43
Speed selection tables
In order to select the correct step for the supply and return fan it is necessary to:
-Choose the table whose unit size number corresponds to the size indicated in the AED unit selection software report.
-Identify the steps of the supply/return fan, choosing from column H (high), the steps in which the RPM values are
closest to those indicated in the AED unit selection software report for the aforementioned fan.
-Set the values of the selected steps on the controller by going to the
Service settings
Field settings
path and
proceed with the following settings
a.
19(29)-2- Step_selected_ supply_fan
, for the Step of the supply fan, from 01 to 15
b.
19(29)-3- Step_selected_return_fan
, for the return fan Step, from 01 to 15
-If the RPM values for the supply and return fans are not present in column H but in column UH (very high), then:
-Set the initial fan speed to Very High by going to the
Service Settings
Field settings
path and changing the
default value from
17(27)-4-01
(High) to
17(27)-4-02
(Very high)
-Set the selection steps as indicated in step 3.
Step
Modular T Smart Size 03
Supply fan
Return fan
Heat recovery operation
Bypass operation
Heat recovery operation
By-pass operation
UH
(very
high)
H
(high)
L (low)
UH
H
L
UH
H
L
UH
H
L
Fan RPM
setting SA
(19(29)-2-…)
Fan RPM
setting EA
(19(29)-3-…)
01
2164
1803
951
2264
1828
1028
2390
2036
1282
2145
1763
951
02
2227
1868
1025
2324
1908
1093
2439
2095
1345
2202
1818
1008
03
2290
1939
1099
2384
1982
1162
2492
2159
1409
2259
1877
1065
04
2350
2005
1176
2443
2048
1225
2541
2217
1474
2316
1932
1122
05
2409
2071
1253
2503
2122
1290
2593
2276
1541
2370
1992
1178
06
2469
2127
1327
2566
2187
1359
2642
2323
1602
2425
2046
1236
07
2529
2187
1404
2626
2261
1423
2695
2375
1666
2476
2105
1293
08
2586
2245
1475
2685
2327
1489
2744
2422
1731
2531
2157
1352
09
2654
2310
1555
2754
2401
1572
2806
2479
1800
2593
2219
1424
10
2728
2367
1634
2825
2469
1657
2873
2529
1865
2657
2279
1499
11
2796
2416
1709
2894
2521
1734
2932
2573
1925
2717
2330
1565
12
2868
2472
1783
2965
2577
1817
2997
2626
1988
2781
2380
1640
13
2931
2524
1848
3033
2629
1891
3054
2670
2048
2841
2427
1706
14
2999
2583
1919
3104
2685
1957
3113
2721
2115
2908
2476
1775
15
3059
2632
1985
3170
2737
2016
3170
2763
2172
2964
2524
1828
The table refers to the indicated values, subject to tolerances.
To adjust the desired air flow value based on on-site measurements, you can increase the RPM to increase
the flow and decrease the RPM to reduce it. If necessary, slightly modify the fan speed in order to obtain
the desired air flow.
Summary of Contents for Modular T Smart ATB
Page 2: ......
Page 59: ...1 2 5 6 7 8 3 4 M5x20 59 19 Filter disassembly only for sizes 5 6 7...
Page 60: ...3 4 2 M5x20 1 60 20 Exchanger removal...
Page 63: ...63...
Page 65: ...65 Repair log DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 66: ...66 DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 67: ...67...