OM 1263 • MICROTECH UNIT CONTROLLER 58 www .DaikinApplied .com
Operator’s Guide
Determining Cooling Capacity
Clg Capacity is a status item which indicates the percentage of
the unit maximum cooling capacity currently operating .
Determining Heat Capacity
Htg Capacity is a status item which indicates the percentage
of the unit maximum primary heating source that is currently
operating . On heat pump units this is the compressor heating
capacity .
Determining Supply Air Fan Capacity
SAF Speed is a status only item which indicates the supply
air fan capacity . 0-100% of maximum speed is indicated if the
unit is equipped with a variable volume supply air fan. 100% is
indicated if the supply fan is constant volume and is running .
Determining RF/EF Capacity
RF/EF capacity is a status only item which indicates the current
exhaust fan capacity . 0-100% of maximum speed is indicated if
the unit is equipped with a variable volume exhaust fan. 100% is
indicated if the exhaust fan is constant volume and is running .
Determining Outside Air Damper
Position
OAD/Econo Cap is a status only item which indicates the
current outdoor air damper or economizer valve position.
Determining System Mode
The system can be set up for local or remote modes .
Off
When the Net App Mode is set to “OFF,” the Unit Status is “Off
Net” and the unit is completely disabled, including unoccupied
heating (night set back) and unoccupied cooling (night set up)
operation .
Heat Only
When the Net App Mode is set to “Heat Only,” heating
operation is allowed to operate as required to maintain the
heating set points . Cooling operation is disabled (Cooling
Status is “Off Net”).
Cool Only
When the Net App Mode is set to “Cool Only,” cooling
operation is allowed to operate as required to maintain the
cooling set points . Heating operation is disabled (Heating
Status is “Off Net”).
Fan Only
When the Net App Mode is set to “Fan Only,” the fans are
allowed to operate but cooling and heating operation is
disabled (Cooling Status and Heating Status are “Off Net”).
Auto
When the Net App Mode is set to “Auto” heating and cooling
operation are allowed to operate as required to maintain the
heating and cooling set points .
OAT Lockout
On heat pump units, compressor heating (primary heat) is
disabled whenever the outdoor air temperature is below the
Low Outdoor Air Ambient Heating Lockout set point or above
the High Outdoor Air Ambient Heating Lockout set point .
Whenever the outdoor air temperature rises above the Low
Outdoor Air Ambient Heating Lockout set point or falls below
the High Outdoor Air Ambient Heating Lockout set point
by more than the Heating Lockout Differential, compressor
heating operation is re-enabled .
Supplemental heating (secondary heat) is disabled whenever
the outdoor air temperature is above the High Outdoor Air
Ambient Supplemental Heating Lockout Set Point . Whenever
the outdoor air temperature falls below the High Outdoor Air
Ambient Supplemental Heating Lockout Set Point by more
than the Heating Lockout Differential, supplemental heating
operation is re-enabled .
Compressor cooling operation is disabled whenever the
outdoor air temperature falls below the Low Outdoor Air
Ambient Cooling Lockout Set Point . Whenever the outdoor
air temperature rises above the Low Outdoor Air Ambient
Cooling Lockout Set Point by more than the Cooling Lockout
Differential, compressor cooling operation is re-enabled.
On non-heat pump units, heating is disabled whenever
the outdoor air temperature is above the High Outdoor Air
Ambient Heating Lockout Set Point . Whenever the outdoor
air temperature falls below the High Outdoor Air Ambient
Heating Lockout Set Point by more than the Heating Lockout
Differential, heating operation is re-enabled.
Compressor cooling operation is disabled whenever the
outdoor air temperature falls below the Low Outdoor Air
Ambient Cooling Lockout Set Point . Whenever the outdoor
air temperature rises above the Low Outdoor Air Ambient
Cooling Lockout Set Point by more than the Cooling Lockout
Differential, compressor cooling operation is re-enabled
.