Control Devices
EDUS391000-C
22
Controls
2.4.4
Description of Functions
Individual Screen, all Screen, Zone Screen
This controller can perform operations in the individual screen, all screen, or zone screen.
Individual screen
The individual screen is used when performing group operations.
All screen
The all screen is used when performing operations for all units at once.
Zone screen
The zone screen is used when performing zone operations.
Basic Functions
Zone Control Functions
Cool/Heat Changeover and Eligibility Setting
Note:
Refer to the next page for the selection of cool/heat mode (eligibility for cool/heat changeover).
Descriptions of outline
Individual/Zone control
Up to 64 groups (Max. 128 units and max. 16 units per group) of indoor units and HRV units can be controlled by
individually or by zone.
Unified ON/OFF
ON/OFF can be set for each zone, and can be controlled simultaneously for entire system by push button or by contact
signal from outside.
Malfunction code display
The status of each group is always displayed, such as ON/OFF, error, etc. If the error occurs, it displays the contents of
error by malfunction code through the self-diagnosis function.
Connection of unification adaptor for computerized
control
By connecting the unification adaptor for computerized control (option), it can be linked with the central monitoring panel
and etc. by contact signal, which enables you to operate ON/OFF simultaneously or monitor the operating status.
Remote control acceptance/rejection
It is possible to restrict the function of local remote controller.
(Only ON operation rejection, or ON/OFF operation rejection)
2 central controllers
By connecting two central remote controllers, the same air-conditioner can be controlled from 2 locations (By tenant or
administration office.)
Descriptions of outline
Zone control
The zone function is a function to control one or more group of air-conditioner, and the operation setting such as ON/OFF
etc. can be made by zone.
Up to 64 zones
Up to 64 zones (64 groups for each zone) can be set. However, the group setting spreading over the plural zone cannot
be set.
Zone register
When the power is supplied first time, each group is registered in each respective zone. If you can simply register the
several groups in the same zone by switch, so that you can have simultaneous operation of the units in that zone
immediately. (The operation of temperature setting and etc. is also controlled by zone simultaneously.)
Zone setting
By adding the zone setting function (Zone “0”) from the central remote controller, you can set the same setting for all the
zone registered by single operation.
ON/OFF control of zone
For example, if there are three groups in one room and if you register these three groups as one zone, you can operate
these three groups simultaneously by single operation (ON/OFF, temperature setting etc.).
You still can operate each group individually by local remote controller.
Maintaining zone setting
Even if the power is turned off, the zone configurations set are maintained semi-permanently. (saved in non-volatile memory)
Cool/Heat changeover by zone
The cool/heat changeover can be made by zone. However, it is required to have a master group for Cool/Heat changeover
in that zone.
Batch operation
The same setup is possible at one operation to all the groups registered on the "All" screen.
No local remote controller
Even if there is no local remote controller, you can still perform the same operation. There is no problem even if no remote
controller is connected. (However, in this case, each one air-conditioner consists of one group.)
Combination with other controllers
You can also combine with a unified ON/OFF controller and a schedule timer.
(Refer to the system configuration for details.)
Connection to central monitoring panel
You can also combine with an Interface for use in BAC net
and a data station in order to connect to the central monitoring
panel. A parallel interface can also be connected.
Descriptions of outline
Possible control
The operation mode of the outdoor unit can be changed by the local remote controller or by the central remote controller.
(For test operation, change setting of cool/heat selector switch of the outdoor unit.)
Remote controller acceptance/rejection
You can set the remote controller acceptance/rejection on the central remote controller by the local remote controller.
"NOT AVAILABLE" DISPLAY
(NO FUNCTION DISPLAY)
If a function is not available in the indoor unit even if the button is pressed, "NOT AVAILABLE" is may be displayed for a
few seconds.
Summary of Contents for FXFQ-PVJU
Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls...
Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features...
Page 64: ...EDUS391000 C Control Devices Controls 63...
Page 65: ...Control Devices EDUS391000 C 64 Controls...
Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A...
Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B...
Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360...
Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360...
Page 76: ...EDUS391000 C Adapter Controls 75 1P013360...
Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A...
Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A...
Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow...
Page 82: ...EDUS391000 C Adapter Controls 81...
Page 83: ...Adapter EDUS391000 C 82 Controls...
Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221...