FXZQ20~50M9V1B
VRV System air conditioners
4PW45002-1
Installation and operation manual
7
W
IRING
EXAMPLE
■
Fit the power supply wiring of each unit with a switch and fuse as
shown in
.
Complete system example (3 systems)
■
When using 1 remote controller for 1 indoor unit. (Normal
operation.)
For group control or use with 2 remote controllers
.
When including BS unit
Precautions
1.
A single switch can be used to supply power to units on the same
system. However, branch switches and branch circuit breakers must
be selected carefully.
2.
For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.
3.
Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.
F
IELD
SETTING
Field setting must be made on the remote controller in function of the
installation condition.
■
Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".
■
For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.
Summary of field settings
1
Outdoor unit
2
Power supply
3
Main switch
4
BS unit (only for heat recovery system)
5
Indoor unit
6
Remote controller
7
Switch
8
Fuse
Power supply wiring
Transmission and remote controller wiring
1
Outdoor unit
2
Indoor unit
3
Remote controller (Optional accessories)
4
Most downstream indoor unit
5
For use with 2 remote controllers
6
BS unit
NOTE
It is not necessary to designate indoor unit address
when using group control. The address is automati-
cally set when power is activated.
Mode
No.
(Note 1)
First
code
No.
Description of setting
Second code No. (Note 2)
01
02
03
04
10
(20)
0
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
contamination is
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
Ultra-long-
life filter
Light
±10,000 hrs.
Hea
vy
±5,000 hrs.
—
—
Long-life
filter
±2,500 hrs.
±1,250 hrs.
Standard
filter
±200 hrs.
±100 hrs.
1
Long-life filter type
Change the setting when ultra-
long-life filter is installed.
This setting is important for time
between 2 filter cleaning display
indications (refer to 10-0-0X).
Long-life filter
Ultra-long-life
filter
—
—
2
Thermostat sensor selection
Use both the
unit sensor (or
remote sensor if
installed) AND
the remote
controller
sensor.
(See note 5+6)
Use unit sensor
only (or remote
sensor if
installed).
(See note 5+6)
Use remote
controller
sensor only.
(See note 5+6)
—
3
Setting for display of time
between 2 filter cleaning display
indications
Display
Do not display
—
—
5
Information to I-manager,
I-touch controller
Only unit sensor
value (or remote
sensor value if
installed).
Sensor value as
set by 10-2-0X
or 10-6-0X.
—
—
6
Thermostat sensor in group
control
Use unit sensor
only (or remote
sensor if
installed).
(See note 6)
Use both the
unit senor (or
remote sensor if
installed) AND
the remote
controller
sensor. (See
note 4+5+6)
—
—
12
(22)
0
Output signal X1-X2 of the
optional KRP1B PCB kit
Thermostat-on +
compressor run
—
Operation
Mal-
function
1
ON/OFF input from outside
(T1/T2 input) = Setting when
forced ON/OFF is to be
operated from outside.
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover = Setting when
remote sensor is used.
1°C
0.5°C
—
—
3
Fan setting during thermostat
OFF at heating operation
LL
Set speed
OFF
(See note 3)
—
4
Differential automatic
changeover
0°C
1°C
2°C
3°C
(See
note 7)
5
Auto-restart after power failure
Disabled
Enabled
—
—
9
Fixed cool/heat master
Disabled
Enabled
—
—
13
(23)
0
Setting for air outlet velocity
This setting is to be changed in
function of ceiling height.
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
1
Selection for air flow direction
This setting is to be changed
when blocking pad optional kit
is used.
4-way flow
3-way flow
2-way flow
—
4
Airflow direction range setting
This setting is to be changed
when range of swing flap
movement needs to be
changed.
Upper
Normal
Lower
—
5
Setting for adjustment of fan
speed (phase control)
Standard
Option 1
Option 2
—
15
(25)
3
Drain pump ope
humidifier interlock
Equipped
Not equipped
—
—
Note 1 :
Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
indoor units can also be set individually.
Note 2 :
Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 :
Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 :
If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 :
If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
10-2-02 or 10-2-03 have priority.
Note 6 :
If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have
priority.
Note 7 :
More settings for Differential automatic change over temperatures are:
Second code No.
05
4°C
06
5°C
07
6°C
08
7°C
Summary of Contents for FXZQ20M9V1B
Page 16: ...4PW45002 1 Copyright Daikin...