Observe the notes mentioned below when wiring to the terminal block for wiring the units.
CAUTION
•
When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the terminal box lid to stick up, then close the cover firmly.
•
When attaching the terminal box lid, make sure you do not pinch any wires.
•
After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in, they
could cause short circuits in the terminal box.)
•
Outside the machine, separate the weak wiring (remote controller cord) and strong wiring (interunit,
ground, and other power wiring) at least 50 mm so that they do not pass through the same place together.
Proximity may cause electrical interference, malfunctions, and breakage.
Fig. 27
Inter-unit wiring
Ground wire
Sheaths
Remote controller cord
(weak electric)
10 – 15mm
70 – 90mm
Clamp (4)
Approximately
7mm
Peel back
the sheath
on the power
line and twist. Length of
sheath to
peel back
Cut off any excess
material after tightening.
Wiring
through-holes
Wiring
through-holes
Remote
controller
wiring terminal
block
Terminal box lid
(P1
•
P2)
Electrical Wiring
Diagram Nameplate
(Inside of terminal box lid)
Remote
controller
wiring
Inter-unit wiring
terminal block
(3P)
Remote
controller
Forced off
Transmission
wiring
Transmission
wiring
P1 P2 F1 F2 T1 T2
Inter-unit
wiring sheath
Clamping position
Secure the ground wire
and inter-unit wiring with
both edges aligned.
Ground wire
Ground
wire
Clamp (4)
Cut off any
excess
material after
tightening the
inter-unit wiring
and ground
wire together.
Ground terminal
(Length of sheath to peel bac
k)
10~15mm
80~100mm
S R
<<Inter-unit wiring (strong electric) / ground wire>>
01_EN_3P161684-4E.fm Page 18 Monday, August 16, 2010 7:11 PM