11 About the units and options

Installation and operation manual

11

LRYELRNUN5A7Y1
CO

 Conveni-Pack outdoor unit and capacity up unit

4P605461-1 – 2020.04

a

b

a

Outdoor unit

b

Capacity up unit

WARNING

Tear apart and throw away plastic packaging bags so that
nobody,  especially  children,  can  play  with  them.  Possible
risk: suffocation.

10.1.2

To handle the outdoor unit

CAUTION

To  avoid  injury,  do  NOT  touch  the  air  inlet  or  aluminium
fins of the unit.

Crane

Lift  the  outdoor  unit  preferably  with  a  crane  and  2  belts  of  at  least
8  m  long  as  shown  in  the  figure  below.  Always  use  protectors  to
prevent belt damage and pay attention to the centre of gravity of the
unit.

a

b

a

Outdoor unit

b

Capacity up unit

NOTICE

Use a belt sling of ≤20 mm wide that adequately bears the
weight of the unit.

Forklift

a

b

a

Outdoor unit

b

Capacity up unit

NOTICE

Use filler cloth on the forklift arms to prevent damage to the
unit. Damage to the painting of the unit decreases the anti-
corrosion protection.

10.1.3

To remove the accessories from the
outdoor unit

Outdoor unit

c

d

a

b

a

General safety precautions

b

Operation and installation manual

c

Copper packings for stop valve caps (15×)

d

Copper packings for service port caps (15×)

Capacity up unit

a

a

Declaration of conformity

11

About the units and options

11.1

About the outdoor unit

This  installation  manual  concerns  the  outdoor  unit  and  the  optional
capacity up unit.

These units are intended for outdoor installation and aimed for air to
air heating, cooling and refrigeration applications.

Summary of Contents for LRYEN10A7Y1

Page 1: ...Installation and operation manual CO Conveni Pack outdoor unit and capacity up unit English Installation and operation manual CO Conveni Pack outdoor unit and capacity up unit LRYEN10A7Y1 LRNUN5A7Y1...

Page 2: ...mm 300 500 500 10 B B1 B2 B3 100 500 500 50 300 200 a a C1 C2 C3 C a 300 500 20 10 50 100 500 100 300 400 200 a A Y X h2 H2 500 h1 H1 1500 1...

Page 3: ...and service ports 19 13 2 1 To handle the stop valve 19 13 2 2 To handle the service port 20 13 2 3 Tightening torques 21 13 3 Connecting the refrigerant piping 21 13 3 1 To remove the spun pipes 21...

Page 4: ...from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable standard I...

Page 5: ...tar system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor because this unit is equipped with an inverter A phase advancing capacitor will reduce perform...

Page 6: ...bol This means that the batteries may NOT be mixed with unsorted household waste If a chemical symbol is printed beneath the symbol this chemical symbol means that the battery contains a heavy metal a...

Page 7: ...e executing any maintenance task WARNING Never replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or...

Page 8: ...instruments or works of art NOTICE Do NOT use the system for cooling water It may freeze NOTICE For future modifications or expansions of your system A full overview of allowable combinations for futu...

Page 9: ...Phase diagram of R744 P bar T C 0 31 100 80 1 5 2 73 8 57 d c b a e P Pressure in bar T Temperature in C a Solid phase b Liquid phase c Vapour phase d Supercritical fluid e Triple point 57 C 5 2 bar 6...

Page 10: ...ge Restart the unit by switching operating switch OFF and ON If the problem persists refer to the service manual The stop valve of an outdoor unit is left closed Open the stop valve on both the gas an...

Page 11: ...unit a b a Outdoor unit b Capacity up unit NOTICE Use a belt sling of 20 mm wide that adequately bears the weight of the unit Forklift a b a Outdoor unit b Capacity up unit NOTICE Use filler cloth on...

Page 12: ...your dealer for assistance WARNING Only the refrigeration parts that are also designed to work with CO2 shall be connected to the system Individual control with a remote controller In case of a system...

Page 13: ...alculations see the reference guide of the indoor unit Appropriate measures INFORMATION Appropriate measures are field supply Choose and install all required appropriate measures in accordance with EN...

Page 14: ...echanical ventilation in accordance with EN 378 3 2016 12 2 Opening and closing the unit 12 2 1 To open the outdoor unit DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING To gain access to...

Page 15: ...it b Capacity up unit 3 Attach the small front plates to the front panels a b 2 7 a Outdoor unit b Capacity up unit 12 3 Mounting the outdoor unit 12 3 1 To provide the installation structure Make sur...

Page 16: ...n bolts M12 It is best to screw in the foundation bolts until their length remains 20 mm above the foundation surface 20 mm NOTICE Prepare a water drainage channel around the foundation to drain waste...

Page 17: ...ion 13 1 2 Refrigerant piping material Piping material K65 copper iron alloy CuFe2P maximum operating pressure 120 bar Piping temper grade and thickness Piping refrigeration unit Piping type Outer dia...

Page 18: ...easily a c b a Showcase b Height difference 5 m c Trap The refrigerant suction piping must always run down a b a b a Outdoor unit or indoor unit b Flow direction in refrigerant suction piping To inst...

Page 19: ...15 9 t1 05 K65 Air conditioner side liquid pipe b 12 7 t0 85 K65 Air conditioner side gas pipe b 15 9 t1 05 K65 a Piping between branching areas C D c d b Piping from first branch to second branch B2...

Page 20: ...te and freeze between the screw thread As a result refrigerant may leak and the valve cap may break a b a Apply screw lock agent b Do NOT apply screw lock agent 5 Tighten the valve cap Also see 13 2 3...

Page 21: ...ese instructions are NOT followed correctly it may result in property damage or personal injury which may be serious depending on the circumstances To remove the spun piping 1 Open the stop valve cap...

Page 22: ...p valve gas refrigeration B Stop valve liquid refrigeration a Gas piping b Liquid piping 2 If applicable remove the knockout and connect the piping to the capacity up unit Side connection 3 Remove the...

Page 23: ...to withstand high pressures and which will prevent water dirt or dust entering the unit CAUTION Do NOT open the stop valve until you have measured the insulation resistance of the main power supply ci...

Page 24: ...th 20 mm Insulation sealing To prevent rain and condensed water entering the unit add a sealing between the insulation and the front panel of the unit a a a a b b a Sealing material b Front panel 14 C...

Page 25: ...4 the additional amount of refrigerant during test run 6 and the factory charged amount of refrigerant 5 see label on the unit The total amount of refrigerant in the system is thus 4 5 6 7 10 Note do...

Page 26: ...kg 5 Factory charged amount of refrigerant into outdoor unit kg 6 3 6 Additional amount of refrigerant charged when test run if required kg a 7 Total amount of refrigerant 5 6 7 kg 8 a The maximum amo...

Page 27: ...consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax EN IEC 61000 3 12 provided tha...

Page 28: ...d1 d2 h h1 h2 d1 d2 X1M A1P X5M X4M X1M PE X1M X3M PE X1M A1P X2M X1M X3M PE k1 k l m k2 k4 k3 j 3N 50 Hz 380 415 V AC c1 c2 3N 50 Hz 380 415 V AC c1 c2 c1 c2 1N 50 Hz 220 240 V AC c1 c2 k5 a Capacity...

Page 29: ...b X5M X4M X1M PE X1M A1P X2M X1M X3M PE a Terminals on outdoor unit b Terminals on capacity up unit Terminal Screw size Tightening torque N m X1M Power supply M8 5 5 7 3 PE Protective earth screw M8...

Page 30: ...fixing b F2 F1 F1 X1M A1P c a F2 Q1 Q2 TO MULTIUNIT TO OUT DUNIT TO IN DUNIT d e 2 1 3 X5M a b c d e X1M A1P X5M 1 2 X1M A1P DIII transmission wiring a To capacity up unit b To indoor units air condit...

Page 31: ...rror occurs that causes unit operation to stop R P2 run signal connection optional when the compressor is running P1 P2 operation signal connection mandatory when the expansion valves of the connected...

Page 32: ...on of the capacity up unit a remote operation switch is required Use a voltage free contact for microcurrent 1 mA 12 V DC Connect to X3M 1 2 and set to Remote R E M O T E OFF O N S1S S1S Factory equip...

Page 33: ...ain PCB A1P of the outdoor unit and capacity up unit This involves the following field setting components Push buttons to give input to the PCB A 7 segment display to read feedback from the PCB DIP sw...

Page 34: ...lay goes to its default situation From there you can access mode 1 and mode 2 Initialisation default situation NOTICE Be sure to turn on the power 6 hours before operation in order to have power runni...

Page 35: ...side of the unit on refrigerant leakage If there is a refrigerant leak try to repair the leak If the repair is unsuccessful call your local dealer Do not touch any refrigerant which has leaked out fro...

Page 36: ...s and circuit breakers on the indoor unit PCB did not trip Operation parameters For a stable operation of the unit each of the following parameters should be in its range Parameter Range Root cause wh...

Page 37: ...the maintenance and repair works Quantities and kind of new reused recycled reclaimed refrigerant which have been charged on each occasion Quantities of refrigerant which have been transferred from th...

Page 38: ...downstream of indoor units error displayed on remote controller O Wrong combination of indoor units Check the number of connected indoor units Check if an indoor unit is installed that is not a possib...

Page 39: ...ata is available on the Daikin Business Portal authentication required 19 1 Piping diagram Outdoor unit HPS HPS HPS os L M H L SV RV M 15 9 C1220T H 15 9 C1220T H 15 9 C1220T H 19 1 C1220T H M M M Pre...

Page 40: ...19 2 Piping diagram Capacity up unit 15 9 C1220T H 15 9 C1220T H L RV M M HPS os H Pressure sensor Plate heat exchanger HPS Pressure switch Heat exchanger Check valve os Oil separator Service port RV...

Page 41: ...ted circuit board earth leakage detector E1HC Crankcase heater M1C E2HC Crankcase heater M2C E3HC Crankcase heater M3C L1R Reactor A3P L2R Reactor A4P L3R Reactor A5P M1C Motor compressor INV1 M2C Mot...

Page 42: ...Crankcase heater M1C F1U F2U Fuse T 6 3 A 250 V A1P F1U Fuse A6P F101U Fuse A4P F3U F4U Fuse B 1 A 250 V F401U F403U Fuse A3P F601U Fuse A2P HAP Light emitting diode service monitor is green A1P A2P...

Page 43: ......

Page 44: ...4P605461 1 2020 04 Copyright 2020 Daikin 4P605461 1 0000000K Verantwortung f r Energie und Umwelt...

Reviews: