5 Installation

Installation manual

14

LMSEY1A09/13 + LMSEY2A19/25

Daikin LMS

4P728170-1 – 2023.03

▪ When  "wall  mounting"  method  was  used,  guide  the  drain

pan pipe (c) through the hole in the insulation pad (b). Then
further guide it into the unit through the hole in the back plate
(e).

▪ When "saddle mounting" method was used, guide the drain

pan pipe (c) through the hole in the cold room wall (a). Then
further guide it into the unit through the hole in the back plate
(e).

2

Instal the 7 screws (f) to fix the drainpan (d) to the evaporator.
Tighten the screws to a torque of 2.17 N•m.

NOTICE

When  the  drain  pan  is  removed,  the  electric  drain  heater
must  be  slid  out  of  the  drain  pan  pipe.  The  electric  drain
heater must be pushed back into the drain pan pipe when
the drain pan is reinstalled.

d

c

b

a

c

e

f

f

f

f

f

g

a

Cold room wall

b

Insulation pad assembly

c

Drain pan pipe

d

Drain pan

e

Back plate of the unit

f

Screw

g

Electric drain heater

5.4.6

To seal the unit

1

Seal the gaps between the unit and insulation pad and the cold
room wall with mastic.

If the saddle mounting method was applied:

2

Reinstall the cold room roof.

3

Complete  fixing  the  unit  further  with  2  screws  through  the  top
fixing holes.

5.4.7

To install the external drain pipe

Frost  gradually  builds-up  on  evaporator  coils  during  operation.  The
unit  uses  a  hot  refrigerant  to  defrost  the  evaporator  coils.  Hot
refrigerant  gas  passes  through  the  evaporator  coil  and  melts  the

frost. The melt water drips into the evaporator drain pan, where the
drain  pan  defrost  coil  prevents  re-icing.  It  then  flows  via  the  drain
pipe (a) to the overflow tank (c) in the condenser part of the unit.

Most  of  the  time  this  water  evaporates  in  the  overflow  tank  (c)  that
has  hot  refrigerant  pipes  (d)  going  through  it.  This  also  works  as  a
"water cooling system" for hot refrigerant at the same time.

In  case  of  an  overflow,  the  external  drain  connection  (e)  must  be
connected to an external drain pipe or hose (g).

INFORMATION

Fresh  meat,  fish  or  vegetables  produce  a  lot  of  humidity.
Already frozen products produce little humidity.

INFORMATION

The  internal  drain  pipe  has  a  siphon,  which  ensures  that
warm air from the unit condenser cannot escape to the unit
evaporator.

a

d

b c

e f g

a

Drain pipe (internal)

b

Overflow opening

c

Overflow tank

d

Hot refrigerant pipes

e

External drain connection (Ø 14 mm)

f

Pipe clamp

g

Drain pipe or hose (external)

1

Install a pipe clamp (f) over the drain pipe (or hose) (g).

2

Slide the drain pipe (g) with the pipe clamp (f) over the external
drain pipe connection (e).

3

Tighten the pipe clamp (f).

4

Make  sure  condensation  water  can  be  evacuated  properly
through the drain pipe:

▪ The  drain  pipe  should  run  as  straight  as  possible  down  the

cold room wall, with no kinks or bends.

▪ Secure with screws, tie wraps and clamps as required.

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

5.5

To connect the power supply

The supply cable for models LM13 has a ground, line and
neutral conductor. The supply cable for models LM25 has
one ground, three line and one neutral conductors. The supply cable
is labelled C1.

NOTICE

In case of a three-phase power supply the compressor can
break down if the wires are not connected correctly.

A number to identify the phases is printed on the surface of
the  wire  insulation.  The  meaning  of  the  numbers  is  the
following: 1=L1, 2=L2, 3=L3, 4=neutral.

Summary of Contents for LMSEY1A09AVM01

Page 1: ...Installation manual Daikin LMS English Installation manual Daikin LMS LMSEY1A09AVM01 LMSEY1A13AVM01 LMSEY2A19AYE01 LMSEY2A25AYE01...

Page 2: ...le units 25 6 6 About the alarms 26 7 Commissioning 26 8 Hand over to the user 27 9 Disposal 27 10 Technical data 27 10 1 Wiring diagram 27 10 2 Piping diagram 29 10 3 Weight 29 11 Glossary 29 1 About...

Page 3: ...could result in electrical shock short circuit leaks fire or other damage to the equipment ONLY use accessories optional equipment and spare parts made or approved by Daikin CAUTION Wear adequate per...

Page 4: ...bles and make sure they do NOT come in contact with the piping and sharp edges Make sure no external pressure is applied to the terminal connections Make sure to install earth wiring Do NOT earth the...

Page 5: ...efrigerating appliances and ice makers with an incorporated or remote refrigerant unit or motor compressor EN 12100 Risk assessment Directive and regulations 2006 42 CE EN ISO 13857 2020 Safety Distan...

Page 6: ...packaging bags so that nobody especially NOT children can play with them Possible consequence suffocation h i d b b Cardboard pillars d Pallet h Screws i Protection cover blue color 5 Remove the prote...

Page 7: ...Insulation accessory e Cold room roof f Condenser fan g High pressure switch h Electronic expansion valve with firewall i Evaporator j Evaporator fan k Thermistor l Defrost coil for drain pan m Drain...

Page 8: ...To install multiple units 415 4 5 Possible options for the unit INFORMATION Certain options may NOT be available in your country Three cable glands a b and c are provided to bring the option cables i...

Page 9: ...ronment e g sea breeze atmosphere This to prevent corrosion caused by high levels of salt in the air which can shorten the life of the unit If outside air is sucked into the cold room the temperature...

Page 10: ...e the blade is long enough to cut through the entire wall panel 5 3 Opening and closing the unit 5 3 1 To open the unit DANGER RISK OF ELECTROCUTION Do NOT leave the unit unattended when the service c...

Page 11: ...st be removed See below for more information To prepare the cold room for wall mounting 1 Make a cutout in the front wall of the cold room The cutout x y will accommodate the unit evaporator protrusio...

Page 12: ...old room 411 the optional insulation pad must be installed on the unit Refer to the installation instruction included in the insulation pad option 1 Install the insulation pad a at the back of the uni...

Page 13: ...pad c Cutout 4 With the unit in place fix it with 4 screws through the fixing holes a b In case of saddle mounting method 1 If not already done position the unit on a lifting table and secure it with...

Page 14: ...n the condenser part of the unit Most of the time this water evaporates in the overflow tank c that has hot refrigerant pipes d going through it This also works as a water cooling system for hot refri...

Page 15: ...must be connected to their main PCB controllers 1 Open the unit condenser front plate and electrical box cover See 5 3 Opening and closing the unit 410 2 Connect the BMS connector J4 of the secondary...

Page 16: ...suitable for 220 240 V and the total load of the control circuit must NOT exceed 4 A INFORMATION For the cold room lamp usually a LED bulb of 0 1 A is used with a maximum 0 3 A 4 Connect the wiring t...

Page 17: ...X4M 32C X4M 33C X4M 34C X4M 35C X4M 36C X4M 37C X4M 38C X4M 39C X4M 40C X4M K3M 33 34 4 9 F3 6 3A F4 6 3A 5 2 5 2 5 6 5 7 5 7 5 7 5 6 5 6 5 4 5 4 5 9 5 9 5 9 5 9 5 10 5 9 5 8 5 8 5 3 HMI ACU Q1 d c a...

Page 18: ...s 4 Select BLUETOOTH SCAN to view the controller devices available within a range of 10 m 5 Select the device to connect to Result BLE will blink on the user interface display to confirm that the conn...

Page 19: ...n Max UoM Menu a App 5 b Unit of measure 0 C 1 F 0 0 1 Pro 6 Display decimal point 0 Yes 1 No 0 0 1 Pro t1 Display on user terminal 0 not configured 1 value of S1 2 value of S2 3 value of S3 4 value o...

Page 20: ...m serial 0 no 1 yes 0 0 1 dFr b Defrost status 0 0 1 dFs b Defrost state idle dI b Maximum interval between consecutive defrosts 8 0 240 hours dP1 b Maximum defrost duration 45 1 240 min dP2 b Maximum...

Page 21: ...0 1 FOE Logical status of the digital light output 0 0 1 FOG Logical status of the digital output 0 0 1 FOI Logical status of the digital output 0 0 1 FOI_1 Logical status of the digital output 0 0 1...

Page 22: ...on for secondary unit 2 0 The controller regulates through the probe connected to itself 1 The controller regulates through the probe connected to the Primary unit 0 0 1 nrt_3 c Network temperature re...

Page 23: ...ontrol setpoint 4 0 25 10 C F StH Setpoint for humidity 90 0 0 CtL Sv Virtual probe read only 20 2 0 0 Sv_1 Virtual probe secondary unit 1 read only 0 0 0 Sv_2 Virtual probe secondary unit 2 read only...

Page 24: ...d Start timespan 5 day 0 00 00 0 00 00 23 59 59 tS5 time Start time datatype 5 0 00 00 0 00 00 23 59 59 tS6 d Start timespan 6 day 0 00 00 0 00 00 23 59 59 tS6 time Start time datatype 6 0 00 00 0 00...

Page 25: ...tatus is open if the switch is open As for the lights also the door status is shared to all controllers Every controller knows if the door s is are open or not and each controller can perform the acti...

Page 26: ...s will happen when a network connection fault occurs that lasts longer than the dI parameter setting Therefore the dI parameter must always be set 6 6 About the alarms To check and reset alarms error...

Page 27: ...t must be done by an authorised area technical assistance service that has proper training equipment and instructions for the dismantling They are also responsible for reuse recycling and recovery CAU...

Page 28: ...F3 Line aux fuse HMI User interface HMI cable User interface cable connection HPS1 High pressure switch 1 HPS2 High pressure switch 1 Symbol Meaning INV1 Inverter compressor 1 INV2 Inverter compresso...

Page 29: ...Thermistor evaporator inlet Th6 B Thermistor evaporator outlet Th7 B Thermistor condenser 10 3 Weight Model Type Weight LMSEY1A09AVM01 A 52 kg LMSEY1A13AVM01 LMSEY2A19AYE01 B 83 5 kg LMSEY2A25AYE01 WA...

Page 30: ...nal equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation Field supply Equipment NOT made by Daikin that...

Page 31: ......

Page 32: ...4P728170 1 2023 03 Copyright 2023 Daikin 4P728170 1 0000000N Verantwortung f r Energie und Umwelt...

Reviews: