Specifications
SiE 00-07
12
Specifications R-407C PLUS Series
1.2
Indoor Unit
4-way blow ceiling mounted cassette
Notes:
1 Nominal cooling capacities are based on the following conditions:
Return air temperature : 27˚C DB, 19˚C WB, Outdoor temperature : 35˚C DB
Equivalent ref. piping : 5m (Horizontal)
2 Nominal heating capacities are based on the following conditions:
Return air temperature : 20˚C DB, Outdoor temperature : 7˚C DB, 6˚C WB
Equivalent ref. piping : 5m (Horizontal)
3 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Daikin Europe model : FXYFP-KB7V1
More detailed information can be found in the Technical Data book covering VRV systems
Model
FXYFP32KVE
FXYFP40KVE
FXYFP50KVE
FXYFP63KVE
Power Supply
1 phase 50/60Hz
220~240V/220V
1 phase 50/60Hz
220~240V/220V
1 phase 50/60Hz
220~240V/220V
1 phase 50/60Hz
220~240V/220V
1 Cooling Capacity
kW
3.6
4.5
5.6
7.1
2 Heating Capacity
kW
4.0
5.0
6.3
8.0
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H
×
W
×
D)
mm
230
×
840
×
840
230
×
840
×
840
230
×
840
×
840
230
×
840
×
840
Coil (Cross
Fin Coil)
Rows
×
Stages
×
Fin Pitch
mm
2
×
8
×
1.5
2
×
8
×
1.5
2
×
8
×
1.5
2
×
8
×
1.5
Face Area
m
²
0.331
0.331
0.331
0.331
Fan
Model
QTS46B14M
QTS46B14M
QTS46B14M
QTS46B14M
Type
Turbo Fan
Turbo Fan
Turbo Fan
Turbo Fan
Motor Output
×
Number
of Units
W
45
45
45
45
Air Flow Rate (H/L)
m
³
/min
13/10
14/10
16/11
18/14
Drive
Direct Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed polystyrene/
Foamed polyethyrene
Foamed polystyrene/
Foamed polyethyrene
Foamed polystyrene/
Foamed polyethyrene
Foamed polystyrene/
Foamed polyethyrene
Piping
Connections
Liquid Pipes
6.4mm (Flare Connection)
6.4mm (Flare Connection)
9.5mm (Flare Connection)
9.5mm (Flare Connection)
Gas Pipes
12.7mm (Flare Connection)
12.7mm (Flare Connection)
15.9mm (Flare Connection)
15.9mm (Flare Connection)
Drain Pipe
(mm)
VP25 (External Dia. 32
Internal Dia. 25)
VP25 (External Dia. 32
Internal Dia. 25)
VP25 (External Dia. 32
Internal Dia. 25)
VP25 (External Dia. 32
Internal Dia. 25)
Weight
kg
24
24
24
24
Safety Devices
Fuse
Thermal protector for Fan
Motor
Fuse
Thermal protector for Fan
Motor
Fuse
Thermal protector for Fan
Motor
Fuse
Thermal protector for Fan
Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Decoration
Panels
Mode
BYC125KJW1
BYC125KJW1
BYC125KJW1
BYC125KJW1
Panel Color
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
White (10Y9/0.5)
Dimensions: (H
×
W
×
D)
mm
40
×
950
×
950
40
×
950
×
950
40
×
950
×
950
40
×
950
×
950
Air Filter
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Resin Net
(with Mold Resistant)
Weight
kg
5
5
5
5
Standard Accessories
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Drain Hose, Clamp metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Drain Hose, Clamp metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Drain Hose, Clamp metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers.
Operation Manual,
Installation Manual, Paper
Pattern for Installation,
Drain Hose, Clamp metal,
Insulation for Fitting, Sealing
Pads, Clamps, Screws,
Washers.
Conversion Formulae
kcal/h=kW
×
860
Btu/h=kW
×
3414
cfm=m
³
/min
×
35.3
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...