Installation

www.DaikinApplied.com 

IM 1005-3 • MICROTECH III REMOTE USER INTERFACE

Wiring the Remote User Interface

Wiring the remote user interface to the MicroTech III unit 

controller can be done in two different ways:  

1.  Daisy-chain connection to as many as eight units.
2.  Direct connection to a single unit controller.

Connection and wiring instructions in each case are described 

in the following section. See 

Table 1

 for wire sizing and 

distance limitations.

NOTE: 

Power is supplied by the MicroTech III unit 

controller.  If a separate 24V power supply 

is desired, please contact either the Daikin 

Applied Air Technical Response Center at 844-

521-3928 (techresponseaah@daikinapplied.

com) or the Chiller Technical Response Center 

at 540-248-9239 (techresponse@daikinapplied.

com).

Table 1: Wiring Specifications

Daisy-Chain Connection

Establish a physical connection from the remote user 

interface to the MicroTech III unit controller. 

1.  Connect a twisted pair wire to the CE + and CE – pins  

of  each unit controller and remote user interface (see 

Figure 4

 and 

Figure 5

)

.

2.  Daisy-chain up to eight MicroTech III unit controllers to 

a single remote user interface. See 

Figure 5

 for wiring 

details. Note the wire size and distance limitations 

provided in 

Table 1.

3.  Cycle power to each MicroTech III unit controller once 

the wiring of the remote user interface is complete.

NOTE: 

Downloading and communication using the daisy-

chain connection may be slower than for the RJ45 

(Ethernet) direct connection.

Figure 4: Interface Details for Daisy-Chain Connection           

Bus connection

CE+, CE-, not interchangeable

Terminal

2-screw connector

Max. length

1000 ft (305 m)

Cable type

 

   Wiring distance up to 500 ft

Twisted pair, shielded cable 16 AWG

   Wiring distance between 500 - 1000 ft

Twisted pair, shielded cable 14 AWG

   Wiring distance over 1000 ft

Not currently supported. Contact the appropriate Daikin Applied Technical Response  

Center for assistance.

  Remote User Interface  Interior Bottom View

Summary of Contents for MicroTech III

Page 1: ...T SWP Rebel Commercial Packaged Rooftop Systems Model DPS Maverick II Commercial Packaged Rooftop Systems Models MPS Pathfinder Air Cooled Screw Chiller Models AWS AWV Trailblazer Air Cooled Scroll Co...

Page 2: ...n 5 Pre Installation 5 Location Considerations 5 Mounting Surfaces 5 Parts 5 Installation 5 Mounting 5 Wiring the Remote User Interface 7 Daisy Chain Connection 7 Direct Connection 8 Operator s Guide...

Page 3: ...nd MicroTech III from Daikin Applied Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representative go to www DaikinApplied com Hazardous Inform...

Page 4: ...onal power supply necessary Supports panel mounting and wall mounting Component Data General Figure 1 shows the details of the remote user interface hardware design The overall physical layout include...

Page 5: ...1934080031 2 Connectors using CE CE connection option 193410302 1 Note that part number 193408001 is no longer available 2 For daisy chaining unit controllers together a 2 pin connector PN 193410302 i...

Page 6: ...IM 1005 3 MICROTECH III REMOTE USER INTERFACE 6 www DaikinApplied com Installation Figure 2 Removing the Cover of remote user interface Figure 3 Wall and Surface Wiring Connections...

Page 7: ...user interface to the MicroTech III unit controller 1 Connect a twisted pair wire to the CE and CE pins of each unit controller and remote user interface see Figure 4 and Figure 5 2 Daisy chain up to...

Page 8: ...ed 3 Cycle power to the unit s once the wiring of the remote user interface is complete NOTE Power is supplied by the unit controller If a separate 24V power supply is desired please contact either th...

Page 9: ...age The left most position of the title line includes an up arrow to indicate there are pages above the currently displayed items a down arrow to indicate there are pages below the currently displayed...

Page 10: ...n multiple times or if the keypad display has been idle longer than the Password Timeout default 10 minutes The main password page provides access to enter a password access the Quick Menu view the cu...

Page 11: ...oller A status bar appears on the Downloading the Objects screen to indicate that the download is in process Figure 12 NOTE Refer to the Troubleshooting section if the remote user interface appears to...

Page 12: ...ware file POL12289 bin on the SD Card in the root directory with no other files 2 Insert the SD Card into the MicroTech III unit controller The unit controller must be powered up and running 3 Connect...

Page 13: ...ify that the unit controller has power Check wiring from the unit controller to the remote user interface NOTE Inputs and outputs are polarity sensitive Frequently Asked Questions 1 Is a separate 24V...

Page 14: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local Daikin Applied representativ...

Reviews: