background image

or other field-supply parts for the newly-mounted 

ceiling. Before continuing installation, adjust the 

clearance between the lifting screw and the ceiling to 

50-80mm.

[Installation example] 

222222221 

Figure 5 

Roof 

Long nut or thread 

line equipment 

Ceiling 

Note) All the above parts are supplied at the installation site. 

5. Indoor unit installation

Be sure to use only the specified parts for installation 

work. 

installation procedure for locations with newly­

mounted ceiling: 

(1) --+ (2) --+ (3) --+ (4) --+ (5)

Installation procedure for locations with existing ceiling:

(1) --+ (3) --+ (4) --+ (5)

(1 )Temporarily  install the indoor units 

• Attach the hanger bracket to the lifting screw. Be sure to

secure the hanger bracket firmly at the upper and lower

ends using the nuts and hanger washers®· The washer
fixing  plate (!)  can  prevent  the  hanger  washer ® from
slipping off.

Hanger washers@ 

(accessories) 

Hanger bracket 

Washer Clamp (7) 

(accessory) 

Insert 

Upper side nut 

[Secure the hanger bracket] 

[Washer clamp(7} fixing method] 

Figure 6 

Figure 7 

(2)For dimensions of the ceiling opening, refer to the

paper board for ceiling opening. Consult your builder or

carpenter for details.

• Center of the ceiling opening is marked on the paper

board for ceiling  opening.  Center of the units is in line

with that of the ceiling opening.

• Fix the paper board for ceiling opening to the units

using 4 screws ®·  In this case, make the hole on the

unit's hanger bracket corresponded to the mounting

hole on the paper board for ceiling opening.

• Relative positions of the main unit and ceiling are marked

on the paper board for ceiling opening. Adjust the height
of the unit body accordingly.

□  □ 

Screws@ 

(accessories) 

Paper board for ceiling opening 

(within the bottom box) 

[Secure the mounting paper pattern] 

Figure 8 

(3)Adjust the levelness of the air conditioner.

• The  indoor  unit  is  equipped  with  a  built-in  drain  pump

and float switch. Adjust the levelness using a level meter
or polyethylene pipe filled with water.

Levelness of unit should not exceed 0.5 deg down at opposite 

side of drain pump. 

Level 

meter 

Vinyl Tube 

-�Caution---------------­

If the unit tilts to the opposite flow direction of the condensed 

water,  the  float  switch  will  not  operate  normally,  which  will 

cause water leakage. 

(4)Pull out the inserted washer fixing plate(!) which is used

to prevent the washer from slipping off and tighten the 
upper nut.

(5)Remove the paper board for ceiling opening.

6. Decorative panel installation

<Refer to panel operation & installation manual for 

detailed decorative panel installation.> 

7. Refrigerant piping installation

<For installing the refrigerant piping of the outdoor unit, 

refer to the installation manual included with the outdoor 

unit.> 

<Insulate both gas side piping and liquid  side piping 

effectively. Otherwise, it may cause water leakage. Use 

the insulation material which can withstand high 

temperature of 120  °C or more. Besides, reinforce the 

insulation of the refrigerant piping in accordance with 

the installation environment. If not reinforced, 

condensation could form on the surface of the 

insulation material.> 

<Be sure to check the refrigerant is R41 0A before 

performing refrigerant piping installation. Adopting 

other refrigerants may result in the abnormal operation 

of the unit.> 

-�Caution---------------­

This product is a dedicated model for the new refrigerant R41 0A. 
Always follow instructions below to perform installation work. 

• Be sure to use the special pipe cutters and flaring tools for

R410A.

• When connecting the flaring,  only coat the refrigerant oil

(ester or ether oil) to the inner side of the flaring.

• Always use the flaring nut included with the unit. (Do not

use other flaring nuts such as  1-type flaring nut. Using

other flaring nuts may lead to refrigerant leakage.)

• To prevent entry of any dirt, dust or moisture into the piping,

adjust the piping through pinching or sealing methods.

Summary of Contents for FXKQ32AVM

Page 1: ...ingle Flow Type FXKQ32AV16 FXKQ40AV16 FXKQS0AV16 FXKQ63AV16 FXKQ32AVM FXKQ40AVM FXKQS0AVM FXKQ63AVM CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE R...

Page 2: ......

Page 3: ...on 6 8 Drain piping installation 8 9 Electrical wiring work 9 9 1 Overview 9 9 2 Specifications of the standard electric wires 9 9 3 Electrical characteristics 10 10 Wiring example 10 10 1 How to conn...

Page 4: ...nce with your local laws and regulations as well as this manual 2 An insufficient power supply capacity or improper electrical operation may lead to electric shocks or fire hazards Use the specified w...

Page 5: ...ant must be charged in its liquid state If the system is charged with refrigerant in its gaseous state due to composition change the system will not function normally The indoor unit is designed for R...

Page 6: ...The unit doesn t operate normally or with parts burnt out Are the indoor and outdoor units Insufficient cool air suction inlet and air outlet or hot air blocked by any obstacles Are the refrigerant p...

Page 7: ...instances 2 Perform installation with a lifting screw Study if the ceiling is strong enough to hold the weight of the indoor unit If the ceiling is not strong enough reinforce the ceiling in advance R...

Page 8: ...quipped with a built in drain pump and float switch Adjust the levelness using a level meter or polyethylene pipe filled with water Levelness of unit should not exceed 0 5 deg down at opposite side of...

Page 9: ...t recommended and only use in emergency It s necessary to use the torque wrench to install the units If you have to install the units but without the torque wrench then perform installation based on f...

Page 10: ...the drain piping the piping may be clogged To prevent the piping from bending and sagging down secure them every 1 1 5m using slings Use the accessory drain hose CD and metal clip The drain hose CD sh...

Page 11: ...the Remote controller installation manual included with it All wiring work must be carried out by the qualified electricians The system includes several indoor units Name each indoor unit after A unit...

Page 12: ...rrent Remote controller wiring weak current Caution Outside the air conditioner don t route the remote controller wiring and transmission wiring together with other electrical wiring Keep the remote c...

Page 13: ...21 System 2 Group control or 2 remote controllers control 1 indoor unit Power supply Single phase 220 240V 50 60Hz L N H Outdoor unit i I Note No need to input the indoor unit address during group con...

Page 14: ...ly one remote controller s setting needs to be changed Connecting method refer to the chapter of Electrical wiring work 3 Remove the electrical component box cover 12 4 Connect the remoter controller...

Page 15: ...oded number in accordance with the room conditions Factory setting of the 2nd coded number is 01 and it means mild filter contamination Air filter Mode 1st 2nd Setting cleaning signal number coded cod...

Page 16: ...Note...

Page 17: ...Note...

Page 18: ...Note...

Page 19: ...Note...

Page 20: ...DAIKINAIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurugram 122002 Haryana India 3P673644 1 C...

Page 21: ...UM LOCAL DE F CIL ACESSO PARA REFER NCIA FUTURA 3P673644 1C Ar condicionado com Sistema Inverter Idiomas dispon veis Ingl s Portugu s FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 FXKQ32AVM FXKQ40AVM FX...

Page 22: ......

Page 23: ...tala o da tubula o de drenagem 8 9 Instala es el tricas 9 9 1 Vis o geral 9 9 2 Especifica es dos fios el tricos padr o 9 9 3 Caracter sticas el tricas 10 10 Exemplo de instala es el tricas 10 10 1 Co...

Page 24: ...odo o trabalho de instala o verifique se h vazamento de g s refrigerante Caso o g s refrigerante vaze para o interior da sala e entre em contato com uma fonte de fogo como um aquecedor de ar fog o ou...

Page 25: ...podem causar interfer ncia eletromagn tica Nesse caso mantenha uma dist ncia adequada dos produtos Requisitos de Descarte A desmontagem da unidade o tratamento do fluido refrigerante do leo e de outra...

Page 26: ...ormalmente ou est com pe as queimadas As unidades interna e externa est o com as entrada do retorno de ar e sa da de ar obstru das Ar frio ou ar quente insuficiente O comprimento da tubula o de fluido...

Page 27: ...e interna Se o teto n o for forte o suficiente reforce o teto com anteced ncia Verifique o espa amento indicado na caixa de embalagem e se necess rio fa a o refor o adequado 3 Altura do forro A unidad...

Page 28: ...cheio de gua O nivelamento da unidade n o deve ultrapassar 0 5 graus no lado oposto bomba de drenagem Medidor de n vel Cuidado Caso a unidade esteja inclinada na dire o oposta ao fluxo da gua condens...

Page 29: ...da tubula o com material de isolamento Consulte a Figura 12 Ao realizar o isolamento prenda as partes de isolamento das juntas inclu das e tubula o do lado l quido e do lado gasoso Al m disso certifi...

Page 30: ...plique for a excessiva N o fazer isso resultar em vazamento de gua Para usar a tubula o de drenagem convergente conecte de acordo com a Figura 14 Selecione a tubula o de drenagem com um tamanho adequa...

Page 31: ...ve ser realizado por eletricistas qualificados O sistema inclui v rias unidades internas Nomeie cada unidade interna como Unidade A Unidade B etc e verifique se os n meros dos fios conectados aos bloc...

Page 32: ...pode resultar em mau funcionamento e falhas Para a instala o e fia o do controle remoto consulte o Manual de instala o do controle remoto inclu do com o mesmo Ao conectar a alimenta o do condicionador...

Page 33: ...de fuga de terra monte o disjuntor de linha ou o interruptor de carga com fus vel Se for necess rio instalar um disjuntor de fuga de terra monte um disjuntor de fuga de terra compat vel com os aparel...

Page 34: ...te o 12 Configura es de campo e execu o de teste Especifica es do fio rea seccional Comprimento Contato externo cabo de vinil embainhado ou cabo de dois n cleos 0 75 1 25mm2 M ximo 100 m A carga m nim...

Page 35: ...la abaixo e altere o segundo n mero codificado de acordo com as condi es do ambiente O ajuste de f brica do segundo n mero codificado 01 e significa contamina o leve do filtro Configura o Mode n mero...

Page 36: ...Nota...

Page 37: ...Nota...

Page 38: ...Nota...

Page 39: ...Nota...

Page 40: ...DAIKINAIRCONDITIONING INDIA PVT LTD 12 Andar Edif cio n 9 Torre A DLF Cyber City DLF Fase III Gurgaon 122 002 Haryana ndia 3P673644 1C...

Page 41: ...VRV Language Available English Portuguese FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 FXKQ32AVM FXKQ40AVM FXKQ50AVM FXKQ63AVM I 3P673655 1C I OPERATION MANUAL Model Ceiling Mounted Cassette Single Flo...

Page 42: ......

Page 43: ...t in injury or property damage or even serious injury under some circumstances After reading keep this manual in a convenient place so that you can refer to it whenever necessary If the equipment is t...

Page 44: ...ner in places with excessive oily smoke such as cooking rooms or in places with flammable gas corrosive gas or metal dust Using the air conditioner in such places may cause a fire or air conditioner f...

Page 45: ...ury or electric shocks To avoid injury do not touch the air inlet or aluminum fins of the air conditioner Do not place objects in direct proximity of the outdoor unit and do not let leaves and other d...

Page 46: ...n the product with organic solvents such as paint thinner Using the organic solvents may result in cracks electric shocks or fire hazards Ask the technical expertise to install the optional accessorie...

Page 47: ...leakage electric shocks and fire hazards The refrigerant within the air conditioner is safe Generally it is unlikely to leak However in case of a refrigerant leakage in the rooms it may generate harmf...

Page 48: ...d by refrigerant flow in the air conditioner During cooling or heating operation this sound can be heard while discharging the water gathered in the air conditioner through the drain pump The sound ca...

Page 49: ...flow rate and direction set properly Does the voltage comply with the instructions of the operation installation manual Is the air filter dirty Are the indoor and outdoor unit s suction inlet and air...

Page 50: ...Note...

Page 51: ...Note...

Page 52: ...DAIKINAIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase Ill Gurugram 122002 Haryana India 3P673655 1C...

Page 53: ...gu s FXKQ32AV16 FXKQ40AV16 FXKQ50AV16 FXKQ63AV16 FXKQ32AVM FXKQ40AVM FXKQ50AVM FXKQ63AVM MANUAL DE OPERA O Modelo Tipo Cassete de Montagem no Teto Fluxo nico 3P673655 1C Ar condicionado com Sistema In...

Page 54: ......

Page 55: ...ade ou mesmo ferimentos graves em algumas circunst ncias Ap s a leitura mantenha este manual em um local conveniente para que voc possa consult lo sempre que necess rio Se o equipamento for transferid...

Page 56: ...uma a oleosa excessiva como salas de cozimento ou em locais com g s inflam vel g s corrosivo ou poeira met lica Usar o condicionador de ar em lugares assim pode causar um inc ndio ou falhas no ar cond...

Page 57: ...em ferimentos ou choques el tricos Para evitar ferimentos n o toque na entrada de ar ou nas aletas de alum nio do ar condicionado N o coloque objetos na proximidade direta da unidade externa e n o dei...

Page 58: ...O uso dos solventes org nicos pode resultar em rachaduras choques el tricos ou riscos de inc ndio Solicite o auxilio t cnico para instalar os acess rios opcionais Utilize os acess rios especificados p...

Page 59: ...lhes da seguinte forma Nome do modelo N mero de s rie e data de instala o Mau funcionamento detalhes c digo de mau funcionamento exibido no controle remoto seu nome endere o e n mero de telefone Expir...

Page 60: ...contra o pelo frio O som causado pela opera o da aba de entrada de ar Durante a opera o de resfriamento o ar do ambiente se tornar frio e poder formar neblina O ar do ambiente resfriado pelo trocador...

Page 61: ...nstala o O filtro de ar est sujo As entradas de suc o e sa da de ar das unidades interna e externa est o bloqueadas Interrompa a opera o do condicionador de ar e desligue o disjuntor Limpe o filtro de...

Page 62: ...Nota...

Page 63: ...Nota...

Page 64: ...DAIKINAIRCONDITIONING INDIA PVT LTD 12 Andar Edif cio n 9 Torre A DLF Cyber City DLF Fase III Gurgaon 122 002 Haryana ndia 3P673655 1C...

Reviews: