11

3P086154-3R

English

Terminal for remote 

controller wiring (P1, P2)

No polarity

Remote 

controller 2

(Sub)

Remote 

controller 1

(Main)

Terminal block 

(X2M)

F2

F1

P2

P1

T2

T1

< Caution >

• 

When using the group control and the 2 remote control-
lers control at the same time, connect the remote con-
troller 2 (Sub) to the indoor unit at the end of the cross-
over wiring (the largest No.). 

Indoor unit 1

Indoor unit 2

Indoor unit 

largest No.

Remote 

controller 2 

(Sub)

Crossover 

wiring (Remote 

controller)

Remote 

controller 1 

(Main)

9-4 

FOR CENTRALIZED CONTROL

• 

When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on 
the remote controller. 
For details, refer to the manuals attached to the centralized 
equipment.

• 

Connect the centralized equipment to the indoor unit con-
nected to the remote controller.

9-5  FOR REMOTE CONTROL (FORCE OFF OR ON / 

OFF OPERATION) 

(1) 

Wiring method and specification

• 

Remote control is available by connecting the external 

input to the terminal T1 and T2 on the terminal block for 
remote controller and transmission wiring (X2M).

F2 T1 T2

FORCED

OFF

Input A

Wiring  

specification

2-conductor, 
stranded non-
shielded copper 
cable/PVC or 
vinyl jacket.

Gauge

AWG18-16

Wiring length

Max. 328 ft. 

(100 m)

External 

 

contact spec

Contact that can 
make and break 
the min. load of 
15 V DC , 1 mA

(2)  Actuation

• 

Input A of FORCED OFF and ON/OFF OPERATION 
will be as the table shown below.

Input A = ON

Input A = OFF

In case of FORCED 
OFF

Remote controller 

prohibited

Remote controller 

permitted

In case of ON/OFF 
OPERATION

Operation

Stop

(3)  How to choose FORCED OFF or ON/OFF OPERA-

TION 

• 

For choosing FORCED OFF or ON/OFF OPERATION, 
setting by remote controller is required.
(Refer to 

10. FIELD SETTING

.)

10. 

FIELD SETTING

<<Refer to also the installation manual attached to the 

outdoor unit.>>

 CAUTION

Before carrying out field setting, check the items mentioned in 

Clause 2: 

a. Items to be checked after completion of work

 

on page 3. Check if all the installation and piping works for 

the air conditioner are completed.

• 

Check if the control box covers of the air conditioner are 

closed.

< FIELD SETTING >

<<After turn on the power supply, carry out field setting 

from the remote controller according to the installation 

state.>>

• 

Carry out setting at 3 places, MODE NO., FIRST CODE 
NO. and SECOND CODE NO. 
The settings shown by 

 in the table indicate those 

when shipped from the factory.

• 

The method of setting procedure and operation is shown in 
the installation manual attached to the remote controller.
(Note)  Though setting of MODE NO. is carried out as a 

group, if you intend to carry out individual setting by 

each indoor unit or confirmation after setting, carry 

out setting with the MODE NO. shown in the paren-
thesis ( ). 

• 

In case of remote control, for changeover of input to 
FORCED OFF or to ON/OFF OPERATION.

[1] Enter into the field setting mode with the remote controller.

[2] Select MODE NO. 

12

.

[3] Set the FIRST CODE NO. to 

1

.

[4-1] For FORCE OFF, set the SECOND CODE NO. to 

01

.

[4-2] For ON/OFF OPERATION, set the SECOND CODE 

NO. to 

02

.

(It is set to FORCE OFF when shipped from the factory.)

• 

Ask your customer to keep the manual attached to the 
remote controller together with the operation manual.

• 

Do not carry out settings other than those shown in the 
table.

01_EN_3P086154-3R.indd   11

1/22/2015   2:28:13 PM

Summary of Contents for FXLQ07MVJU

Page 1: ...STALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA SYSTEM Inverter Air Conditioners 3P086154 3R English Français Español 00_CV_3P08...

Page 2: ...ls are present due to risk of explosions that can cause serious injury or death Safely dispose all packing and transportation mate rials in accordance with federal state local laws or ordinances Packing materials such as nails and other metal or wood parts including plastic packing ma terials used for transportation may cause injuries or death by suffocation WARNING Only qualified personnel must c...

Page 3: ...procedures Since R410A is a blend the required additional refrig erant must be charged in its liquid state If the refriger ant is charged in a state of gas its composition can change and the system will not work properly The indoor unit is for R410A See the catalog for in door models that can be connected Normal operation is not possible when connected to other units Indoor units are for indoor in...

Page 4: ...c interference WARNING Entrust installation to the place of purchase or an autho rized serviceman Improper installation could lead to leaks and in worse cases electric shock of fire Use of unspecified parts could lead to the unit falling leaks and in worse cases electric shock or fire NOTE Be sure to read this manual before installing the indoor unit 2 1 ACCESSORIES Check the following accessories...

Page 5: ...lammable gas leakage Piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manu al of the outdoor unit WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could fall out of place and cause serious injury Do not install unit in an area where flammable materials are present due to the risk explosion ...

Page 6: ... designated by Daikin 1 Level the indoor unit with the leveling screws 7 If the floor is too uneven to level the unit place the unit on a flat base and level Leveling screws 7 accessory 2 If the unit is in danger of falling over either fasten to the wall using the holes provided or fasten to the floor with an optional floor fastener 3 The legs can be retracted if the indoor unit is to be hung on a...

Page 7: ...t venti late the room thoroughly right away The outdoor unit is charged with refrigerant Use copper alloy seamless pipes To prevent flare nut cracking and gas leaks be sure to use both a spanner and torque wrench together as shown in the drawing when connecting or disconnecting pipes to from the unit Refer to Table 2 for the dimensions of flare When making a flare connection coat the flared inner ...

Page 8: ...e A in mm Flare shape f 1 4 6 4 10 4 12 7 15 7 1 5 0 342 0 358 8 9 0 2 R0 016 0 031 90 2 A 4 5 2 f 3 8 9 5 24 1 29 4 36 3 3 6 0 504 0 520 13 0 0 2 f 1 2 12 7 36 5 44 5 54 9 5 4 0 638 0 654 16 4 0 2 f 5 8 15 9 45 6 55 6 68 6 6 8 0 760 0 776 19 5 0 2 Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may foll...

Page 9: ...n or explosion may occur if the gas leaks Water piping Hard vinyl tubes are not effective ground Lightning conductor or telephone ground wiring Electric potential may rise abnormally if struck by a light ning bolt For electric wiring work refer to also the WIRING DIA GRAM attached to the control box cover Carry out wiring between the outdoor units indoor units and the remote controllers according ...

Page 10: ...rcuit may occur inside the control box When clamping the wirings be sure no tension is applied to the wire connections by using the included clamps Also when wiring make sure the control box cover fits snugly by arranging the wirings neatly and attaching the control box cover firmly When attaching the control box cover make sure no wirings get caught in the edges Pass the wirings through the hole ...

Page 11: ...it No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit For use with 2 remote controllers IN D OUT D F1 F2 F1 F2 F1 F2 P1 P2 T1 T2 F1 F2 T1 T2 F1 F2 T1 T2 F1 F2 T1 T2 L2L1 L2L1 L2L1 L2L1 Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz Power supply single phase 208 230 V 60 Hz L1 L2 P2 P1 P2 P...

Page 12: ...TION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERA TION For choosing FORCED OFF or ON OFF OPERATION setting by remote controller is required Refer to 10 FIELD SETTING 10 FIELD SETTING Refer to also the installation manual attached to the outdoor unit CAUTION Before carrying out field setting check the items mentioned in Clause 2 a Items to be checked after completion of work on page 3 ...

Page 13: ...FORCED OFF wiring are connected incorrectly The transmission wiring is disconnected No indication The power supply to the indoor unit is not made The power supply work to the indoor unit is not carried out The remote controller wiring and the trans mission wiring and FORCED OFF wiring are connected incorrectly The remote controller wiring is discon nected CAUTION After test operation is completed ...

Page 14: ... 1502 HT 3P086154 3R EM04A011B 00_CV_3P086154 3R indd 2 1 19 2015 3 21 12 PM ...

Reviews: