![background image](http://html1.mh-extra.com/html/daikin/fxhq-a/fxhq-a_technical-data-manual_2459726012.webp)
• Indoor Unit • Ceiling suspended unit • FXHQ-A
1
6
• VRV Systems • Indoor Unit
10
6
Capacity tables
6 - 3 Capacity Correction Factor
Indoor air
temperature
14.0 °CWB
16.0 °CWB
18.0 °CWB
19.0 °CWB
20.0 °CWB
22.0 °CWB
24.0 °CWB
20.0 °CDB
23.0 °CDB
26.0 °CDB
27.0 °CDB
28.0 °CDB
30.0 °CDB
32.0 °CDB
FXHQ32
TC
0.707
0.692
0.745
0.768
0.788
0.819
0.844
SHF
1.098
1.181
1.127
1.102
1.082
1.055
1.042
FXHQ63
TC
0.695
0.702
0.749
0.772
0.791
0.821
0.844
SHF
1.120
1.169
1.122
1.098
1.079
1.058
1.060
FXHQ100
TC
0.690
0.697
0.757
0.779
0.798
0.829
0.856
SHF
1.123
1.169
1.114
1.091
1.073
1.055
1.057
FXHQ-A
3D079901
Capacity correction factor Te = 9°C