37
Commissioning
7
Configuration
The settings (format: XX(XX)-X-XX), for example 19(29)-1-02, used in this chapter, are made up of 3 parts,
separated by "-":
• Mode number: for example, 19(29), where 19 is the mode number for group settings, and 29 is the
mode number for individual settings
• Switch number: for example, 1
• Position number: for example, 02
Operating procedure
To adjust the settings of the ventilation unit for heat recovery, you can use the user interface of the Modular
L Smart unit or the air conditioner.
Initial settings
-Mode numbers 17, 18 and 19: Modular L Smart group control.
-Mode numbers 27, 28 and 29: individual control
Changing the settings with BRC1E53
Make sure that the doors of the switch boxes on the Modular L Smart unit are closed.
1. Briefly press a button to turn on the screen lighting.
2. Press and hold the Cancel button (a) for at least 4 seconds to enter the service Settings menu.
3. Navigate to Field Settings with the Up/Down buttons and press the Menu/Enter button (b).
4. Press the Left/Right buttons to highlight the number in Mode.
5. Press the Up/Down buttons to select the required mode number.
Result: Based on the number of mode selected, starting with 20, you will also have to select a
number of units for individual control.
6. Use the Left/Right buttons to highlight the number in Unit No.
7. Use the Up/Down buttons to select the internal unit number. It is NOT necessary to select a unit
number when configuring the entire group.
8. Use the Left/Right buttons to select a position number (0 to 15) for the switch number you want
to change.
In case of individual settings:
Field Settings
Unit No.
0
Mode
20
Setting
Return
Summary of Contents for Modular T Smart ATB
Page 2: ......
Page 59: ...1 2 5 6 7 8 3 4 M5x20 59 19 Filter disassembly only for sizes 5 6 7...
Page 60: ...3 4 2 M5x20 1 60 20 Exchanger removal...
Page 63: ...63...
Page 65: ...65 Repair log DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 66: ...66 DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 67: ...67...