SiE 00-07
Troubleshooting
Troubleshooting R-407C PLUS Series
137
3.14
Outdoor Unit: PC Board Defect
Remote Controller
Display
E1
Supposed Causes
Defect of outdoor unit PC board (A1P)
Troubleshooting
Replace outdoor unit PC board A1P.
3.15
Outdoor Unit: Actuation of High Pressure Switch
Remote Controller
Display
E3
Supposed Causes
Actuation of outdoor unit high pressure switch
Defect of outdoor unit PC board (A1P)
Instantaneous power failure
Troubleshooting
∗
1: Actuation of high pressure switch (HPS)
The outdoor unit PC board’s connector is disconnected.
Is the outdoor unit heat exchanger dirty?
Defect of outdoor fan
Is the refrigerant over-charged?
Operation
is normal when turned on
again by remote
controller.
Replace outdoor unit PC board A1P.
Actuation of high pressure switch.
∗
1
YES
YES
There was an instantaneous power
failure or a past safety device actuated.
Re-check refrigerant system.
NO
NO
(VF041)
Contact
S1HP (X10A) or S2HP
(X11A) is open.