16
|
Unit installation
Installer and user reference guide
52
FXSA15~140A2VEB
VRV system air conditioner
4P599622-1 – 2020.05
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for power
and transmission lines.
▪
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated properly.
▪
Ceiling insulation
. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
▪
Protective guards.
Make sure to install protective guards (field supply) on the
suction and discharge side to prevent somebody from touching the fan blades or
heat exchanger.
▪
Spacing
. Mind the following requirements:
≥
500
c
A
(mm)
b
a
A
Minimum distance to the floor
2.7 m
to avoid accidental touching
2.5 m
in case the fan is covered (e.g. false ceiling, grille, …)
a
Ceiling
b
Floor surface
c
Maintenance space
▪
Discharge grille.
Minimum requirement installation height of discharge grille
≥1.8 m.
Service space and ceiling opening size
Make sure ceiling opening is big enough to ensure a sufficient clearance for
maintenance and service.