6. Electric Characteristics
FXHQ12-36MVJU
Model
Power supply
IFM
Input (W)
SCCR
Hz
Volts
Voltage range
MCA
MOP
KW
FLA
Cooling
Heating
FXHQ12MVJU
60
208/230 V
Max. 253 V
Min. 187 V
0.8
15
0.062
0.6
90
90
SCCR kA rms,
Symmetrical
@600 V MAX: 5
FXHQ24MVJU
1.0
15
0.130
0.8
127
127
FXHQ36MVJU
1.4
15
0.130
1.1
161
161
Symbol:
MCA: Minimum Circuit Ampacity (A)
MOP: Maximum Overcurrent Protective Device (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Ampacity (A)
IFM: Indoor Fan Motor
SCCR: Short-Circuit Current Rating
Note:
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MOP
MCA = 1.25 × FLA
MOP ≤ 4 × FLA
(Next lower standard fuse raring. Minimum 15 A)
4. Select wire size based on the value of MCA.
5. Either a fuse or a circuit breaker is acceptable.
C: 4D049333B