EDUS391000-C
Control Devices
Controls
37
6. Refreshed operation
Refreshed operation is the function to transmit setting of "Temperature control", "Temperature setting" automatically
from DCS302C71.
"Refreshed operation" is "ON" when shipped from the factory.
Factory Setting
It depends on the setting of outdoor systems that an indoor unit setting is "Temperature control " or " Temperature
setting".
In case of Refreshed operation is "ON"
When setting is changed by DCS302C71, it operates by this setting from the next operation.
If it sets up with 79°F in cooling by DCS302C71, next operation will also be operated at 79°F in cooling. (Even if it has
changed into heating operation, fan only operation with wired or wireless remote control, it operates at 79°F in
cooling.)
When zone registration is carried out by Central Remote Controller.
It operates from next time with the value set up in the zone.
When a zone 1 is set up with 68°F of heating. (Refer to the system of the following figure.)
When controlled by Central Remote Controller, 3 indoor units registered into the zone 1 are operated by 68°F of
heating. Because priority is given to zone setting, even if it sets up 2-02 with 77°F of heating on an individual screen
from Central Remote Controller, 2-02 is operated at 68°F.
When there are two or more indoor units in a zone.
Because an operating mode depends on the outdoor unit, the operating mode of each indoor unit does not become
the same setting.
When the outdoor unit system 1 is cooling, the outdoor unit system 2 is heating and it operates by the system of the
following figure. Setting of a zone 2 is operated in heating mode, because 2-03, 2-04, and 2-05 do not have a cooling/
heating selection right as for 79°F of cooling, but temperature setting becomes 79°F.
When you unify the operating mode of an indoor unit in the same zone, please set up a zone in the indoor unit of the
same outdoor unit system.
Outdoor Units Systems
Indoor Units Mode
Cooling Mode
Cooling 82°F
Heating Mode
Heating 72°F
Fan Mode
Fan Operation
Outdoor Unit
System 1
Outdoor Unit
System 2
Cooling/Heating Selection Right
1-00
1-01
1-02
1-03
1-04
1-05
Zone 2
2-00
2-01
2-02
Zone 1
2-03
2-04
2-05
Central Remote
Controller
Summary of Contents for FXFQ-PVJU
Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls...
Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features...
Page 64: ...EDUS391000 C Control Devices Controls 63...
Page 65: ...Control Devices EDUS391000 C 64 Controls...
Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A...
Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B...
Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360...
Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360...
Page 76: ...EDUS391000 C Adapter Controls 75 1P013360...
Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A...
Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A...
Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow...
Page 82: ...EDUS391000 C Adapter Controls 81...
Page 83: ...Adapter EDUS391000 C 82 Controls...
Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221...