FXHQ-MVJU
EDUS39-600A-F5
8.
Capacity Tables
8.1
Cooling Capacity at Te: 43°F (6°C)
Model
Indoor air temp. °FWB (°CWB) (Te: 43°F (6°C))
61 (16.1)
64 (17.8)
67 (19.4)
70 (21.1)
72 (22.2)
75 (23.9)
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
FXHQ12MVJU
9.5
8.5
10.7
8.8
12.0
9.4
12.7
9.4
12.9
9.3
13.1
8.9
FXHQ24MVJU
18.9
15.3
21.5
16.6
24.0
17.1
25.5
17.4
25.8
17.1
26.3
16.2
FXHQ36MVJU
28.4
21.8
32.2
23.9
36.0
25.1
38.2
25.3
38.7
24.6
39.4
23.7
TC: Total capacity: MBH
SHC: Sensible heat capacity: MBH
Note:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies
the required heat load.
2.
shows rated condition.
8.2
Heating Capacity
Model
Indoor air temp. °FDB (°CDB) (Tc: 115°F (46°C))
62 (16.7)
65 (18.3)
68 (20.0)
70 (21.1)
72 (22.2)
75 (23.9)
TC
TC
TC
TC
TC
TC
MBH
MBH
MBH
MBH
MBH
MBH
FXHQ12MVJU
14.9
14.7
14.0
13.5
13.0
12.3
FXHQ24MVJU
29.7
29.5
28.0
27.0
26.0
24.5
FXHQ36MVJU
44.6
44.2
42.0
40.0
39.0
36.8
TC: Total capacity: MBH
Note:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies
the required heat load.
2.
shows rated condition.
8.3 Correction Factor for Cooling Capacity at Te: 48°F (9°C)
Refer to the correction factor table below when a mini-split indoor unit
is connected to a
VRV
Heat Pump system using a Branch Port box.
Model
Indoor air temp. °FWB (°CWB) (Te: 48°F (9°C))
57 (13.9)
61 (16.1)
64 (17.8)
67 (19.4)
70 (21.1)
72 (22.2)
75 (23.9)
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
FXHQ12MVJU
0.71
1.09
0.69
1.18
0.74
1.13
0.78
1.09
0.81
1.07
0.82
1.05
0.84
1.04
FXHQ24MVJU
0.69
1.12
0.70
1.17
0.74
1.13
0.78
1.09
0.81
1.07
0.82
1.06
0.84
1.06
FXHQ36MVJU
0.69
1.12
0.70
1.17
0.75
1.12
0.79
1.08
0.82
1.06
0.83
1.06
0.85
1.06
TC: Total capacity
SHF: Sensible heat factor
CA14A307C
Summary of Contents for FXHQ-MVJU
Page 1: ...Ceiling Suspended Type FXHQ MVJU EDUS39 600A F5 202103 Engineering Data 60 Hz...
Page 2: ......
Page 7: ...5 FXHQ MVJU EDUS39 600A F5 3 Dimensions FXHQ12MVJU 3D049330A Unit in...
Page 8: ...6 FXHQ MVJU EDUS39 600A F5 FXHQ24MVJU 3D049331A Unit in...
Page 9: ...7 FXHQ MVJU EDUS39 600A F5 FXHQ36MVJU 3D049332B Unit in...
Page 25: ......
Page 26: ......
Page 27: ......