background image

• Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE

• VRV Systems • Indoor Units

2

1

Specifications

3

1

In

do

or

 U

ni

t

VR

Sy

st

em

s

FX

NQ

-M

AV

E

Co

nc

ea

le

F

1-1  Technical Specifications

FXNQ20MAVE

FXNQ25MAVE

FXNQ32MAVE

FXNQ40MAVE

FXNQ50MAVE

FXNQ63MAVE

Capacity

Cooling

kW

2.20

2.80

3.60

4.50

5.60

7.10

Heating

kW

2.50

3.20

4.00

5.00

6.30

8.00

Power Input (50Hz)

Cooling

kW

0.049

0.049

0.090

0.090

0.110

0.110

Heating

kW

0.049

0.049

0.090

0.090

0.110

0.110

Power Input (60Hz)

Cooling

kW

0.047

0.047

0.079

0.084

0.105

0.108

Heating

kW

0.047

0.047

0.079

0.084

0.105

0.108

Casing

Material

Galvanised steel

Dimensions

Unit

Height

mm

610

610

610

610

610

610

Width

mm

930

930

1070

1070

1350

1350

Depth

mm

220

220

220

220

220

220

Weight

Unit

kg

19

19

23

23

27

27

Heat Exchanger

Dimensions

Nr of Rows

3

3

3

3

3

3

Fin Pitch

mm

1.50

1.50

1.50

1.50

1.50

1.50

Face Area

0.159

0.159

0.200

0.200

0.282

0.282

Nr of Stages

14

14

14

14

14

14

Fan

Type

Sirocco fan

Quantity

1

1

1

1

1

1

Air Flow Rate

Cooling

High

m³/min

7.00

7.00

8.00

11.00

14.00

16.00

Low

m³/min

6.00

6.00

6.00

8.50

11.00

12.00

Fan

Motor

Quantity

1

1

1

1

1

1

Model

D14B20

D14B20

2D14B13

2D14B13

2D14B20

2D14B20

Output (high)

W

15

15

25

25

35

35

Drive

Direct drive

Refrigerant

Name

R-410A

Cooling

Sound Pressure

High

dBA

35.0

35.0

35.0

38.0

39.0

40.0

Low

dBA

32.0

32.0

32.0

33.0

34.0

35.0

Piping connections

Liquid (OD)

Type

Flare connection

Diameter

mm

6.35

6.35

6.35

6.35

6.35

9.52

Gas

Type

Flare connection

Diameter

mm

12.7

12.7

12.7

12.7

12.7

15.9

Drain

Diameter

mm

21

21

21

21

21

21

Heat Insulation

Glass Fiber/Urethane Foam

Air Filter

Resin net with mold resistance

Refrigerant control

Electronic expansion valve

Temperature control

Microprocessor thermostat for cooling and heating

Safety devices

PC board fuse

Fan motor thermal protector

Standard Accessories Standard Accessories

Installation and operation manual

Insulation for fitting

Drain hose

Clamps

Screws

Washer

Level adjustment screw

Notes

Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB,  outdoor temperature 

: 35°CDB,  equivalent refrigerant piping : 7.5m (horizontal)

Nominal heating capacities are based on : indoor temperature : 20°CDB,  outdoor temperature : 7°CDB, 

6°CWB,  equivalent refrigerant piping : 7.5m (horizontal)

Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.

Sound pressure levels are measured at 220V

1-2  Electrical Specifications (50Hz)

FXNQ20MAVE

FXNQ25MAVE

FXNQ32MAVE

FXNQ40MAVE

FXNQ50MAVE

FXNQ63MAVE

Power Supply

Name

VE

Phase

1~

Frequency

Hz

50

Voltage

V

220-240

Summary of Contents for FXNQ-MAVE Series

Page 1: ...technical data Concealed Floor Standing Unit FXNQ MAVE air conditioning systems...

Page 2: ...ications 60Hz 3 2 Safety device settings 4 3 Options 4 4 Control systems 5 5 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 8 6 Dimensional drawing centre of gravity 10 Dimensiona...

Page 3: ...high W 15 15 25 25 35 35 Drive Direct drive Refrigerant Name R 410A Cooling Sound Pressure High dBA 35 0 35 0 35 0 38 0 39 0 40 0 Low dBA 32 0 32 0 32 0 33 0 34 0 35 0 Piping connections Liquid OD Typ...

Page 4: ...se a circuit breaker 1 3 Electrical Specifications 60Hz FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Power Supply Name VE Phase 1 Frequency Hz 60 Voltage V 220 Current Minimum cir...

Page 5: ...3 Options 3D034529C FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA PC BOARD FUSE 250V 10A FAN MOTOR THERMAL PROTECTOR C OFF 135 10 ON 120 or less FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA F...

Page 6: ...NQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA CENTRALISED REMOTE CONTROL DCS302C51 UNIFIED ON OFF CONTROL DCS301C51 SCHEDULE TIMER DST301C51 FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA...

Page 7: ...31 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 2 1 9 33 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 1 1 9 35 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 0 2 0 3 1 1 9 37 0 1 9 1 6 2 3...

Page 8: ...31 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 2 3 8 6 4 3 7 33 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 1 3 8 6 3 3 6 35 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 5 9 4 0 6 0 3 8 6 2 3 6 37 0 3 8 3 0 4 5...

Page 9: ...3 0 3 0 2 8 3 0 2 2 3 1 3 1 3 1 3 1 3 0 2 8 5 0 4 1 3 3 3 2 3 2 3 1 3 0 2 8 7 0 6 0 3 4 3 4 3 2 3 1 3 0 2 8 9 0 7 9 3 5 3 4 3 2 3 1 3 0 2 8 11 0 9 8 3 6 3 4 3 2 3 1 3 0 2 8 13 0 11 8 3 6 3 4 3 2 3 1 3...

Page 10: ...5 8 5 8 5 5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6 1 5...

Page 11: ...Description 1 Liquid pipe connection port 6 4 flare connection 2 Gas pipe connection port 12 7 flare connection 3 Drain pipe connection port O D 21 4 Switch box 5 Air filter FXNQ32 40MA 3D038864B 150...

Page 12: ...4 7 hole Total on right left 2 12x18 slot hole Hole for fixing to the floor Top plate 10 4 7 hole Total on front rear Hole for fixing to the floor 4 12x30 slot hole Hole for rear mounting NOTES 1 Loc...

Page 13: ...oor Standing Unit FXNQ MAVE VRV Systems Indoor Units 12 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 3 6 FXNQ MA 4D034533B Model A FXNQ20MA 395 FXNQ25MA 395 FXNQ32MA 465 FXNQ40MA 465...

Page 14: ...or Units 13 Indoor Units Concealed Floor Standing Unit FXNQ MAVE 7 Piping diagram 3 7 FXNQ MA 4D034245A Heat exchanger Fan Filter Filter Electronic expansion valve Liquid pipe connection port Gas pipe...

Page 15: ...ontrol In details refer to the installation manual attached to the unit 3 Use copper conductors only Indoor unit R2T R3T Thermistor Coil A1P Printed circuit board T1R Transformer 220 240V 22V C1 Capac...

Page 16: ...pressure level dB 0 dB 0 0002 bar Scale 220V 240V H L H L A 35 32 37 34 C 39 37 41 39 220V 240V 1 5m 1 5m 0 1m Board Duct Field work Microphone Air discharge option NOTES 1 Over all dB B G N is alread...

Page 17: ...ns Power source 220 240V 220V 50 60Hz JIS standard 4 Location of microphone 5 Operating noise differs with operation and ambient conditions FXNQ63MA 4D034538A Approximate threshold hearing for continu...

Page 18: ...010 1 Open the lid of control panel both left and right 2 Remove screws both left and right 3 Push the knobs both left and right to the rear 4 Lift the front of the top plate 5 Lower the front panel t...

Page 19: ...ndoor Units 18 10 Installation 10 2 Service space 3 10 FXNQ MA 3P086154 1 4 A or more Maintenance area B or more 625 80 or more NOTE 1 Leave sufficient clearance for air inlet and maintenance Model A...

Page 20: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: