12. Field settings and test run
(1 )Check if the electrical component box covers of the indoor
unit and outdoor unit are fastened securely.
(2)Field settings.
<According to the installation condition, make the field
settings using the remote controller after turning on the
power supply. Please perform in accordance with
"Field settings" of the manual included with the remote
controller.
>
• Make the settings by changing the "mode number",
"1 st coded number'' and "2nd coded number''.
• For setting procedure and operating method, refer to
the "Field settings" of the manual included with the
remote controller.
Values marked with
*
and () are the ones when
setting the indoor unit separately during group control.
• During remote control, perform input changeover of
"Forced OFF" and "ON/OFF" with the remote
controller. After start the field settings, select the
mode number "12" and set the 1st coded number and
the 2nd coded number to "1" and "01" respectively.
This is "Forced OFF"
• Set the 2nd coded number to "02" for "ON/OFF"
operation. (Factory setting is "Forced OFF").
After finishing field settings, deliver the "Field settings"
and operation manual to the customers for keeping
and future reference.
a .
Settings when installing the optional accessories
• For settings when installing the optional accessories,
refer to the installation manual included with the
optional accessories.
b.
Setting the air filter cleaning signal
• The remote controller is equipped with the aid filter
cleaning signal LCD, to display the time to clean the air
filter.
• Refer to the table below and change the 2nd coded
number in accordance with the room conditions.
(Factory setting of the 2nd coded number is "01" and it
means mild filter contamination.)
Air filter
Mode
1st
2nd
Setting
cleaning signal number coded coded
display
number number
Air filter contami-
About 2500
01
nation-light
hours
10(20)
0
Air filter contami-
About 1250
02
nation-heavy
hours
Perform test run based on the operation & installation
manual of the outdoor unit
• If something unusual occurs, the operation lamp of the
remote controller will flash.
Check the malfunction code displayed on the LCD to
determine the position of the fault.
For malfunction codes and correspondent
explanations, refer to the "Service precautions" of the
indoor unit.
If the following signals are indicated on the display,
then the wiring may be improper or the power supply is
not turned on. In this case, check again.
Display
Description
Displaying "Under
• Shot circuit of the forced-OFF terminals
centralized control
{T1, T2).
�"
Displaying "t:3"
• Test run has not been completed.
• The outdoor unit is not powered up.
• The outdoor unit is not connected to the
Displaying " U'-1 "
power wiring.
• The transmission wiring and the forced-
Displaying " UH "
OFF terminals (T1, T2) are incorrectly
connected.
• The transmission wiring is disconnected.
• The indoor unit is not powered up.
• The indoor unit is not connected to the
power wiring.
• The remote controller connecting &
No display
transmission wiring terminals (F1, F2)
and forced-OFF terminals (T1, T2) are
incorrectly connected.
• The remote controller transmission
wiring is disconnected.
If the test run is performed while the room is under
construction; do not operate the unit until construction is
complete.
Operating the unit in such conditions may result in damage
to the unit and surroundings.
13
Summary of Contents for FXKQ32AVM
Page 2: ......
Page 16: ...Note...
Page 17: ...Note...
Page 18: ...Note...
Page 19: ...Note...
Page 22: ......
Page 36: ...Nota...
Page 37: ...Nota...
Page 38: ...Nota...
Page 39: ...Nota...
Page 42: ......
Page 50: ...Note...
Page 51: ...Note...
Page 54: ......
Page 62: ...Nota...
Page 63: ...Nota...