Electric heater operating mode setting
(12) -2
〈
When electric heater is used in “Heat Pump lockout
mode”
〉
Check the heater capacity. (Select heater marked with “
•
” or
“
2
” in Table 8.)
Perform on-site setting using the remote controller.
•
Set the “heat pump lockout mode” using the outdoor unit.
•
(Refer to the service manual for the outdoor unit.)
〈
When used as “Auxiliary electric heater”
〉
Check the heater capacity. (Select heater marked with “
•
1
” in
Table 8.)
Perform on-site setting using the remote controller.
•
Table 8
Model
Electric heater kit model name
HKR-
03
HKR-
05C
HKR-
06
HKR-
08C
HKR-
10C
HKR-
15C
HKR-
20C
12 type
18 type
1
24 type
1
30 · 36 type
1
1
42 type
1
1
1
1
2
48 · 54 type
1
1
1
1
2
2
Electric Heater kit setting
(Optional kit)
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Heat Pump lock out mode
11 (21)
3
01*
Auxiliary electric heater &
Heat Pump Lockout mode
available
03
* factory set
Electric heater ON/OFF temperature setting
(12) -3
While in heating operation, the heater control (ON/OFF) is
•
conducted as shown below;
ON
Set temperature
OFF
<Ton: F°>
<Toff: F°>
Perform on-site setting using the remote controller.
•
Mode
No.
FIRST
CODE
NO.
CODE
SECOND CODE NO.
01*
02
03
04
05
06
10 (20)
7
<Ton>
-7.2
-6.3
-5.4
-4.5
-3.6
-2.7
<Toff>
-3.6
-2.7
-1.8
-0.9
0
0.9
* factory set
SETTING FOR LOCAL SUPPLIED OPTION.
10-6
Installation of the humidifi er, economizer and air
(1)
purifi er (UV lamp)
Humidifi er, economizer and air purifi er (UV lamp) are
•
sold separately. For the method of installation, refer to
the manual provided with each optional product.
WARNING
If the unit is installed with an electric heater, install the
•
optional product at a location where it is not exposed directly
to the heat from the electric heater. Direct exposure to heat
can result in an equipment malfunction or fi re.
Connect the wires
(2)
Run the wires through the low-voltage hole.
•
Connect the wires to the terminal block (10P) of the
•
product. The terminal Nos. for wire connection are
shown below. Refer to the information as needed.
Terminal Nos. are indicated on the name plate for the
terminal block.
Terminal
block (10P)
10
5
1
4
3
6
2
7
9
8
Terminal No.
Input/output signal
1, 2
Outputs: indoor unit ON signal. (AC 24V)
3, 4
Outputs: indoor unit cooling THERMO ON
signal. (AC 24V)
5, 6
Receives input: Air purifi er operation ON
signal. (dry contact)
7, 8
Receives input: Humidifi er operation ON
signal. (dry contact)
9, 10
Receives input: Forced closure of Indoor Unit
Electronic Expansion Valve during cooling
operation. (dry contact)
On-site setting of air purifi er/humidifi er
(3)
Mode No.
FIRST CODE NO .
01
02
03
14 (24)
4
FAN SPEED
UNDER
OPERATING
purifi er and
humidifi er
Refer to
remote
controller
setting
SPEED
H*
14 (24)
5
FAN RESI-
DUE TIME
FOR HUMIDI-
FIER
30 [sec]
60* [sec]
120 [sec]
* factory set
SETTINGS FOR SEPARATELY SOLD ACCES-
10-7
SORIES
See the instruction manuals included with optional accesso-
•
ries for the necessary settings.