Table 28: Controller, Digital Outputs
#
Description
Load
Output OFF
Output ON
1
Evaporator Water Pump #1
Pump Contactor
Pump OFF
Pump ON
2
Evaporator Water Pump #2
Pump Contactor
Pump OFF
Pump ON
3
Condenser Water Pump #1
Pump Contactor
Pump OFF
Pump ON
4
Condenser Water Pump #2
Pump Contactor
Pump OFF
Pump ON
5
Tower Fan #1
Fan Contactor
Fan OFF
Fan ON
6
Tower Fan #2
Fan Contactor
Fan OFF
Fan ON
7
Expansion Valve Calibration
Digital Input (50K Ohms)
Normal
Calibration
8
Alarm
Alarm Indicator
Alarm OFF
Alarm ON
9
Tower Fan #3
Fan Contactor
Fan OFF
Fan ON
10
Tower Fan #4
Fan Contactor
Fan OFF
Fan ON
11
Alarm Output
User Defined
Alarm OFF
Alarm ON
Controller Setpoints
groups setpoints that relate to the entire unit operation and are stored in the controller. For a complete list of setpoints,
.Standard settings are made through the HMI. The Password (PW) column indicates the
password that must be active in order to change the setpoint. The letters in the Password column refer to the following:
O
= Operator (the password number for operator level is 100)
M
= Manager (the password number for manager level is 2001)
T
= Technician (the password number for technician level is only provided to Daikin Applied technicians)
Table 29: Controller Setpoints
Description
Default
Range
PW
Unit
Unit Enable
OFF
OFF, ON
O
Control Source
SWITCHES
Switches, Local (Touch Screen), BAS Network
O
Display Units
°F/psi
°F/psi, °C/kPa
O
Language
ENGLISH
ENGLISH, (TBD)
O
BAS Protocol
Modbus
NONE, BACnet, LonWorks, Modbus
M
Motor Amps
Demand Limit
OFF
OFF, ON
M
Minimum Amps
3%
1 to 80%
M
Maximum Amps
100%
10 to 100%
M
Soft Load
OFF
OFF, ON
M
Begin Amp Limit
20%
10 to 100%
M
Soft Load Ramp
5 min
1 to 60 min
M
Maximum Rate
1.0 °F/min
0.1 to 5.0 °F/min
M
Minimum Rate
0.4 °F/min
0.1 to 5.0 °F/min
M
Staging
Mode
Pump
Normal, Efficiency, Pump, Standby
M
Sequence #
1
1,2, … (# of Compressors)
M
Maximum Compressors ON
2
1-16
M
Stage Delta T
1.0 °F
0 to 9.9 °F
M
Nominal Capacity
100 Tons
0 to 2000 Tons
T
NOTE:
continues onto the following pages.