SiE 00-07
Troubleshooting by Remote Controller
Troubleshooting R-407C PLUS Series
125
2.6
Remote Controller Self-Diagnosis Function
The remote controller switches are equipped with a self diagnosis function so that more appropriate
maintenance can be carried out. If a malfunction occurs during operation, the operation lamp, malfunction
code and display of malfunctioning unit No. let you know the contents and location of the malfunction.
When there is a stop due to malfunction, the contents of the malfunction given below can be diagnosed by
a combination of operation lamp, INSPECTION display of the liquid crystal display and display of
malfunction code. It also lets you know the unit No. during group control.
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Refered
Indoor
Unit
A0
9
9
9
Error of external protection device
A1
9
9
9
PC board defect
A1
8
7
9
PC board defect
A3
9
9
9
Malfunction of drain level control system (33H)
A6
9
9
9
Fan motor lock
A7
8
7
9
Malfunction of swing flap motor (M1S)
A9
9
9
9
Malfunction of moving part of electronic expansion valve
(Y1E)
AF
8
7
9
Drain level above limit
AH
9
9
9
Malfunction of air filter maintenance
—
AJ
9
9
9
Malfunction of capacity determination device
C4
9
9
9
Malfunction of thermistor (R2T) for liquid pipe (loose
connection, disconnection, short circuit, failure)
C5
9
9
9
Malfunction of thermistor (R3T) for gas pipes (loose
connection, disconnection, short circuit, failure)
C9
9
9
9
Malfunction of thermistor (R1T) for air inlet (loose
connection, disconnection, short circuit, failure)
CJ
8
8
8
Malfunction of thermostat sensor in remote controller
Outdoor
Unit
E0
9
9
9
Actuation of safety device
E1
9
9
9
PC board defect
E1
8
7
9
PC board defect
E3
9
9
9
Actuation of high pressure switch
E4
9
9
9
Actuation of low pressure sensor
E9
9
9
9
Malfunction of moving part of electronic expansion valve
(Y1E)
F3
9
9
9
Abnormal discharge pipe temperature
H3
8
7
9
High pressure switch failure
—
H4
9
9
9
Actuation of low pressure switch
—
H9
9
9
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
H9
8
7
9
Malfunction of thermistor (R1T) for outdoor air (loose
connection, disconnection, short circuit, failure)
J1
9
9
9
Malfunction of pressure sensor
—
J3
9
9
9
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
J3
8
7
9
Malfunction of discharge pipe thermistor (R3T) (loose
connection, disconnection, short circuit, failure)
J5
9
9
9
Malfunction of thermistor (R4T) for suction pipe (loose
connection, disconnection, short circuit, failure)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...