background image

7

3P086154-3R

English

 CAUTION

• 

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-

ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has an extremely negative effect on refrigerant pip

-

ing systems. For instance, if chlorine based flux is used, it 
will cause pipe corrosion. If the flux contains fluorine, it will 

damage the refrigerant oil.)

 DANGER

• 

Use of oxygen may cause an explosion resulting in serious 

injury or death. Only use nitrogen gas.

• 

Refrigerant gas may produce toxic gas if it comes in contact 
with fire such as from a fan heater, stove or cooking device. 
Exposure to this gas could cause severe injury or death.

• 

Before brazing local refrigerant piping, nitrogen gas shall 

be blown through the piping to expel air from the piping.

 

If brazing is done without nitrogen gas blowing, a large 

amount of oxide film develops inside the piping, and could 

cause system malfunction.

• 

When brazing the refrigerant piping, only begin brazing 
after having carried out nitrogen substitution or while insert-
ing nitrogen into the refrigerant piping. Once this is done, 

connect the indoor unit with a flared or a flanged connec

-

tion.

• 

Nitrogen should be set to 2.9 psi (0.02 MPa) with a pres-
sure-reducing valve if brazing while inserting nitrogen into 
the piping.

Refrigerant 

piping

Part to be 

brazed

Taping

Pressure-

reducing 

valve

Hands valve

Nitrogen

Nitrogen

 NOTE

Use the flare nuts attached with the unit.

• 

Refer to Table 2 for tightening torque.

Table 2

Piping 

size 

[in. (mm)]

Tightening 

torque 

[lbf·ft. (N·m)]

Dimension for 

processing flare 

A [in. (mm)]

Flare shape

f

 1/4 

(6.4)

10.4 – 12.7 

(15.7±1.5)

0.342 – 0.358

(8.9±0.2)

R0.016-0.031

90°±2°

A

45°±2°

f

 3/8 

(9.5)

24.1 – 29.4

(36.3±3.6)

0.504 – 0.520

(13.0±0.2)

f

 1/2 

(12.7)

36.5 – 44.5

(54.9±5.4)

0.638 – 0.654

(16.4±0.2)

f

 5/8 

(15.9)

45.6 – 55.6

(68.6±6.8)

0.760 – 0.776

(19.5±0.2)

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow at 
the installation method mentioned below.

After the work is finished, make sure to check that 

there is no gas leak.

When you keep on tightening the flare nut with a span

-

ner, there is a point where the tightening torque suddenly 

increases. From that position, further tighten the flare nut at 

the angle shown below:

Table 3

Piping size 

[in. (mm)]

Tightening 

angle

Recommended arm length of 

tool used [in. (mm)]

f

 1/4 (6.4)

60° – 90°

Approx. 6 (150)

f

 3/8 (9.5)

60° – 90°

Approx. 8 (200)

f

 1/2 (12.7)

30° – 60°

Approx. 10 (250)

f

 5/8 (15.9)

30° – 60°

Approx. 12 (300)

7.  DRAIN PIPING WORK

Install the drain pipe as shown below. Improperly installed 

piping could lead to leaks and eventually wet furniture 

and belongings.
(1) 

Carry out the drain piping.

3/4 drain pipe

2 (50) or more

Drip pan

Metal clamp 

(accessory) (2)

Drain hose 

(accessory) (1)

Cut to suitable length

[length : in. (mm)]

Connect the drain 
hose (1) using the 
attached hose and 
parts, as shown in 
the right drawing.

Piping process 

inside unit

Tilt

• 

If converging multiple drain pipes, install according to the 
procedure shown below.

Slope downwards at a gradient 
of at least 1/100

Select converging drain pipes whose gauge is suitable for the 
operating capacity of the unit.

(2) 

After piping work is finished, check drainage flows 

smoothly.

• 

Add approximately 1/4 gal (1L) of water slowly from the 
air outlet and check drainage flow.

(3) 

Be sure to insulate all indoor pipes.

01_EN_3P086154-3R.indd   7

1/22/2015   2:28:11 PM

Summary of Contents for FXLQ07MVJU

Page 1: ...STALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA SYSTEM Inverter Air Conditioners 3P086154 3R English Français Español 00_CV_3P08...

Page 2: ...ls are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transportation mate rials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood parts including plastic packing ma terials used for transportation may cause injuries or death by suffocation WARNING Only qualified personnel must c...

Page 3: ...procedures Since R410A is a blend the required additional refrig erant must be charged in its liquid state If the refriger ant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R410A See the catalog for in door models that can be connected Normal operation is not possible when connected to other units Indoor units are for indoor in...

Page 4: ...c interference WARNING Entrust installation to the place of purchase or an autho rized serviceman Improper installation could lead to leaks and in worse cases electric shock of fire Use of unspecified parts could lead to the unit falling leaks and in worse cases electric shock or fire NOTE Be sure to read this manual before installing the indoor unit 2 1 ACCESSORIES Check the following accessories...

Page 5: ...lammable gas leakage Piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manu al of the outdoor unit WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could fall out of place and cause serious injury Do not install unit in an area where flammable materials are present due to the risk explosion ...

Page 6: ... designated by Daikin 1 Level the indoor unit with the leveling screws 7 If the floor is too uneven to level the unit place the unit on a flat base and level Leveling screws 7 accessory 2 If the unit is in danger of falling over either fasten to the wall using the holes provided or fasten to the floor with an optional floor fastener 3 The legs can be retracted if the indoor unit is to be hung on a...

Page 7: ...t venti late the room thoroughly right away The outdoor unit is charged with refrigerant Use copper alloy seamless pipes To prevent flare nut cracking and gas leaks be sure to use both a spanner and torque wrench together as shown in the drawing when connecting or disconnecting pipes to from the unit Refer to Table 2 for the dimensions of flare When making a flare connection coat the flared inner ...

Page 8: ...e A in mm Flare shape f 1 4 6 4 10 4 12 7 15 7 1 5 0 342 0 358 8 9 0 2 R0 016 0 031 90 2 A 4 5 2 f 3 8 9 5 24 1 29 4 36 3 3 6 0 504 0 520 13 0 0 2 f 1 2 12 7 36 5 44 5 54 9 5 4 0 638 0 654 16 4 0 2 f 5 8 15 9 45 6 55 6 68 6 6 8 0 760 0 776 19 5 0 2 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may foll...

Page 9: ...n or explosion may occur if the gas leaks Water piping Hard vinyl tubes are not effective ground Lightning conductor or telephone ground wiring Electric potential may rise abnormally if struck by a light ning bolt For electric wiring work refer to also the WIRING DIA GRAM attached to the control box cover Carry out wiring between the outdoor units indoor units and the remote controllers according ...

Page 10: ...rcuit may occur inside the control box When clamping the wirings be sure no tension is applied to the wire connections by using the included clamps Also when wiring make sure the control box cover fits snugly by arranging the wirings neatly and attaching the control box cover firmly When attaching the control box cover make sure no wirings get caught in the edges Pass the wirings through the hole ...

Page 11: ...it No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit For use with 2 remote controllers IN D OUT D F1 F2 F1 F2 F1 F2 P1 P2 T1 T2 F1 F2 T1 T2 F1 F2 T1 T2 F1 F2 T1 T2 L2L1 L2L1 L2L1 L2L1 Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz L1 L2 P2 P1 P2 P...

Page 12: ...TION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERA TION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SETTING 10 FIELD SETTING Refer to also the installation manual attached to the outdoor unit CAUTION Before carrying out field setting check the items mentioned in Clause 2 a Items to be checked after completion of work on page 3 ...

Page 13: ...FORCED OFF wiring are connected incorrectly The transmission wiring is disconnected No indication The power supply to the indoor unit is not made The power supply work to the indoor unit is not carried out The remote controller wiring and the trans mission wiring and FORCED OFF wiring are connected incorrectly The remote controller wiring is discon nected CAUTION After test operation is completed ...

Page 14: ... 1502 HT 3P086154 3R EM04A011B 00_CV_3P086154 3R indd 2 1 19 2015 3 21 12 PM ...

Reviews: