4. DEHUMIDIFICATION CONTROL SETTING
This unit features the dehumidification function. Therefore, it is necessary to set whether the
dehumidification control is to be executed or not according to the cargo to be transferred.
You can set whether the dehumidification control is to be executed or not by operating the display
panel of controller.
4.1 Description of setting
Whether the dehumidification control is to be executed or not is switched over according to the setting
of dehumidification control parameter "dHu" under the "7. G-SET operation / Automatic pump down
operation mode / Dehumidification ON-A
・
OFF setting"
CAUTION
1
.
ON/OFF of the reheating coil and DE-HUMID LED lit/unlit are not
synchronous.
2
.
To apply the humidification control, be sure to set "ON-A".
Dehumidification
control
Setting of
dehumidification
control "dHu"
DE-HUMID LED
Remarks
To execute
ON-A (Applied)
ON
Case of the unit without the
humidity sensor
Note) If the following conditions
are both satisfied, the
dehumidification control
will automatically be set to
"OFF" (dehumidification
control clearing function).
¡
The "dHU-CAN" is set to ON.
¡
48 hours or more lapsed after
the main unit power supply
turned OFF.
Not to execute
off (Not applied)
OFF
Note) The dehumidification control clearing function is a function to automatically change the
setting of dehumidification control to OFF if the main unit power supply turns OFF for a
period of 48 hours or more. The ON/OFF setting of the dehumidification control clearing
function "dHU-CAN" is made while in optional function setting mode. For details of setting
procedure, refer to information (on page 15). The setting of dehumidification control "dHU"
can also be made while in optional function setting mode.
P001-028̲S/G-A4 英(LEX10E-A18A) 2006.04.21 20:17 ページ 11
https://daikin-p.ru
Summary of Contents for LXE10E-A18A
Page 30: ...15 APPENDIX 15 1 Refrigerant piping diagram 29 https daikin p ru ...
Page 33: ...32 https daikin p ru ...
Page 38: ...37 1 部品名称 1 1 庫外側 q レヒートコイル電磁弁 Trans FRESH RSV DSV BSV HSV ESV ISV 1 https daikin p ru ...
Page 39: ...38 1 2 庫内側 1 3 2 q レヒートコイル w USDAレセプタクル e パソコンポートレセプタクル https daikin p ru ...
Page 61: ...60 CA装置取付位置例 庫内側 Trans FRESH ASS Y A4 A5 CABLES W MOUNTING BOX q https daikin p ru ...
Page 62: ...15 付図 15 1 配管系統図 61 https daikin p ru ...
Page 65: ...64 https daikin p ru ...
Page 69: ...Parts related with the unit outside 庫外関連部品 68 TR05 09A https daikin p ru ...
Page 73: ...Parts related with refrigerant piping outside 庫外冷媒配管関連部品 72 TR05 09A https daikin p ru ...
Page 77: ...Parts related with the unit inside 庫内関連部品 76 TR05 09A https daikin p ru ...
Page 81: ...Parts related with refrigerant piping inside 庫内冷媒配管関連部品 80 TR05 09A https daikin p ru ...
Page 91: ...Control box コントローラボックス 90 TR05 09A https daikin p ru ...
Page 92: ... 91 TR05 09A Control box コントローラボックス https daikin p ru ...
Page 95: ...Parts related with name plate 銘板関連 94 TR05 09A https daikin p ru ...
Page 96: ...Parts related with name plate 銘板関連 95 TR05 09A https daikin p ru ...
Page 99: ...Parts related with option 1 Recorder box オプション関連部品1 レコーダボックス 98 TR05 09A https daikin p ru ...
Page 105: ...Storage for power cable ケーブル収納 104 TR05 09A https daikin p ru ...
Page 107: ...Parts related with option 4 TRANS FLESH オプション関連部品4 トランス フレッシュ 106 TR05 09A https daikin p ru ...
Page 119: ...MEMO https daikin p ru ...