Table 2: Quick Menu
Menu Display Name
Default Setting
Range
Password Level
System Mode
Local
Local/Remote
6
Heat/Cool In
Heat/Cool
Heat/Cool
6
CmpIntrLock
—
Open/Closed
6
Dehum Status
—
Active/Inactive
6
Clg Capacity
—
0 – 100%
None
OAD/Econo Cap
—
0 – 100%
None
Htg Capacity
—
0 – 100%
None
Reheat Capacity
—
0 – 100%
None
SAF Speed
—
0 – 100%
None
RF/EF Cap
—
0 – 100%
None
OA Temp
—
-50 .0 – 200 .0°F
None
System Mode
is an adjustable item that sets the status for
the for the unit to run on local with field inputs are ignored or
remote where operation is based on field inputs
Heat/Cool In
is an adjustable item that only applicable
on heatpump units to determine DX cooling or heatpump
operation
CmpInterLock
is an adjustable input safety that can be used
to prevent compressor operation based on external system
safeties
Dehum Status
is a status only item which indicates the status
of operation of the dehumidifier. The dehumidifier can be active
or inactive .
Clg Capacity
is a status only item which indicates the
percentage of the unit maximum cooling capacity currently
operating .
OAD/Econo Cap
is a status only item which indicates the
percentage that the outdoor damper or economizer valve is
currently open .
Htg Capacity
is a status only item which indicates the
percentage of the unit maximum heating capacity currently
operating .
Reheat Capacity
is a status only item which indicates the
percentage of the unit maximum reheat capacity currently
operating .
SAF Capacity
is a status only item which indicates the
capacity of the supply air fan .
RF/EF Capacity
is a status only item indicating the capacity of
the return fan/exhaust air fans .
OA Temp
is a status only item which displays the current
temperature reading from the unit mounted outdoor air
temperature sensor . This sensor is standard on all units .
Summary of Contents for MicroTech III DPS