2-3 Indoor Unit Constraints

• The design pressure for the indoor unit is 2.5 MPa or more.
• Install an R410A mechanical thermostatic expansion valve on 

each indoor unit.

• Insulate the feeler block of the mechanical thermostatic expan-

sion valve.

• Install an R410A solenoid valve on the primary side of the 

mechanical thermostatic expansion valve (Max. operating differ-
ential pressure of 3.5 MPa [35 bars] or over) described above for 
each indoor unit.

• Install a filter on the primary side of the solenoid valve described 

above for each indoor unit. Determine the filter mesh count based 
on the size specified by the solenoid valve and mechanical ther-
mostatic expansion valve being used.

• Route the path to the indoor unit heat exchanger so that the flow 

of refrigerant is from top to bottom.

• When installing a number of indoor units, be sure to install them at 

the same level.

• Use the electric heater defrosting as the defrosting type. Hot-gas 

defrosting models cannot be used.

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions. 
Get the customer’s permission.

1.

There is no danger of fire due to leakage of inflammable gas.

2.

Select the location of the unit in such a way that the sound gener-
ated by the unit disturb anyone.

3.

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

4.

The piping length between the booster unit and outdoor unit or 
between the booster unit and indoor unit may not exceed the 
allowable piping length. (Refer to

 

REFRIGERANT PIPING

”)

5.

When installing the unit outdoors, install it preferably in a location 
that is not exposed to rain.

6.

The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available. 
(See the “Installation Space Examples” for the minimum space 
requirements.)

Installation Space Examples

• During installation, install the units using the most appropriate of 

the patterns shown in the following figure for the location in ques-
tion, taking into consideration human traffic and wind.

• As regards space in front of the unit, consider the space needed 

for the local refrigerant piping when installing the units. 

• If the work conditions in the following figure do not apply, contact 

your dealer or Daikin directly.

CAUTION

1.

An inverter booster unit may cause electronic noise generated 
from AM broadcasting. Examine where to install the main booster 
unit and electric wires, keeping proper distances away from ste-
reo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is a 
distance of at least 3 meters for indoor remote controllers, place 
power wiring and transmission wiring in conduits, and ground the 
conduits.

2.

If condensate may drip on downstairs (or walkway) depending on 
the floor condition, take a measure such as the installation of  
drain pan kit (sold separately).

3.

The refrigerant R410A itself is nontoxic, nonflammable and is 
safe. If the refrigerant should leak however, its concentration may 
exceed the allowable limit depending on room size. Due to this it 
could be necessary to take measures against leakage. 
See “Engineering Data” for details.

4.

PLACING THE UNIT

4-1 Handling the Unit

1.

Decide on the transportation route.

2.

If hanging the unit, use a cloth sling to prevent damaging the unit. 
Keeping the following points in mind, hang the unit following the 
procedure shown in the following figure.

• Use the slings bearing product mass enough.
• Lift the unit with 2 belts of the at least 4m long.
• Put cushion cloth where the slings contact the casing.
• Lift the product with cave at the product center of gravity posi-

tion.

If using the handle of unit, carry the unit slowly with having the 
handle.

1, 2

<When installed 

as a single unit>

Piping slot

Booster unit

500mm

500mm

500mm

500mm

500mm

200mm

200mm

500mm

500mm

500mm

Front side

Front side

<When installed in serial>

Power supply

Power supply

Power supply

Power 
supply

Power supply

Unit cooler

Control 
panel

Booster 

unit

1.5m or more

1.5m or more

1.5m or more

1.5m or more

Control 

panel

Alarm 

panel

1.5m or more

1m or more

1.5m or more

1.5m or more

1m or more

 1.5m or more

 1.5m or more

 1.5m or more

Remote 

controller

Showcase

Indoor unit

Belt sling

Belt sling

Cushion cloth

Handle

Hang on the edge 
of the bottom plate.

Summary of Contents for LCBKQ3AV1

Page 1: ...ands Installation manual Booster Unit Installationsanleitung Zusatzgerät Manuel d installation Unité d accélération Manual de instalación Unidad booster Manuale di installazione Compressore ausiliario Installatiehandleiding Boostereenheid Manual de instalação Booster Booster Unit LCBKQ3AV1 E ...

Page 2: ......

Page 3: ...nstalling the unit in a small room take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage Contact the place of purchase for more information Excessive refrigerant in a closed ambient can lead to oxygen deficiency Be sure to use only the specified accessories and parts for instal lation work Failure to use the specified par...

Page 4: ...be charged with fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Values are indicated in F gas regulations EC No 842 2006 Annex I Parts 1 and 2 The refrigerant R410A requires strict cautions for keeping the sys tem clean dry and tight Read the chapter REFRIGERANT PIPING carefully ...

Page 5: ...o consideration human traffic and wind As regards space in front of the unit consider the space needed for the local refrigerant piping when installing the units If the work conditions in the following figure do not apply contact your dealer or Daikin directly CAUTION 1 An inverter booster unit may cause electronic noise generated from AM broadcasting Examine where to install the main booster unit...

Page 6: ... fluoride is contained the flux will have adverse influences on the refrigerant piping line such as the dete rioration of refrigerating machine oil CAUTION All field piping must be installed by a licensed refrigeration tech nician and must comply with relevant local and national regula tions Precautions for reuse of existing refrigerant piping heat exchangers Keep the following points in mind for ...

Page 7: ...r unit Example of piping connection Piping size O D min thickness mm Note 1 Liquid piping inlet Main liquid piping between booster unit and outdoor unit Liquid piping outlet Between booster unit and refrigeration showcase Suction piping Between booster unit and refrigeration showcase Discharge piping Main gas piping between booster unit and outdoor unit Note 2 If the size of the connection pipe of...

Page 8: ...lve opened without turning the power on otherwise refrigerant may be condensed in the compressor and the insulation of the main power supply circuit may be degraded Be sure to use an exclusive tool to handle the shutoff valve The shutoff valve is not of back sheet type Excessive force imposed may break the valve Use a charge hose when using the service port Make sure that there is no refrigerant g...

Page 9: ...gn pres sure 3 8MPa of the outdoor unit and pressurize the low pressure side suction side to the design pressure 2 5MPa of the indoor unit field supplied In this case they shall be accepted if no pressure drop is found for 24 hours through pressurization at least 5 minutes from the port A and the liquid shutoff port shown in the right figure Check if there are any leakage areas in the case of pres...

Page 10: ... rise in electrical potential in the grounding Be sure to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the earth leakage circuit breaker itself Earth leakage circuit breaker which are especially for protecting ground faults should be used in conjuncti...

Page 11: ...oles on the right side Timer for refrigeration Timer for freezer Note 3 In case of the malfunction Constant a contact output Relay Alarm panel Warning output Caution output Branch switch Overcurrent circuit breaker Refrigeration operating output Freezer operation output Indoor unit Booster unit Remote switch Note 1 Remote controller In Out Out Out Thermostat for inner temperature adjustment Defros...

Page 12: ...ion for transmission wire and refrigeration operation input wiring Connection for remote switch wire Set the operation switch to Remote as shown in the figure below to remotely start up and shut down Use a remote switch that has a contact assuring the minimum applicable load of DC12V 1mA 6 4 Checking of Device and Installation Conditions Be sure to check the followings For those doing electrical w...

Page 13: ...switch BS5 using an insulating rod See the right figure Refer to the Service Manual for other malfunction codes Take the following action if you find a malfunction code on the remote controller during the test run 1 Set the operating switch to the OFF position to reset the power sup ply and then return the switch to the ON position to restart the unit If the problem persists refer to the Service M...