Appendix
www.DaikinApplied.com 33
IM 1285-4 • MICROTECH III
Table 5: ACH580 Parameters
MD5 Parameters
#
Name
Unit
VALUE
GROUP 96 - SYSTEM
96.04 MACRO SELECT
HVAC DEFAULT
GROUP 99 - MOTOR DATA
99.06 MOTOR NOM CURR
A
Motor Specific
99.07 MOTOR NOM VOLT
V
Motor Specific
99.09 MOTOR NOM SPEED
RPM
Motor Specific
99.10 MOTOR NOM POWER
HP
Motor Specific
GROUP 12 - STANDARD AI
12.15 AI1 UNIT SELECTION
MA
12.19 AI1 SCALED ATAI1 MIN
200
12.20 AI1 SCALED AT AI1 MAX
1000
12.25 AI2 UNIT SELECTION
MA
12.29 AI2 SCALED AT AI2 MIN
200
12.30 AI2 SCALED AT AI2 MAX
1000
GROUP 20 - START/STOP/DIR
20.01 EXT1 COMMANDS
EMBEDDED FIELDBUS
20.21 DIRECTION
FORWARD
20.41 START INTERLOCK 1
NOT USED
20.42 START INTERLOCK 2
NOT USED
GROUP 22 - REFERENCE SELECT
22.11 EXT SPEED REF1
EFB REF1
22.22 CONSTANT SPEED SEL1
ALWAYS OFF
22.41 SPEED REF SAFE
RPM
0
GROUP 28 - FREQUENCY REFERENCE CHAIN
28.11 EXT1 FREQUENCY REF1
EFB REF1
28.22 CONSTANT FREQ SEL1
ALWAYS OFF
28.41 FREQUENCY REF SAFE
Hz
0
28.72 FREQ ACCELERATION TIME 1
S
60
28.73 FREQ DECELERATION TIME 1
S
60
GROUP 31 - FAULT FUNCTIONS
31.01
External Event 1 Source
DI2
31.14 NUMBER OF TRIALS
5
31.16 DELAY TIME
S
3
31.27 STALL FREQUENCY LIMIT
Hz
45
31.25 AR OVERCURRENT
ENABLE
GROUP 46 - MONITOR / SCALING SETTINGS
46.02 FREQUENCY SCALING
1000
GROUP 58 - EMBEDDED FILEDBUS
58.01 PROTOCOL ENABLE
MODBUS RTU
58.03 NODE ADDRESS
1 (SAF) or 2 (RF/EF)
58.04 BAUD RATE
19.2 KBPS
58.05 PARITY
8 NONE 2
58.14 COMMUNICATION LOSS ACTION
SPEED REF SAFE
58.15 COMMUNICATION LOSS MODE
CW/REF1/REF2
58.16 COMMUNICATION LOSS TIME
S
25.0 S
58.33 ADDRESSING MODE
MODE0
GROUP 71 - EXTERNAL PID1
71.32 GAIN
1.00
71.33 INTEGRATION TIME
S
2155
GROUP 97 - MOTOR CONTROL
97.20 U/F RATIO
LINEAR
58.06 Communication Control
Enabled