FXSQ20~140P7VEB
VRV System air conditioners
4PW56483-1

Installation and operation manual

4

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories (except for the air inlet panel),
read also the installation manual of the optional accessories.
Depending on the field conditions, it may be easier to install optional
accessories before the indoor unit is installed.

1

Install the indoor unit temporarily.

-

Attach the hanger bracket to the suspension bolt. Be sure to 
fix it securely by using a nut and washer from the upper and 
lower sides of the hanger bracket. 

(See figure 4)

2

Check if the unit is horizontally levelled.

-

Do not install the unit tilted. The indoor unit is equipped with a 
built-in drain pump and float switch. (If the unit is tilted 
against condensate flow, the float switch may malfunction 
and cause water to drip.)

-

Check if the unit is levelled at all four corners with a water 
level or a water-filled vinyl tube as shown in 

figure 9

.

3

Tighten the upper nut.

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

To  prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.

Use annealed material only for flare connections.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Table 1 

When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.

Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

Finally, insulate as shown in the figures below.

Piping insulation procedure

1

Nut (field supply)

2

Washer for hanger bracket (supplied with the unit)

3

Tighten (double nut)

1

Water level

2

Vinyl tube

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

1

2

4

3

Pipe 

gauge 

(mm)

Tightening torque 

(N•m)

Flare dimension 

A (mm)

Flare shape

Ø6.4

15~17

8.7~9.1

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

Ø15.9

63~75

19.3~19.7

Gas piping

Liquid piping

1

Piping insulation material (field supply)

2

Flare nut connection

3

Insulation for fitting (delivered with the unit)

4

Piping insulation material (main unit)

5

Main unit

6

Clamp (field supply)

7

Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)

A

Turn seams up

B

Attach to base

C

Tighten the part other than the piping insulation material

D

Wrap over from the base of the unit to the top of the flare nut 
connection

For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.

Exposed piping may cause condensation or may
cause burns when touched.

R=0.4~0.8

45

° ±

2

90

°±

2

A

A

B

D

C

7

1

2

3

4

5

6

6

A

B

C

1

2

3

4

5

6

6

D

7

Summary of Contents for FXSQ140P7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20P7VEB FXSQ25P7VEB FXSQ32P7VEB FXSQ40P7VEB FXSQ50P7VEB FXSQ63P7VEB FXSQ80P7VEB FXSQ100P7VEB FXSQ125P7VEB FXSQ140P7VEB System air conditioners...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...itivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk...

Page 4: ...etic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do...

Page 5: ...ectrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept When installing the wireless remote controller kit the distanc...

Page 6: ...ce 2 Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation...

Page 7: ...ecified refrigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tighteni...

Page 8: ...drain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less tha...

Page 9: ...ation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units Mark each indoor unit as uni...

Page 10: ...nits less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch mu...

Page 11: ...ications Ultra long life filter Light 10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotese...

Page 12: ...or unit If any other error display occurs on the display of the remote controller refer to Test operation on page 10 and the operation manual of the outdoor unit Check the defective point Using the re...

Page 13: ...extremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneou...

Page 14: ...the air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the ma...

Page 15: ...RMINAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRI...

Page 16: ...NOTES NOTES...

Page 17: ...N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control b...

Page 18: ...4PW56483 1 Copyright Daikin...

Reviews: