![Daikin Modular T Smart ATB Installation, Use And Maintenance Manual Download Page 40](http://html1.mh-extra.com/html/daikin/modular-t-smart-atb/modular-t-smart-atb_installation-use-and-maintenance-manual_4701079040.webp)
40
Mode
setting
Switch
No.
setting
Setting description
Position No. setting
Position No. setting
01
02
03
04
05
06
07
08 09 10 11 12 13 14 15
17(27)
0
Filter scheduled clean-
ing setting
About 2500
hours
±1250
hours
1
Night free cooling
timer (after stop)
Off
On after 2
hours
On after 4
hours
On after 6
hours
On after
8 hours
2
Pre-cooling/pre-
heating
Off
On
3
Pre-cooling/pre-heat-
ing duration
30 minutes 45 minutes
60 min-
utes
4
Initial fan speed
High
Very high
5
Yes / No setting for
duct connection with
VRV system
Without
duct
With duct
Without
duct
With duct
Cold area setting (fan
operation when heater
thermostat is off)
Stop
Low
Stop
Low
6
Night free cooling (fan
settings)
High
Very high
7
Target temperature
for independent night
free cooling
18°C
19°C
20°C
21°C
22°C
23°C
24°C 25°C 26°C 27°C 28°C 29°C 30°C
8
Setting of interdependent
control device for central-
ized zones
No
Yes
9
Preheating time exten-
sion setting
0 minutes
30 minutes
60 min-
utes
90 min-
utes
Summary of Contents for Modular T Smart ATB
Page 2: ......
Page 59: ...1 2 5 6 7 8 3 4 M5x20 59 19 Filter disassembly only for sizes 5 6 7...
Page 60: ...3 4 2 M5x20 1 60 20 Exchanger removal...
Page 63: ...63...
Page 65: ...65 Repair log DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 66: ...66 DATE SERVICE TYPE TIME REQUIRED SIGNATURE...
Page 67: ...67...