External static pressure settings

Settings for external static pressure can be achieved in 2 ways:

Using the airflow automatic adjustment function

Airflow automatic adjustment is the volume of blow-off air that
has been automatically adjusted to the rated quantity.

1

Make sure the test run is done with a dry coil.

If the coil is not dry, run the unit for 2 hours with fan only to dry
the coil.

2

Check if the power supply wiring to the air conditioning unit is
completed along with the duct installation.

If a closing damper is installed in the air conditioning unit, make
sure that it is open.
Also check if the air filter is properly attached into the air
passage on the air suction side of the air conditioning unit.

3

If there is more than one air inlet and outlet, adjust the dampers
so that the airflow rate of each air inlet and outlet is conform with
the designed airflow rate. 

Make sure the air conditioning unit is in fan operation mode.
Press and set the airflow adjustment button on the remote
controller to change the airflow rate to H or L.

4

Setting the airflow automatic adjustment settings.

When the air conditioning unit is running in fan operation mode
perform the next steps:
-

stop the air conditioning unit,

-

go to field setting mode,

-

select mode No. 21 (or 11 in case of group setting),

-

set the first code No. to "7",

-

set the second code No. to "03".

Return to normal operating mode after setting these settings
and press the ON/OFF operation button. The operation lamp will
light up and the air conditioning unit will start the fan operation
for airflow automatic adjustment.

After 1 to 8 minutes, the air conditioning unit stops operating
automatically when the fan operation for airflow automatic
adjustment has been carried out, the operation lamp will be off.

5

When the air conditioning unit has stopped, check on an indoor
unit if the second code No. of mode No. 21 is set to "02".

If the air conditioning unit does not stop operating or the second
code No. is not "02", repeat step 4.
If the outdoor unit is not turned on, the display on the remote
controller will show "

U4

" or "

UH

" (refer to 

"Test operation" on

page 10

). However, you can continue setting this function

because these messages are only applicable to outdoor units.
After setting this function, be sure to turn on the outdoor unit
before performing the test operation on the outdoor unit.
If any other error display occurs on the display of the remote
controller, refer to 

"Test operation" on page 10

 and the operation

manual of the outdoor unit. Check the defective point.

Using the remote controller

Check on an indoor unit if the second code of mode No. 21 is set to
"01" (= factory setting). Change the second code according to the
external static pressure of the duct to be connected as shown in
table 2.

Table 2

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".

MAIN/SUB CHANGEOVER

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 18)

(The remote controller PC board is attached to the upper part of
the remote controller.)

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 19)

(Leave the switch of the other remote controller set to "M".)

Do not adjust the dampers during fan operation for
airflow automatic adjustment.

Mode 

No.

First 

code No.

Second 

code No.

Setting content

11 (21)

7

01

Airflow adjustment is OFF

02

Completion of airflow adjustment

03

Start of airflow adjustment

If the external static pressure of the FXSQ140P7VEB
is higher than 100 Pa, do not use airflow automatic
adjustment function.

If there is no change after airflow adjustment in the
ventilation paths, be sure to perform setting the airflow
automatic adjustment again.

Contact your dealer if there is no change after
performing airflow adjustment in the ventilation paths,
after performing the test operation of the outdoor unit
or when the air conditioning unit is moved to another
location.

If booster fans, an outdoor air processing unit or HRV
via duct are used, do not use airflow automatic
adjustment control with a remote controller.

If the ventilation paths have been changed, perform
the setting of the airflow automatic adjustment again
as described above from step 3 onwards.

NOTE

The second code No. is set to "03" by default.

Mode 

No.

First 

code 

No.

Second 

code 

No.

External static pressure (Pa)

FXSQ

20

25

32

40

50

63

80

100 125 140

13 

(23)

6

03

30

30

30

30

30

30

40

40

50

50

04

35

35

35

35

35

40

45

50

55

55

05

40

40

40

40

40

50

50

60

60

60

06

45

45

45

45

45

60

60

70

70

70

07

50

50

50

50

50

70

70

80

80

80

08

55

55

55

60

60

80

80

90

90

90

09

60

60

60

70

70

90

90

100 100 100

10

65

65

65

80

80

100 100 110 110 110

11

70

70

70

90

90

120 120 120

12

100 100

130

13

140

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Summary of Contents for FXSQ140P7VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXSQ20P7VEB FXSQ25P7VEB FXSQ32P7VEB FXSQ40P7VEB FXSQ50P7VEB FXSQ63P7VEB FXSQ80P7VEB FXSQ100P7VEB FXSQ125P7VEB FXSQ140P7VEB System air conditioners...

Page 2: ...680 1 5 3 4 2 7 180 460 160 160 300 425 1 3 2 180 460 350 1 2 2 3 5 0 75 625 A 300 mm 1 1 5 m 2 3 1 4 100 mm 1 0 625 mm 1 1 2 4 5 3 6a 7a 7b 7c 6b 6c 8 9 10 11 2 1 3 5 4 700 630 A B 4 3 2 1 1 1 2 4 5...

Page 3: ...itivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet C 12 Merk...

Page 4: ...etic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do...

Page 5: ...ectrical appliances Noise may be generated depending on the conditions under which the electric wave is generated even if 1 meter is kept When installing the wireless remote controller kit the distanc...

Page 6: ...ce 2 Ceiling opening 3 Service access panel optional accessory 4 Air filter 5 Air inlet duct 6 Duct service opening 7 Interchangeable plate NOTE Before installation of the unit in case of installation...

Page 7: ...ecified refrigerant such as air etc inside the refrigerant circuit Use annealed material only for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tighteni...

Page 8: ...drain raising pipes and insulate them 2 Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less tha...

Page 9: ...ation Note that the operation will restart automatically if the main power supply is turned off and then turned back on again This system consists of multiple indoor units Mark each indoor unit as uni...

Page 10: ...nits less than 12 A Branch the line outside the terminal board of the unit in accordance with electrical equipment standards when using two power wiring of a gauge greater than 2 mm2 1 6 The branch mu...

Page 11: ...ications Ultra long life filter Light 10 000 hrs Heavy 5 000 hrs Long life filter 2 500 hrs 1 250 hrs Standard filter 200 hrs 100 hrs 2 Thermostat sensor selection Use both the unit sensor or remotese...

Page 12: ...or unit If any other error display occurs on the display of the remote controller refer to Test operation on page 10 and the operation manual of the outdoor unit Check the defective point Using the re...

Page 13: ...extremely contaminated If the dirt becomes impossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneou...

Page 14: ...the air inlet and outlet are not blocked Remove any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the ma...

Page 15: ...RMINAL STRIP POWER SUPPLY X2M TERMINAL STRIP CONTROL Y1E ELECTRONIC EXPANSION VALVE Z1C Z2C NOISE FILTER FERRITE CORE Z1F NOISE FILTER CONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRI...

Page 16: ...NOTES NOTES...

Page 17: ...N IN D OUT D F1 F2 F1 F2 Control box P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control b...

Page 18: ...4PW56483 1 Copyright Daikin...

Reviews: