Troubleshooting
Troubleshooting R-407C PLUS Series
135
3.10
Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes
Remote Controller
Display
C5
Supposed Causes
Defect of indoor unit thermistor (R3T) for gas pipe
Defect of indoor unit PC board
Troubleshooting
3.11
Indoor Unit: Malfunction of Thermistor (R1T) for Air Inlet
Remote Controller
Display
C9
Supposed Causes
Defect of indoor unit thermistor (R1T) for air inlet
Defect of indoor unit PC board
Troubleshooting
(VF037)
Replace the indoor unit PC board.
Connect the thermistor and turn on
again.
NO
NO
Replace the thermistor (R3T).
YES
YES
Connector
is connected to X11A of
the indoor unit PC board.
Resistance
is normal when
measured after disconnecting
the thermistor (R3T) from
the indoor unit PC board.
(0.6k
Ω
~360k
Ω
)
Replace the indoor unit PC board.
Connect the thermistor and turn on
again.
NO
NO
Replace the thermistor (R1T).
YES
YES
Connector
is connected to X13A of
the indoor unit PC
board.
Resistance
is normal when
measured after
disconnecting the thermistor
(R1T) from the indoor unit
PC board. (7.2k
Ω
~
112k
Ω
)
(VF038)
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...