Installation

11 - 1 Drainage instructions

Rig the drain pipe as shown below and take measures against 
condensation. Improperly rigged piping could lead to leaks and 
eventually wet furniture and belongings.

Install the drain pipes.

Keep piping as short as possible and slope it downwards so that 
the air does not remain trapped inside the pipe.

The diameter of the drain pipe should be larger than or equal to 
the diameter of the connecting pipe (Vinyl tube; pipe size: 25 mm; 
outer dimension: 32 mm).

Use the attached drain hose and clamp metal. Insert the drain hose 
into the drain socket, up to the white tape. Tighten the clamp until 
the screw head is less than 4 mm from the hose.

Wrap the attached sealing pad over the clamp and drain hose to 
insulate.

Insulate the drain hose inside the building.

Insulate the clamp and drain hose with the attached large sealing 
pad. If the drain hose cannot be sufficiently set on a slope, execute 
the drain raising piping. Secure a downward gradient of 1/100 or 
more for the drain pipe. To accomplish this, mount supporting 
brackets at an interval of 1 - 1.5 m.

Precautions when installing drain-up piping.

Make sure the drain-up piping is maximum 330 mm high. Install 
the drain-up piping horizontally, and make sure it is not further 
than 300 mm from the base of the drain socket.

Use the following outline if installing concentrated drain piping. If 
converging multiple drain pipes, install according to the procedure 
shown on the right.

Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

CAUTION

1

Installing the unit at an angle opposite to the drain piping might 
cause leaks.

Clamp metal

Clamp metal

(attached)

Large sealing pad
(attached)

Tape (white)

< 4 mm

Drain hose

Ceiling slab

Clamp metal (attached)

Drain hose (attached)

Riser

< 300

< 500

170

1-1.5 m

Drain-up piping

Support bracket

Adjustable (< 330)

> 100 mm

T-joint converging drain pipes

Summary of Contents for FXKQ-MAVE Series

Page 1: ...Ceiling Mounted Corner Cassette FXKQ MAVE air conditioning systems technical data...

Page 2: ...Ceiling Mounted Corner Cassette FXKQ MAVE technical data air conditioning systems...

Page 3: ...settings 4 3 Options 4 4 Control systems 5 5 Capacity tables 6 Cooling capacity tables 6 Heating capacity tables 7 6 Dimensional drawing centre of gravity 8 Dimensional drawing 8 Centre of gravity 9...

Page 4: ...1 3D12H1AN1V1 3D12H1AP1V1 4D12H1AJ1V1 Output high W 15 15 20 45 Drive Direct drive Refrigerant Name R 410A Cooling Sound Pressure High dBA 38 0 38 0 40 0 42 0 Low dBA 33 0 33 0 34 0 37 0 Piping connec...

Page 5: ...al systems where voltage supplied to unit terminals is not below or above listed range limits Maximum allowable voltage range variation between phases is 2 MCA MFA MCA 1 25 x FLA MFA is smaller than o...

Page 6: ...IN PUMP THERMAL FUSE C 145 FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA DECORATION PANEL BYK45FJW1 BYK71FJW1 PANEL SPACER KPBJ52F56W KPBJ52F80W LONG LIFE REPLACEMENT FILTER KAFJ521F56 KAFJ521F80 AIR DISCHARGE...

Page 7: ...Q63MA CENTRALISED REMOTE CONTROL DCS302C51 UNIFIED ON OFF CONTROL DCS301B51 SCHEDULE TIMER DST301B51 FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA WIRING ADAPTER KRP1B61 WIRING ADAPTER FOR ELECTRICAL APPENDICES...

Page 8: ...31 0 2 4 2 2 2 9 2 5 3 4 2 6 3 6 2 7 3 8 2 9 4 0 2 7 4 1 2 6 33 0 2 4 2 2 2 9 2 5 3 4 2 6 3 6 2 7 3 8 2 9 3 9 2 7 4 0 2 6 35 0 2 4 2 2 2 9 2 5 3 4 2 6 3 6 2 7 3 8 2 9 3 9 2 7 4 0 2 6 37 0 2 4 2 2 2 9...

Page 9: ...7 3 7 3 5 3 0 2 2 3 9 3 9 3 9 3 9 3 7 3 5 5 0 4 1 4 1 4 1 4 0 3 9 3 7 3 5 7 0 6 0 4 2 4 2 4 0 3 9 3 7 3 5 9 0 7 9 4 3 4 3 4 0 3 9 3 7 3 5 11 0 9 8 4 5 4 3 4 0 3 9 3 7 3 5 13 0 11 8 4 5 4 3 4 0 3 9 3...

Page 10: ...nection VP25 O D 32 4 Wire intake 5 Interunit wiring connection 6 Grounding terminal Inside switch box M4 7 Discharge 8 Air suction grille 9 Long life filter 10 Suspension bolt FXKQ63MA 3D038841 20 mm...

Page 11: ...V Systems Indoor Units 9 Indoor Units CEILING MOUNTED CORNER CASSETTE FXKQ MAVE 6 Dimensional drawing centre of gravity 6 2 Centre of gravity FXKQ MA 4D037079A Model A FXKQ25 32 40MA 1 110 FXKQ63MA 1...

Page 12: ...Systems Indoor Units 10 7 Piping diagram FXKQ MA 4D034245A Heat exchanger Fan Filter Filter Electronic expansion valve Liquid pipe connection port Gas pipe connection port Piping connection diameters...

Page 13: ...onnection from X2A to X3A 4 Use copper conductors only Indoor Unit R1T Thermistor Air A1P Printed circuit board R2T R3T Thermistor Coil A2P Terminal board S1Q Limit switch Swing flap C1R Capacitor M1F...

Page 14: ...stic pressure 0dB 0 0002 bar 2 Operation noise differs with operation and ambient conditions 3 Measuring place anechoic chamber Model Sound pressure level 220 V Sound pressure level 240 V Sound power...

Page 15: ...ssure level dB 0dB 0 0002 m bar Approximate threshold hearing for continuous noise FXKQ40MA 4D037072 Octave band center frequency Hz Octave band sound pressure level dB 0dB 0 0002 bar Approximate thre...

Page 16: ...ting temperature distribution Lower air blow NOTES 1 The corner type is applicable on a high ceiling The standard set up height is 3 m Shown here is the measurement distribution at the ceiling height...

Page 17: ...clamp and drain hose with the attached large sealing pad If the drain hose cannot be sufficiently set on a slope execute the drain raising piping Secure a downward gradient of 1 100 or more for the dr...

Page 18: ...operation button on the remote control The unit will engage the test operation mode Press the operation mode selector button until selection FAN OPERATION Then press the ON OFF button The indoor unit...

Page 19: ...MOUNTED CORNER CASSETTE FXKQ MAVE 11 Installation 11 2 Suspension bolt pitch position FXKQ MA Decoration panel Ceiling opening port Indoor unit Suspension bolt 4 pc Model A B C D FXKQ25 32 40MA 1 110...

Page 20: ...CASSETTE FXKQ MAVE VRV Systems Indoor Units 18 11 Installation 11 3 Service space FXKQ MA 200 or more 200 or more 20 or more 1 500 or more Suction side Discharge side 220 or more 1 000 or more NOTES...

Page 21: ...ithout prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this publicat...

Reviews: