OM 1263 • MICROTECH UNIT CONTROLLER 24 www .DaikinApplied .com
Commission Unit
Inverter Compressor Set-Up
(
See page 51 — 56 for more information)
Table 13: Inverter Compressor Set Up Menu
Item Display
Name
Default Setting
Range
Password Level
Compressor Status
Clg State=
—
Off
4
Start
Init
Normal
Pumpdn
Standby
Htg State=
—
Off
4
Start
Init
Normal
Pumpdn
Standby
INV Cmp Spd=
—
0 – 100%
4
INV Spd Cmd=
—
0 – 100%
4
VCmpOilStatus=
—
Open
2
Closed
Comp 3=
—
Off
4
On
Fault Code Details
INV Port Temp=
—
-50 .0 – 200 .0°F
2
INV Fin Temp=
—
-50 .0 – 200 .0°F
2
INV Amps=
—
0 – 50A
4
Ctrl Card Tmp=
—
-50 .0 – 200 .0°F
2
Heatsink Tmp=
—
-50 .0 – 200 .0°F
2
Refrig Circuit Status
PTD=
—
0 – 5000kPa
4
PTS=
—
0 – 5000kPa
4
4 WayValve=
—
Cool
2
Heat
RcvrSol Valve=
—
Closed
2
Open
BP Sol Valve=
—
Closed
2
Open
Item Display
Name
Default Setting
Range
Password Level
Compressor Setup
Clg Stg Time=
5min
3 – 60min
4
Clg Lo OAT Lk=
55°F (RTU/SCU)
0 – 100°F
4
0°F (MPS)
25°F (DPS)
Clg OAT Diff=
2°F
0 – 10°F
4
Htg Lo OAT Lk=
0°F
-20 – 50°F
4
45°F (100% OA
w/o ER)
Htg Hi OAT Lk=
55°F
0 – 100°F
4
EffHtgHiOATLk=
—
0 – 100°F
4
Htg OAT Diff=
2°F
0 – 10°F
4
INV Period=
20s
1 – 300s
4
INV Gain=
2
0 .0 – 100 .0
4
INV PAT=
60s
0 – 999s
4
INV Max Chg=
15%
0 – 50%
4
OilManagement=
Off
Off
2
Balance
LoBoost
HiBoost
Boost
LowOilTime=
10m
1 – 30m
2
OilBoostTime=
10m
1 – 15m
2
VFD Status=
—
OK
2
OvrTActv
WrnActv
AlmNoTrp
AlmTrp
TripLck
NoComm
VFD Alm/Wrn=
—
None
2
A** – W**
IFB Comm Status (10010)