6 Piping installation

Installation manual

9

CVXM-A, FVXM-A, CVXM-A9, FVXM-A9, FVXTM-A
Split system air conditioners
3P477070-2P – 2022.09

d

c

a

b

a

Drain pan

b

Drain socket

c

Drain hose (accessory)

d

Screw (accessory)

2

Check  for  water  leaks  (see 

"5.3.3  To  check  for  water

leaks"

 [

4

 9]).

3

Insulate  the  indoor  drain  socket  and  drain  hose  with  ≥10  mm
insulation material to prevent condensation.

4

Connect the drain piping to the drain hose. Insert the drain hose
≥50 mm, so it will not be pulled out of the drain pipe.

100

a

≥50

220

150

100

(mm)

c

d

b

a

a

Drain hose (accessory)

b

Vinyl chloride drain pipe (VP-30) (field supply)

c

Reducer (field supply)

d

Vinyl chloride drain pipe (VP-20) (field supply)

5.3.3

To check for water leaks

1

Remove the air filters.

2

Gradually pour approximately 1 l of water in the drain pan, and
check for water leaks.

6

Piping installation

6.1

Preparing refrigerant piping

6.1.1

Refrigerant piping requirements

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant piping.

INFORMATION

Additional  refrigerant  charge  is  NOT  allowed  in  case  of
combination of the outdoor unit 

3MXM40

 or 

3MXM52

 with

the indoor units 

CVXM-A

 and/or 

FVXM-A

. The total piping

length MUST be ≤30 m. For CVXM-A9 and FVXM-A9 refer
to 

"To determine the minimum floor area"

 [

4

 5].

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Class

Pipe outer diameter (mm)

Liquid piping

Gas piping

20~35

Ø6.4

Ø9.5

50

Ø6.4

Ø12.7

Refrigerant piping material

Piping material:

 phosphoric acid deoxidised seamless copper

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

6.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

Summary of Contents for Perfera CVXM20A3V1B

Page 1: ...on manual Split system air conditioners English Installation manual Split system air conditioners CVXM20A3V1B FVXM25A3V1B FVXM35A3V1B FVXM50A3V1B CVXM20A3V1B9 FVXM25A3V1B9 FVXM35A3V1B9 FVXM50A3V1B9 FV...

Page 2: ...wiring diagram legend 12 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin includ...

Page 3: ...y connecting the piping to the indoor units DANGER RISK OF BURNING SCALDING CAUTION Incomplete flaring may cause refrigerant gas leakage Do NOT re use flares Use new flares to prevent refrigerant gas...

Page 4: ...Industries Czech Republic s r o declares that the radio equipment type inside of this unit is in compliance with Directive 2014 53 EU and S I 2017 1206 Radio Equipment Regulations 2017 This unit is c...

Page 5: ...m m is not listed below use the closest higher value The total refrigerant charge m the minimum floor area is Amin limitation depends also on room height H and if the unit is installed ABOVE or UNDER...

Page 6: ...ole location f Right bottom piping hole location 1 Drill a wall hole depending on which side piping is taken out See 5 2 2 To drill a wall hole 48 2 Open the front panel and remove the front grille 3...

Page 7: ...4 30 f 734 740 170 350 70 200 593 595 170 350 d e c c a A B mm a a 75 5 4 60 60 5 4 75 C 159 238 689 159 b b 0 6 75 75 5 4 h g 627 5 115 285 b b b b 300 5 3 Indoor unit installation drawing Half conce...

Page 8: ...ont grille same on the other side c Slit portion for side piping on the bottom frame same of the other side d Slit portion for the bottom piping 1 Cut off the slit portion using nippers 2 Remove an bu...

Page 9: ...ic acid deoxidised seamless copper for refrigerant piping INFORMATION Additional refrigerant charge is NOT allowed in case of combination of the outdoor unit 3MXM40 or 3MXM52 with the indoor units CVX...

Page 10: ...tact point gaps that provides full disconnection under overvoltage category III WARNING If the supply cord is damaged it MUST be replaced by the manufacturer its service agent or similarly qualified p...

Page 11: ...n 1 After the drain piping refrigerant piping and the electrical wiring are finished Wrap the refrigerant pipes and the interconnection cable with insulation tape Overlap at least half the width of th...

Page 12: ...atically Caution When the main power is turned OFF and then back on again operation will resume automatically Notice Applicable for units with refrigerant leakage sensor only Notice Applicable for uni...

Page 13: ...S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch low S T Thermostat S RH Humidi...

Page 14: ......

Page 15: ......

Page 16: ...3P477070 2P 2022 09 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: