Tons)
Suction
Discharge
Liquid
SST
0°F
20°F
40°F
0°F
20°F
40°F
∆
T
2°F
1°F
0 .5°F
2°F
1°F
0 .5°F
2°F
1°F
0 .5°F
1°F
1°F
1°F
vel =
100 fpm
1°F
∆
p (PSI)
1 .60
0 .813
0 .406
2 .22
1 .104
0 .552
2 .91
1 .455
0 .727
3 .05
3 .05
3 .05
3 .05
OD (in .)
1/2
—
0.18
0.12
0.40
0.27
0.19
0.6
0.40
0.27
0.8
0.8
0.8
2.3
3.6
5/8
0.51
0.34
0.23
0.76
0.52
0.35
1.1
0.75
0.51
1.5
1.6
1.6
3.7
6.7
7/8
1.3
0.91
0.62
2.0
1.37
0.93
2.9
1.97
1.35
4.0
4.1
4.2
7.8
18.2
1-1/8
2.7
1.86
1.27
4.0
2.77
1.90
5.8
3.99
2.74
8.0
8.3
8.5
13.2
37.0
1-3/8
4.7
3.25
2.22
7.0
4.84
3.32
10.1
6.96
4.78
14.0
14.4
14.8
20.2
64.7
1-5/8
7.5
5.16
3.53
11.1
7.67
5.26
16.0
11.00
7.57
22.1
22.7
23.4
28.5
102.5
2-1/8
15.6
10.71
7.35
23.1
15.92
10.96
33.1
22.81
15.73
45.7
47.1
48.5
49.6
213.0
2-5/8
27.5
18.97
13.04
40.8
28.19
19.40
58.3
40.38
27.84
80.4
82.9
85.4
76.5
376.9
3-1/8
44.0
30.31
20.85
65.0
44.93
31.00
92.9
64.30
44.44
128.2
132.2
136.2
109.2
601.5
3-5/8
65.4
45.09
31.03
96.6
66.81
46.11
137.8
95.68
66.09
190.3
196.2
202.1
147.8
895.7
4-1/8
92.2
63.71
43.85
136.3
94.25
65.12
194.3
134.81
93.22
267.8
276.1
284.4
192.1
1263.2
ASHRAE Handbook Refrigeration, Chapter 2, 2006.
© American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.,
Values in
are based on 105°F condensing temperature. Multiply table capacities by the following factors for other
condensing temperatures.
Condensing
Temperature (°F)
Suction Line
Discharge Line
80
1.11
0.79
90
1.07
0.88
100
1.03
0.95
110
0.97
1.04
120
0.90
1.10
130
0.86
1.18
140
0.80
1.26
Notes for
:
1.
Table capacities are in tons of refrigeration.
2.
∆p = pressure drop due to line friction, psi per 100 ft of
equivalent line length
3.
∆t = corresponding change in saturation temperature,
°F per 100 ft
4. Line capacity for other saturation temperatures
∆
t and
equivalent lengths L
e
5. Saturation temperatures
∆
t for other capacities and
equivalent lengths L
e
Line Capacity = Table Capacity
Table L
e
Actual L
e
Actual
∆
t
Table
∆
t
0.55
R-22 Sizing — Notes
×
∆t = Table ∆t
Actual L
e
Table L
e
Actual Capacity
Table Capacity
1.8
×
Line Capacity = Table Capacity
Table L
e
Actual L
e
Actual
∆
t
Table
∆
t
0.55
R-22 Sizing — Notes
×
∆t = Table ∆t
Actual L
e
Table L
e
Actual Capacity
Table Capacity
1.8
×