6 Configuration
Installation manual
19
LMSEY1A09/13 + LMSEY2A19/25
Daikin LMS
4P728170-1 – 2023.03
a b c
a
UP button
b
DOWN button
c
PROGRAM button
CtL
Control menu
Pro
Display probes menu
HcP
HACCP menu
CnF
Configuration menu
ALM
Alarms menu
PSd
Service menu
ESC
Exit the menu loop
Note:
To return to the standard display, go to "ESC" and press the
PROGRAM (c) button.
INFORMATION
If no button is pressed, the terminal will return to the
standard display after 7 seconds.
6.4
Parameters
Name
Description
Default
Min.
Max.
UoM
Menu
(a)
App
/5
(b)
Unit of measure:
▪ 0: °C
▪ 1: °F
0
0
1
●
Pro
●
/6
Display decimal point:
▪ 0: Yes
▪ 1: No
0
0
1
●
Pro
●
/t1
Display on user terminal:
▪ 0: not configured
▪ 1: value of S1
▪ 2: value of S2
▪ 3: value of S3
▪ 4: value of S4
▪ 5: value of S1H
▪ 6 to 8: not available
▪ 9: control probe
▪ 10: virtual probe
▪ 11 to 14: not available
▪ 15: current control setpoint
9
0
15
●
Pro
●
/t2
Display on remote display:
▪ 0 to 15, see /t1 (above)
0
0
15
●
Pro
●
A1
(b)
Alarm thresholds (AH, AL) relative to the setpoint St or
absolute:
▪ 0: relative
▪ 1: absolute
0
0
1
●
A3
(b)
Defrost terminated after maximum time signal:
▪ 0: disabled
▪ 1: enabled
0
0
1
●
Ad
(b)
Delay time for high and low temp. alarms (AH, AL)
120
0
240
min
●
ALM
●
Add
(b)
High temp. alarm bypass time for door open
5
1
240
min
●
ALM
●