For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 

mm thickness,

polyethylene foam).

For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 2 or 3
directions.

1

Select an installation site where the following conditions
are fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where piping between indoor and outdoor units is possible within
the allowable limit. (Refer to the installation manual of the outdoor
unit.)

This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be
required to take adequate measures.

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances.
(Noise may be generated depending on the conditions under
which the electric wave is generated, even if 1 meter is kept.)

2

Ceiling height

Install this unit where the height of bottom panel is more than
2.5 m so that the user cannot easily touch.

3

Air flow directions

Select the air flow directions best suited to the room and point of
installation. (For air discharge in 2 or 3 directions, it is necessary
to make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to the chapter 

"Field setting" on

page 7

.) (See 

figure 2

 (

 = air flow direction))

4

Use suspension bolts for installation. Check whether the
ceiling is strong enough to support the weight of the
indoor unit. If there is a risk, reinforce the ceiling before
installing the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 6

  (

  = air flow

direction)

P

REPARATIONS

 

BEFORE

 

INSTALLATION

1.

Relation of ceiling opening to unit and suspension bolt
position. 

(See figure 7)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

1

Air discharge in 4 directions

2

Air discharge in 3 directions

3

Air discharge in 2 directions

1

Air inlet

2

Air outlet

NOTE

Leave 200 mm or more space where marked
with * on sides where the air outlet is closed.

1

Decoration panel dimensions

2

Ceiling opening dimensions

3

Indoor unit dimensions

4

Suspension bolt pitch dimensions

5

Refrigerant piping

6

Suspension bolt (x4)

7

False ceiling

8

Hanger bracket

NOTE

Installation is possible with a ceiling opening
dimension of 660 mm (marked with *). However, to
achieve a ceiling-panel overlapping dimension of
20 mm, the spacing between the ceiling and the unit
should be 45 mm or less. If the spacing between
ceiling and the unit is over 45 mm, attach sealing
material in the part marked 

 or recover the ceiling. 

(See figure 3)

 

1

Sealing material

2

False ceiling

Summary of Contents for FXZQ20M9V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ20M9V1B FXZQ25M9V1B FXZQ32M9V1B FXZQ40M9V1B FXZQ50M9V1B System air conditioners...

Page 2: ...4 50 100 2 2 3 4 5 1 1 2 45 45 5 6 533 3 575 2 585 660 1 700 4 700 2 585 660 3 575 4 533 1 585 660 8 7 20 20 180 2 1500 1500 1500 2500 1500 1500 1500 1500 1 2 2 1 2 3 3 2 1 4 2 3 4 1 2 1 2 2 1 295 5 4...

Page 3: ...LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 SETTING 2 1 4 3 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 13 1 2 3 8 7 4 4 5 5 5 6 6 6 5 21 3 2 1 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1...

Page 4: ...12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo t...

Page 5: ...hens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machine...

Page 6: ...ore than 2 5 m so that the user cannot easily touch 3 Air flow directions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is...

Page 7: ...unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the...

Page 8: ...and drain hose to insulate How to perform piping See figure 15 Precautions Install the drain raising pipes at a height of less than 545 mm Install the drain raising pipes at a right angle to the indoo...

Page 9: ...on manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground...

Page 10: ...ranch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding terminal Looseness in...

Page 11: ...sorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of ti...

Page 12: ...er to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Read the chapter Test operation on page 8 before making a test run without attaching the decor...

Page 13: ...CLEAN AIR FILTER display disappears For details refer to the operation manual of the outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove...

Page 14: ...D H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS...

Page 15: ...25 27 29 28 26 T1 T2 10 15 mm A D 1 2 3 4 5 6 7 8 15 11 9 15 10 15 8 15 10 15 B 11 12 12 13 14 1 0 1 5 m m C E REMOTE CONTROL TRANSMISSION WIRING FORCED OFF L N L N 25 26 27 28 29...

Page 16: ...4PW45002 1 Copyright Daikin...