3. DEFROSTING OPERATION
(1) Defrosting system
A hot-gas defrost system is adopted in the units; i.e. the high temperature and high pressure refrigerant
(hot gas) from the compressor is sent to the evaporator and drain pan for defrosting. Since the evaporator
is heated directly by the hot gas (refrigerant), defrosting can be performed effectively.
(2) Defrosting initiation
Defrosting is initiated by the timer or the manual defrost key.
However, defrosting is not initiated when frosting on the evaporator can not be detected.
¡
Evaporator inlet temperature : 5˚C or higher (during chilled operation)
¡
Evaporator outlet temperature : 20˚C or higher
q
Initiation by timer (Timer is set at the electronic controller, refer to section 3.3.2 of service manual for its
operating method.)
※
1. On-demand defrost selection (12 hours for Frozen mode and 6 hours automatic for Chilled mode)
※
2. 6 hours when the control temperature is –20˚C or below.
w
Starting by MANUAL DEFROST key (on the operation panel sheet key)
Press the MANUAL DEFROST key, then press the ENTER/ESC key while indicate "ON" on the LED
display. The manual defrosting operation starts.
e
Initiation by frost detection
If the suction air temperature does not drop at the speed of 0.2˚C/1hr during frozen pull-down
operation, defrosting will be initiated because it is judged that frost is formed on the evaporator.
However, if the suction temperature is –20˚C or lower, defrosting will not be initiated. (activated)
(3) On demand defrost setting
When "99" in long timer is selected, defrosting is activated upon the condition of frost on evaporator
coil. This function is only for Frozen setting (SP < –10.1 deg C). and starting with 12 hours.
(If this function is selected for chilled setting, defrost initiates every 6 hours automatically.)
Procedure:
Step 1: After defrost, the controller records compressor running time for 1
st
1 hour. (T1)
Step 2: When 12 hours passed after defrost, controller records compressor running time for last 1
hour (T2). And the controller check whether the below condition is satisfied.
Step 3: If the above condition is satisfied, defrost is activated.
If above condition is not satisfied, defrost is postponed another one hour.
After counting up 13 hours, then repeat "Step 2".
Defrost will be postponed every one hour until the above condition (Step 2) is satisfied.
(Max. 24 hours)
T2 > T1
×
1.15
Type of timer
Defrosting interval set
Function
Long timer
3, 6, 9, 12, 24 and 99
※
1
hours are
selectable
Optional function setting mode:
If the"AUT-INT"is set to ON, the set time
may be changed. For details, refer to
information in
"
defrosting interval automatic
changing function
"
(on page 10).
Regardless of the control temperature,
defrosting is initiated according to the
selected interval.
Short timer
4 hours
※
2
Defrosting is initiated every 4 hours until the
control temperature comes within the in-
range after pull-down.
Out-range timer
30 minutes
After the control temperature comes within
in-range once, defrosting will be started 30
minutes later if the control temperature
rises out of the in-range.
P001-028̲S/G-A4 英(LEX10E-A18A) 2006.04.21 20:17 ページ 9
https://daikin-p.ru
Summary of Contents for LXE10E-A18A
Page 30: ...15 APPENDIX 15 1 Refrigerant piping diagram 29 https daikin p ru ...
Page 33: ...32 https daikin p ru ...
Page 38: ...37 1 部品名称 1 1 庫外側 q レヒートコイル電磁弁 Trans FRESH RSV DSV BSV HSV ESV ISV 1 https daikin p ru ...
Page 39: ...38 1 2 庫内側 1 3 2 q レヒートコイル w USDAレセプタクル e パソコンポートレセプタクル https daikin p ru ...
Page 61: ...60 CA装置取付位置例 庫内側 Trans FRESH ASS Y A4 A5 CABLES W MOUNTING BOX q https daikin p ru ...
Page 62: ...15 付図 15 1 配管系統図 61 https daikin p ru ...
Page 65: ...64 https daikin p ru ...
Page 69: ...Parts related with the unit outside 庫外関連部品 68 TR05 09A https daikin p ru ...
Page 73: ...Parts related with refrigerant piping outside 庫外冷媒配管関連部品 72 TR05 09A https daikin p ru ...
Page 77: ...Parts related with the unit inside 庫内関連部品 76 TR05 09A https daikin p ru ...
Page 81: ...Parts related with refrigerant piping inside 庫内冷媒配管関連部品 80 TR05 09A https daikin p ru ...
Page 91: ...Control box コントローラボックス 90 TR05 09A https daikin p ru ...
Page 92: ... 91 TR05 09A Control box コントローラボックス https daikin p ru ...
Page 95: ...Parts related with name plate 銘板関連 94 TR05 09A https daikin p ru ...
Page 96: ...Parts related with name plate 銘板関連 95 TR05 09A https daikin p ru ...
Page 99: ...Parts related with option 1 Recorder box オプション関連部品1 レコーダボックス 98 TR05 09A https daikin p ru ...
Page 105: ...Storage for power cable ケーブル収納 104 TR05 09A https daikin p ru ...
Page 107: ...Parts related with option 4 TRANS FLESH オプション関連部品4 トランス フレッシュ 106 TR05 09A https daikin p ru ...
Page 119: ...MEMO https daikin p ru ...