Appendix
www.DaikinApplied.com 39
IM 1285-4 • MICROTECH III
Figure 30 continued: ATV 212 (MD2) Drive Parameters
PART NUMBER
REV
PART DESCRIPTION
170632000
B
Rooftop - MT3 SAF (set 321) PARAMETERS
Drive
Voltage
HP
Application
ATV21
ALL
ALL
SAF/RAF, RT/SC
Code
Function Description
Unit
Min. Value
Max. Value
Default
Value
New Value
Logical
Address
F706
Free unit display bias
0.01Hz
0,00
80,00
0
706
F707
Free step 1 (pressing a panel key once)
0.01Hz
0,00
80,00
0
707
F708
Free step 2 (panel display)
1
0
255
0
708
F710
Standard monitor display selection
1
0
10
0
710
F721
Panel stop pattern
1
0
1
0
721
F730
Prohibition of freq. setting on the operation panel (FC)
1
0
1
0
730
F732
Panel operation prohibition (Local/Remote keys)
1
0
1
0
1
732
F733
Panel operation prohibition (RUN/STOP keys)
1
0
1
0
733
F734
Prohibition of panel emergency stop operation
1
0
1
0
734
F735
Prohibition of panel reset operation
1
0
1
0
735
F738
Selection of AUF
1
0
1
0
738
F748
Selection of watt hour memory
1
0
1
1
748
F749
Display unit selection of watt hour
1
0
3
0
749
F800
Communication band speed
1
0
1
1
800
F801
Parity
1
0
2
1
=0; McQuay
801
F802
Inverter number; SAF=1;RAF=2;HW=3
1
0
247
1
=1;McQuay
802
F803
Communication error trip time
1sec
0
100
3
10
803
F805
Communication waiting time
0.01sec
0,00
2,00
0
805
F806
Setting master & slave for comm between inverters
1
0
4
0
806
F811
Communication input point 1 setting
1%
0
100
0
811
F812
Communication input point 1 frequency
0.01Hz
0,00
200,00
0
812
F813
Communication input point 2 setting
1%
0
100
100
813
F814
Communication input point 2 frequency
0.01Hz
0,00
200,00
0
=60;McQuay
814
F829
Selection of communication protocol
1
0
4
1
829
F851
Inverter action at network & communication break
1
0
4
4
0
851
F856
Number of motor poles for comm speed calculation
1
1
8
2
856
F870
Block write data 1
1
0
6
0
870
F871
Block write data 2
1
0
6
0
871
F875
Block read data 1
1
0
11
0
875
F876
Block read data 2
1
0
11
0
876
F877
Block read data 3
1
0
11
0
877
F878
Block read data 4
1
0
11
0
878
F879
Block read data 5
1
0
11
0
879
F880
Free notes
1
0
65535
0
321
880
F890
Parameter for option 1
1
0
65535
0
890
F891
Parameter for option 2
1
0
65535
0
891
F892
Parameter for option 3
1
0
65535
0
892
F893
Parameter for option 4
1
0
65535
0
893
F894
Parameter for option 5
1
0
65535
0
894
F895
Parameter for option 6
1
0
65535
0
895
F896
Parameter for option 7
1
0
65535
0
896
F897
Parameter for option 8
1
0
65535
0
897
F898
Parameter for option 9
1
0
65535
0
898
F899
Parameter for option 10
1
0
65535
0
899
F910
Step-out detection current level (for PM motors)
1%
10
150
100
910
F911
Step-out detection time (for PM motors)
0.1sec
0,0
25,0
0.0
911
F912
q-axis self-inductance (for PM)
0.01mH
0,00
650,00
0.00
912
ATV21 MT3 SAF PAGE 4