Troubleshooting
SiE 00-07
132
Troubleshooting R-407C PLUS Series
3.6
Indoor Unit: Malfunction of Moving Part of Electronic Expansion Valve (Y1E)
Remote Controller
Display
A9
Supposed Causes
Malfunction of moving part of electronic expansion valve
Defect of indoor unit PC board
Defect of connecting cable
Troubleshooting
∗
1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between the
connector pins.
(Normal)
: Continuity
×
: No continuity
(VF033)
After connecting, turn the power supply
off and then back on.
Replace the moving part of the
electronic expansion valve.
YES
YES
NO
NO
Replace the connecting cable.
If you turn the power supply off and
turn on again, and it still does not help,
replace the indoor unit PC board.
NO
YES
The electronic
expansion valve is connected
to X7A of the indoor unit
PC board.
Normal
when coil check (
∗
1) of
the moving part of the electronic
expansion valve
is checked.
The connecting
cable is short-circuited or
disconnected.
Pin No.
1. White
2. Yellow
3. Orange
4. Blue
5. Red
6. Brown
1. White
×
Approx. 300
Ω
×
Approx. 150
Ω
×
2. Yellow
×
Approx. 300
Ω
×
Approx. 150
Ω
3. Orange
×
Approx. 150
Ω
×
4. Blue
×
Approx. 150
Ω
5. Red
×
6. Brown
Summary of Contents for FXYBP20K7V1
Page 1: ...System R 407C PLUS Series Service Manual SiE 00 07 ...
Page 11: ...Introduction SiE 00 07 x ...
Page 17: ...Product Outline SiE 00 07 6 General Information R 407C PLUS Series ...
Page 41: ...Specifications SiE 00 07 30 Specifications R 407C PLUS Series ...
Page 119: ...Test Operation SiE 00 07 108 Test Operation R 407C PLUS Series ...
Page 132: ...SiE 00 07 Troubleshooting by Remote Controller Troubleshooting R 407C PLUS Series 121 ...