background image

• VRV Systems • Indoor Units

9

• Indoor Units • Concealed Floor Standing Unit • FXNQ-MAVE

5

Capacity tables

5 - 2 Heating capacity tables

3

5

FXNQ-MA

CA03A095

Unit Size

Nominal capacity

Outdoor

air temperature

Indoor air temperature 

ƒ

CDB

16.0

18.0

20.0

21.0

22.0

24.0

ƒ

CDB

ƒ

CWB

kW

kW

kW

kW

kW

kW

50

6.3

-19.8

-20.0

3.7 3.7 3.7 3.7 3.7 3.7 

-18.8

-19.0

3.8 3.8 3.8 3.8 3.8 3.8 

-16.7

-17.0

4.1 4.0 4.0 4.0 4.0 4.0 

-14.7

-15.0

4.3 4.3 4.3 4.2 4.2 4.2 

-12.6

-13.0

4.5 4.5 4.5 4.5 4.5 4.5 

-10.5

-11.0

4.7 4.7 4.7 4.7 4.7 4.7 

-9.5

-10.0

4.8 4.8 4.8 4.8 4.8 4.8 

-8.5

-9.1

4.9 4.9 4.9 4.9 4.9 4.9 

-7.0

-7.6

5.1 5.1 5.1 5.1 5.1 5.1 

-5.0

-5.6

5.3 5.3 5.3 5.3 5.3 5.3 

-3.0

-3.7

5.5 5.5 5.5 5.5 5.5 5.5 

0.0

-0.7

5.9 5.9 5.8 5.8 5.8 5.5 

3.0

2.2

6.2 6.2 6.2 6.1 5.9 5.5 

5.0

4.1

6.4 6.4 6.3 6.1 5.9 5.5 

7.0

6.0

6.6 6.6 6.3 6.1 5.9 5.5 

9.0

7.9

6.8 6.7 6.3 6.1 5.9 5.5 

11.0

9.8

7.0 6.7 6.3 6.1 5.9 5.5 

13.0

11.8

7.1 6.7 6.3 6.1 5.9 5.5 

15.0

13.7

7.1 6.7 6.3 6.1 5.9 5.5 

63

8.0

-19.8

-20.0

4.7 4.7 4.7 4.7 4.7 4.7 

-18.8

-19.0

4.9 4.9 4.8 4.8 4.8 4.8 

-16.7

-17.0

5.1 5.1 5.1 5.1 5.1 5.1 

-14.7

-15.0

5.4 5.4 5.4 5.4 5.4 5.4 

-12.6

-13.0

5.7 5.7 5.7 5.7 5.7 5.7 

-10.5

-11.0

6.0 6.0 6.0 6.0 6.0 5.9 

-9.5

-10.0

6.1 6.1 6.1 6.1 6.1 6.1 

-8.5

-9.1

6.3 6.3 6.2 6.2 6.2 6.2 

-7.0

-7.6

6.5 6.5 6.4 6.4 6.4 6.4 

-5.0

-5.6

6.8 6.7 6.7 6.7 6.7 6.7 

-3.0

-3.7

7.0 7.0 7.0 7.0 7.0 7.0 

0.0

-0.7

7.5 7.4 7.4 7.4 7.4 7.0 

3.0

2.2

7.9 7.8 7.8 7.7 7.5 7.0 

5.0

4.1

8.1 8.1 8.0 7.7 7.5 7.0 

7.0

6.0

8.4 8.4 8.0 7.7 7.5 7.0 

9.0

7.9

8.7 8.5 8.0 7.7 7.5 7.0 

11.0

9.8

8.9 8.5 8.0 7.7 7.5 7.0 

13.0

11.8

9.0 8.5 8.0 7.7 7.5 7.0 

15.0

13.7

9.0 8.5 8.0 7.7 7.5 7.0 

Summary of Contents for FXNQ-MAVE Series

Page 1: ...technical data Concealed Floor Standing Unit FXNQ MAVE air conditioning systems...

Page 2: ...ications 60Hz 3 2 Safety device settings 4 3 Options 4 4 Control systems 5 5 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 8 6 Dimensional drawing centre of gravity 10 Dimensiona...

Page 3: ...high W 15 15 25 25 35 35 Drive Direct drive Refrigerant Name R 410A Cooling Sound Pressure High dBA 35 0 35 0 35 0 38 0 39 0 40 0 Low dBA 32 0 32 0 32 0 33 0 34 0 35 0 Piping connections Liquid OD Typ...

Page 4: ...se a circuit breaker 1 3 Electrical Specifications 60Hz FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE Power Supply Name VE Phase 1 Frequency Hz 60 Voltage V 220 Current Minimum cir...

Page 5: ...3 Options 3D034529C FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA PC BOARD FUSE 250V 10A FAN MOTOR THERMAL PROTECTOR C OFF 135 10 ON 120 or less FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA F...

Page 6: ...NQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA CENTRALISED REMOTE CONTROL DCS302C51 UNIFIED ON OFF CONTROL DCS301C51 SCHEDULE TIMER DST301C51 FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA...

Page 7: ...31 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 2 1 9 33 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 1 2 0 3 1 1 9 35 0 1 9 1 6 2 3 1 8 2 6 2 0 2 8 2 1 3 0 2 1 3 0 2 0 3 1 1 9 37 0 1 9 1 6 2 3...

Page 8: ...31 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 2 3 8 6 4 3 7 33 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 6 0 4 0 6 1 3 8 6 3 3 6 35 0 3 8 3 0 4 5 3 4 5 2 3 8 5 6 3 9 5 9 4 0 6 0 3 8 6 2 3 6 37 0 3 8 3 0 4 5...

Page 9: ...3 0 3 0 2 8 3 0 2 2 3 1 3 1 3 1 3 1 3 0 2 8 5 0 4 1 3 3 3 2 3 2 3 1 3 0 2 8 7 0 6 0 3 4 3 4 3 2 3 1 3 0 2 8 9 0 7 9 3 5 3 4 3 2 3 1 3 0 2 8 11 0 9 8 3 6 3 4 3 2 3 1 3 0 2 8 13 0 11 8 3 6 3 4 3 2 3 1 3...

Page 10: ...5 8 5 8 5 5 3 0 2 2 6 2 6 2 6 2 6 1 5 9 5 5 5 0 4 1 6 4 6 4 6 3 6 1 5 9 5 5 7 0 6 0 6 6 6 6 6 3 6 1 5 9 5 5 9 0 7 9 6 8 6 7 6 3 6 1 5 9 5 5 11 0 9 8 7 0 6 7 6 3 6 1 5 9 5 5 13 0 11 8 7 1 6 7 6 3 6 1 5...

Page 11: ...Description 1 Liquid pipe connection port 6 4 flare connection 2 Gas pipe connection port 12 7 flare connection 3 Drain pipe connection port O D 21 4 Switch box 5 Air filter FXNQ32 40MA 3D038864B 150...

Page 12: ...4 7 hole Total on right left 2 12x18 slot hole Hole for fixing to the floor Top plate 10 4 7 hole Total on front rear Hole for fixing to the floor 4 12x30 slot hole Hole for rear mounting NOTES 1 Loc...

Page 13: ...oor Standing Unit FXNQ MAVE VRV Systems Indoor Units 12 6 Dimensional drawing centre of gravity 6 2 Centre of gravity 3 6 FXNQ MA 4D034533B Model A FXNQ20MA 395 FXNQ25MA 395 FXNQ32MA 465 FXNQ40MA 465...

Page 14: ...or Units 13 Indoor Units Concealed Floor Standing Unit FXNQ MAVE 7 Piping diagram 3 7 FXNQ MA 4D034245A Heat exchanger Fan Filter Filter Electronic expansion valve Liquid pipe connection port Gas pipe...

Page 15: ...ontrol In details refer to the installation manual attached to the unit 3 Use copper conductors only Indoor unit R2T R3T Thermistor Coil A1P Printed circuit board T1R Transformer 220 240V 22V C1 Capac...

Page 16: ...pressure level dB 0 dB 0 0002 bar Scale 220V 240V H L H L A 35 32 37 34 C 39 37 41 39 220V 240V 1 5m 1 5m 0 1m Board Duct Field work Microphone Air discharge option NOTES 1 Over all dB B G N is alread...

Page 17: ...ns Power source 220 240V 220V 50 60Hz JIS standard 4 Location of microphone 5 Operating noise differs with operation and ambient conditions FXNQ63MA 4D034538A Approximate threshold hearing for continu...

Page 18: ...010 1 Open the lid of control panel both left and right 2 Remove screws both left and right 3 Push the knobs both left and right to the rear 4 Lift the front of the top plate 5 Lower the front panel t...

Page 19: ...ndoor Units 18 10 Installation 10 2 Service space 3 10 FXNQ MA 3P086154 1 4 A or more Maintenance area B or more 625 80 or more NOTE 1 Leave sufficient clearance for air inlet and maintenance Model A...

Page 20: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: