• Indoor Unit • Ceiling suspended unit • FXHQ-A
1
2
• VRV Systems • Indoor Unit
4
2
Specifications
Standard Accessories : Declaration of conformity;
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;
Notes
(1) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(2) Maximum allowable voltage range variation between phases is 2%.
(3) MCA/MFA: MCA = 1.25 x FLA
(4) MFA
≤
4 x FLA
(5) Next lower standard fuse rating minimum 16A
(6) Select wire size based on the value of MCA
(7) Instead of a fuse, use a circuit breaker
2-2 Electrical Specifications
FXHQ32A
FXHQ63A
FXHQ100A
Power supply
Name
VE
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
10
Max.
%
10
Current - 50Hz
Minimum circuit amps (MCA)
A
0.8
1.7
Maximum fuse amps (MFA)
A
16
Full load amps
(FLA)
Fan motor
A
0.6
1.3