background image

5

ELECTRIC WIRING WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire
the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal board
wiring to the outdoor unit and BS unit are properly matched. If
wiring and piping between the outdoor unit and an indoor unit
are mismatched, the system may cause a malfunction.

Electrical characteristics

Model

Hz

Volts

Voltage range

FXYCP20~125

50

230

min.198-max.264

power supply

Fan motor

MCA

MFA

KW

FLA

FXYCP20

0.5

16A

0.010

0.4

FXYCP25•32

0.5

16A

0.015

0.4

FXYCP40•50

0.8

16A

0.020

0.6

FXYCP63

0.9

16A

0.030

0.7

FXYCP80

1.1

16A

0.050

0.9

FXYCP125

1.3

16A

0.085

1.0

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

NOTE 

For details, refer to "Electrical data".

Specifications for field supplied fuses and wire

Power supply wiring

Model

Field fuses

Wire

Size

FXYCP20~125

16A

H05VV-U3G

Local codes

Transmission wire

Model

Wire

Size

FXYCP20~125

Sheathed wire (2)

0.75-1.25mm

2

NOTE 

For details, refer to the chapter "Wiring example".

Allowable length of transmission wiring between indoor
and outdoor units, and between the indoor unit and the
remote controller is as follows:
1 Outdoor unit - indoor unit: max. 1000m

(total wiring length: 2000m)

2 Indoor unit - remote controller: max 500m

WIRING EXAMPLE AND HOW TO SET THE
REMOTE CONTROLLER

How to connect wiring (see figure 11)

Power supply wiring
Remove the switch box lid (1) and connect the wires to the
power supply terminal board inside. While doing this, pull the
wires inside through the rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A as
before.

Unit wiring and remote controller wiring
Remove the switch box lid (2) and pull the wires inside
through the rubber bush B and connect to the terminal board
for unit transmission wiring.

PRECAUTIONS (see figure 13)

1

Terminal board for unit transmission wirings

2

Clamp

3

Transmission wiring between units

4

Remote controller wiring

5

Power supply wiring

6

Field supplied wires

7

Power supply terminal board

8

Earth terminal (supplied with the unit)

1 Observe the notes mentioned below when wiring to the power

supply terminal board.

Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

2 Keep total current of crossover wiring between indoor units

less than 12A. Branch the line outside the terminal board of
the unit in accordance with electrical equipment standards,
when using two power wiring of a gauge greater than 2mm

2

(Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3 Do not connect wires of different gauge to the same

grounding terminal. Looseness in the connection may
deteriorate the protection.

4 Remote controller cords and wires connecting the units

should be located at least 50mm away from power supply
wiring. Not following this guideline may result in malfunction
due to electrical noise.

5 For the remote controller wiring, refer to the "Installation

manual of the remote controller" supplied with the remote
controller.

6 Never connect the power supply wiring to the terminal board

for transmission wiring. This mistake could damage the entire
system.

7 Use only specified wires and tightly connect wires to the

terminals. Be careful that wires do not place external stress
on the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete
connections could result in overheating, and in the worse
case, electric shock or fire.

Summary of Contents for FXYCP20K7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL System air conditioner FXYCP20K7V1 FXYCP25K7V1 FXYCP32K7V1 FXYCP40K7V1 FXYCP50K7V1 FXYCP63K7V1 FXYCP80K7V1 FXYCP125K7V1...

Page 2: ...es overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning r utf rd i verensst mmelse med och f lje...

Page 3: ...6 5 1 1 7 5 6 2 3 4 5 6 8 7 9 13 12 10 11 3 4 2 1 1 2 3 4 P 1 P 2 F 1 F 2 T 1 T 2 8 7 5 6 4 3 1 2 1 2 3 4 3 4 1 2 100 mm 1 9 8 5 6 10 11 12 1 2 7 13 1 3 6 4 5 2 1500 1500 1000 H 350 100 100 520 5 640...

Page 4: ...T1 T2 1 2 3 4 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 3 5 2 4 IN D OUT D F1 F2 F1 F2 Control box...

Page 5: ...escribed in this manual Caution concerning new refrigerant series The connectable outdoor units must be RSX Y P K or RSEYP K the outdoor units designed exclusively for R407C If outdoor units for R22 a...

Page 6: ...parts are field supplied For other installation than standard installation contact your Daikin dealer for details Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas lea...

Page 7: ...efore installation 5 Check if the unit is horizontally levelled Do not install the unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against con...

Page 8: ...additional force To ensure a downward slope of 1 100 install hanging bars every 1 to 1 5m If unifying multiple drain pipes install the pipes as shown in figure 9 Select converging drain pipes whose ga...

Page 9: ...bush A and clamp the wires along with other wires using clamp A untightening the clip of clamp A by pressing After the connection tighten clamp A as before Unit wiring and remote controller wiring Rem...

Page 10: ...sed control forced off and on off operation 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wi...

Page 11: ...l on one side and open by pulling toward yourself while holding it up NOTE Do not let go of the suction grill when opening or closing it If released the grill will spring back closed 2 Remove the air...

Page 12: ...polishing powder nor liquid insecticide It may cause discolouring or warping Do not let the indoor unit get wet It may cause electric shock or fire Clean the air suction grill when it is closed DISPO...

Page 13: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE09081 1...

Reviews: