• Block the gap (shaded area shown in the figure below) with seal-

ing material such as putty if an intrusion by small creatures is pos-
sible.

6-3 Wiring Connection

High voltage wiring (Power supply wiring, Refrigeration opera-
tion output wiring, and earth wire)

• When two wires are connected to a single terminal, connect them 

so that the rear sides of the crimp contacts face each other.

• Also, make sure the thinner wire is on top, securing the two wires 

simultaneously to the resin hook using the accessory clamp (1).

Power circuit, safety device, and cable requirements

• A power circuit (see the following table) must be provided for con-

nection of the unit. This circuit must be protected with the required 
safety devices, i.e. a main switch, a slow blow fuse on each phase 
and an earth leakage circuit breaker.

• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with 

relevant local and national regulations.

• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.
• Use wire type H07RN-F when protected pipes are not used.

Refrigeration operation output wire specifications

CAUTION

• Refer to the “

6-1 Example of Wiring Entire System

” by all 

means when connecting the operation output wiring.
A compressor failure may result if the operating output wiring is 
not connected.

Low voltage wiring (transmission wire, refrigeration operation 
input wiring and remote switch wire)

Connect low voltage wiring between the booster unit and the outdoor 
unit, the booster unit and the integrated heat control board and the 
remote switch by referring to the figure below.

<Precautions for low voltage wiring>

• Never connect the 220-240V power supply to the terminal block of 

low voltage wiring. The entire system could be damaged.

• Isolate low voltage wiring from high voltage wiring (power supply 

wire, refrigeration operation output wiring and earth wire) by at 
least 50 mm.

• Always install low voltage wiring using vinyl cord with a 0.75-1.25 

mm

2

 sheath or cable (duplex).

• Install low voltage wiring within the limit described below. Exceed-

ing the limit can cause transmission problems.
Distance between the booster unit and the outdoor unit: 100 m

<Connection for transmission wire and refrigeration operation 
input wiring>

<Connection for remote switch wire>

• Set the operation switch to “Remote” as shown in the figure below 

to remotely start up and shut down.

• Use a remote switch that has a contact assuring the minimum 

applicable load of DC12V/1mA.

6-4 Checking of Device and Installation Conditions

Be sure to check the followings.

<For those doing electrical work>

See “

6-2 Procedure for Incoming Wiring

”.

1.

Make sure there is no faulty power wiring or loosing of a nut.
See “

6-3 Wiring Connection

”.

2.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

<For those doing pipe work>

1.

Make sure piping size is correct.
See “

5-1 Selection of Piping Material

”.

2.

Make sure insulation work is done. 
See “

5-6 Thermal Insulation for Piping

”.

3.

Make sure there is no faulty refrigerant piping.
See “

5. REFRIGERANT PIPING

”.

7.

CHECKS AFTER WORK COMPLETION

• Make sure the following works are complete in accordance with 

the installation manual.

„

Piping work

„

Wiring work

„

Air tight test/Vacuum drying

„

Installation work for indoor unit (Refrigeration unit cooler, 
refrigeration showcase, freezer showcase, air-conditioner)

„

Installation work for outdoor unit

„

Drainage water

Phase and 

frequency

Voltage

Minimum 

circuit 

amp.

Recom-

mended 

fuses

LCBKQ3AV1

φ

1,  50Hz

220-240V

15A

20A

Electric wire thickness

0.75~1.25mm

2

Max. wiring length

130m

Do not touch the high pressure 
piping in the            shaded area 
during wiring.

Gap

(Block with sealing 
material.)

Power supply
(1 phase 220~240V)

Earth wire

Power supply 

terminal block

Earth wire

Attach the 
insulation sleeve

Power supply wire

Earth terminal

X1M

X1M

Overcurrent 
circuit breaker
(Earth leakage 
circuit breaker)

Refrigeration operation 
output wiring

Fix refrigeration operation 
output wiring (S1, S2) with 
the attached clamp.

Fix power supply wiring 
(L/N phases) with the 
attached clamp

L

N

Terminal block

Crip style terminal

Wire: narrow

Clamp (1)

Wire: thick

Resin hook

High voltage wiring

Low voltage wiring

Transmission wire 

Refrigeration operation
input wiring 

Refrigeration operation input wiring 

<Outdoor unit>

F1F2 F1F2 F1F2 T1T2 F1F2 1 2

In-Out  Out-Out  Out-Multi

In-Out

<Booster unit>

50mm or more

Transmission

wire

Never connect the power supply wire

Fix low voltage wiring 
with the attached clamp

REMOTE

ON

OFF

REMOTE

ON

Remote switch 
(between 1 and 2)

Ú

Constant a-contact input

OFF

Summary of Contents for LCBKQ3AV1

Page 1: ...ands Installation manual Booster Unit Installationsanleitung Zusatzgerät Manuel d installation Unité d accélération Manual de instalación Unidad booster Manuale di installazione Compressore ausiliario Installatiehandleiding Boostereenheid Manual de instalação Booster Booster Unit LCBKQ3AV1 E ...

Page 2: ......

Page 3: ...nstalling the unit in a small room take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Be sure to use only the specified accessories and parts for instal lation work Failure to use the specified par...

Page 4: ...be charged with fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Values are indicated in F gas regulations EC No 842 2006 Annex I Parts 1 and 2 The refrigerant R410A requires strict cautions for keeping the sys tem clean dry and tight Read the chapter REFRIGERANT PIPING carefully ...

Page 5: ...o consideration human traffic and wind As regards space in front of the unit consider the space needed for the local refrigerant piping when installing the units If the work conditions in the following figure do not apply contact your dealer or Daikin directly CAUTION 1 An inverter booster unit may cause electronic noise generated from AM broadcasting Examine where to install the main booster unit...

Page 6: ... fluoride is contained the flux will have adverse influences on the refrigerant piping line such as the dete rioration of refrigerating machine oil CAUTION All field piping must be installed by a licensed refrigeration tech nician and must comply with relevant local and national regula tions Precautions for reuse of existing refrigerant piping heat exchangers Keep the following points in mind for ...

Page 7: ...r unit Example of piping connection Piping size O D min thickness mm Note 1 Liquid piping inlet Main liquid piping between booster unit and outdoor unit Liquid piping outlet Between booster unit and refrigeration showcase Suction piping Between booster unit and refrigeration showcase Discharge piping Main gas piping between booster unit and outdoor unit Note 2 If the size of the connection pipe of...

Page 8: ...lve opened without turning the power on otherwise refrigerant may be condensed in the compressor and the insulation of the main power supply circuit may be degraded Be sure to use an exclusive tool to handle the shutoff valve The shutoff valve is not of back sheet type Excessive force imposed may break the valve Use a charge hose when using the service port Make sure that there is no refrigerant g...

Page 9: ...gn pres sure 3 8MPa of the outdoor unit and pressurize the low pressure side suction side to the design pressure 2 5MPa of the indoor unit field supplied In this case they shall be accepted if no pressure drop is found for 24 hours through pressurization at least 5 minutes from the port A and the liquid shutoff port shown in the right figure Check if there are any leakage areas in the case of pres...

Page 10: ... rise in electrical potential in the grounding Be sure to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the earth leakage circuit breaker itself Earth leakage circuit breaker which are especially for protecting ground faults should be used in conjuncti...

Page 11: ...oles on the right side Timer for refrigeration Timer for freezer Note 3 In case of the malfunction Constant a contact output Relay Alarm panel Warning output Caution output Branch switch Overcurrent circuit breaker Refrigeration operating output Freezer operation output Indoor unit Booster unit Remote switch Note 1 Remote controller In Out Out Out Thermostat for inner temperature adjustment Defros...

Page 12: ...ion for transmission wire and refrigeration operation input wiring Connection for remote switch wire Set the operation switch to Remote as shown in the figure below to remotely start up and shut down Use a remote switch that has a contact assuring the minimum applicable load of DC12V 1mA 6 4 Checking of Device and Installation Conditions Be sure to check the followings For those doing electrical w...

Page 13: ...switch BS5 using an insulating rod See the right figure Refer to the Service Manual for other malfunction codes Take the following action if you find a malfunction code on the remote controller during the test run 1 Set the operating switch to the OFF position to reset the power sup ply and then return the switch to the ON position to restart the unit If the problem persists refer to the Service M...

Page 14: ...3P248411 5B EM09A056 1002 FS ...

Reviews: