background image

EDUS391000-C

Control Devices

Controls

37

6. Refreshed operation

Refreshed operation is the function to transmit setting of "Temperature control", "Temperature setting" automatically 
from DCS302C71.
"Refreshed operation" is "ON" when shipped from the factory.
Factory Setting
It depends on the setting of outdoor systems that an indoor unit setting is "Temperature control " or " Temperature 
setting".

In case of Refreshed operation is "ON"
When setting is changed by DCS302C71, it operates by this setting from the next operation.
If it sets up with 79°F in cooling by DCS302C71, next operation will also be operated at 79°F in cooling. (Even if it has 
changed into heating operation, fan only operation with wired or wireless remote control, it operates at 79°F in 
cooling.)
When zone registration is carried out by Central Remote Controller. 
It operates from next time with the value set up in the zone.
When a zone 1 is set up with 68°F of heating. (Refer to the system of the following figure.)
When controlled by Central Remote Controller, 3 indoor units registered into the zone 1 are operated by 68°F of 
heating. Because priority is given to zone setting, even if it sets up 2-02 with 77°F of heating on an individual screen 
from Central Remote Controller, 2-02 is operated at 68°F.
When there are two or more indoor units in a zone.
Because an operating mode depends on the outdoor unit, the operating mode of each indoor unit does not become 
the same setting.
When the outdoor unit system 1 is cooling, the outdoor unit system 2 is heating and it operates by the system of the 
following figure. Setting of a zone 2 is operated in heating mode, because 2-03, 2-04, and 2-05 do not have a cooling/
heating selection right as for 79°F of cooling, but temperature setting becomes 79°F.
When you unify the operating mode of an indoor unit in the same zone, please set up a zone in the indoor unit of the 
same outdoor unit system.

Outdoor Units Systems

Indoor Units Mode

Cooling Mode

Cooling 82°F

Heating Mode

Heating 72°F

Fan Mode

Fan Operation

Outdoor Unit

System 1

Outdoor Unit

System 2

Cooling/Heating Selection Right

1-00

1-01

1-02

1-03

1-04

1-05

Zone 2

2-00

2-01

2-02

Zone 1

2-03

2-04

2-05

Central Remote

Controller

Summary of Contents for FXFQ-PVJU

Page 1: ...EDUS 391000 C AMERICAS AMERICAS Controls...

Page 2: ...Controller 17 2 5 DCS301C71 Unified ON OFF Controller 40 2 6 DST301BA61 Schedule Timer 48 2 7 DCS601C71 intelligent Touch Controller 55 3 Adapter 67 3 1 KRCS01 1B 4B Remote Sensor 67 3 2 DTA104A53 61...

Page 3: ...4 KRP1C74 KRP1C74 KRP1C74 KRC1C75 11 Group Control Adapter KRP4A73 KRP4A74 KRP4A71 KRP4A71 KRP4A72 KRP4A71 KRP4A71 KRP4A74 C 3D043022F C 3D068551 C 3D068222A C 3TW30729 6 Part name Model No Function i...

Page 4: ...imple Operation Simple operation used with arrow keys and menu driven method Multilingual Display Available for selection of 3 languages Other Features Wide variety of functions to meet customer needs...

Page 5: ...ture of button allocation for each function the number of buttons has been decreased from 15 to 9 Can intuitively handle frequently performed basic operations 1 Large text display 2 Large buttons 3 Ba...

Page 6: ...peration with arrow keys and menu driven system Available for simple operation with arrow keys and menu driven system Press Menu OK button to change the screen and then the main menu appears Select th...

Page 7: ...Controls Available for simple operation with arrow keys and menu driven system Guide on display The item you wish to set can be changed with up or down button The display gives an explanation of each...

Page 8: ...91000 C Control Devices Controls 7 Multilingual Display Available for display in 3 different languages Always available for switching display by selecting from main menu 3 languages English French Spa...

Page 9: ...Control Devices EDUS391000 C 8 Controls Other Features...

Page 10: ...oor unit with 2 remote controllers the remote controller operated first turns the backlight on When controlling 2 remote controllers the following functions cannot be set with the sub remote controlle...

Page 11: ...ouch Controller DCS601C71 intelligent Manager DAM602A71 72 BACnet Gateway DMS502B71 Central remote controller DCS302C71 Unified ON OFF controller DCS301C71 Schedule timer DST301BA61 Residential centra...

Page 12: ...Models Applicable Models 3D065275 Unit in IF THE HOLE SIZE IS TOO LARGE OR THE LOCATION NOT PROPER THE WIRE MAY COME OUT OF THE HOLE IN THE REMOTE CONTROLLER Applicable Indoor unit VRV All models tha...

Page 13: ...ontrols 2 2 BRC4C 7C 7E Wireless Remote Controller Receiver BRC7C812 BRC4C82 C 3D005912D 2 7 16 11 16 6 3 16 Unit in C 3D007898B 2 7 16 11 16 2 3 4 2 3 16 3 8 11 16 1 3 8 1 15 16 3 9 16 1 32 6 3 16 4...

Page 14: ...EDUS391000 C Control Devices Controls 13 BRC7E83 BRC7E818 3D049336 Unit in C 3D034905B 2 7 16 11 16 6 3 16 Unit in...

Page 15: ...eration DISPLAY OPERATION MODE This display shows current OPERATION MODE is not available with outdoor units specially designed for cooling only is reserved only for outdoor units capable of heat reco...

Page 16: ...the mounting surface Be careful not to distort the shape of the lower part of remote controller by over tightening the mounting screws For the electric parts box to be procured in the field use option...

Page 17: ...ly touch the PC board with your hand NOTES 2If controlling with one remote controller be sure to set it to MAIN 2Set the remote controller before turning power supply on is displayed for about one min...

Page 18: ...e within 1 system Up to 4 units in case of the double central control mode Executes zone control for up to 64 zones and is designed for operation efficiency Error contents are displayed in code mainte...

Page 19: ...unit The number of indoor units in one group is up to 16 units Zone control The zone means the indoor units connected by the same control wiring for central remote controller connected to terminal F1...

Page 20: ...ON OFF controllers can be connected 8 controllers 2 locations One schedule timer can be connected Notes 1 Electrical power should be supplied to each central remote controller Single phase 100 240V 2...

Page 21: ...peration on the local side cannot be carried out during forced OFF input No voltage normal open contact Micro current contact capable of handling 16VDC and approx 10mA Max 492 ft cable length Power su...

Page 22: ...ch have stopped due to an error DISPLAY TIME TO CLEAN AIR CLEANER ELEMENT TIME TO CLEAN AIR FILTER Displayed to notify the user it is time to clean the air filter or air cleaner element of the group d...

Page 23: ...up is registered in each respective zone If you can simply register the several groups in the same zone by switch so that you can have simultaneous operation of the units in that zone immediately The...

Page 24: ...he selection eligibility for cool heat 1 Preparation When turning on the power first time CHANGEOVER UNDER CONTROL sign blinks When you set Branch Selector unit Heat Recovery series Indoor unit Contin...

Page 25: ...ing temperature setting 75 F However the display of zone setting of the master remote controller remains at heating temperature setting at 80 F Cautions Operation code cannot be set by the sub central...

Page 26: ...ed using the ZONE NUMBER button Keeping the button pressed down will move it rapidly 3 to the group you wish to register using the arrow keys Keeping the button pressed down will move it rapidly 4 Pre...

Page 27: ...ill be displayed for a period of another approximately two seconds Monitor in zone unit Operating and monitoring the system even in group or zone unit has become enabled from the DCS302C71 Monitoring...

Page 28: ...DJUSTMENT button This sets fixed or swing for the fan direction Press the FAN STRENGTH ADJUSTMENT button Pressing this button scrolls through and Depending on the indoor unit only and may be available...

Page 29: ...ne registered units Call up the zones which you wish to set in the zone screen and set the timer numbers Since the timer number will be set to after press priority the timer number in the last screen...

Page 30: ...he sub branches from the branch line 3 Star method Up to 16 branches is possible Never diverge the sub branches from the branch line Specifications of Transmission Wiring Be sure to use either 2 core...

Page 31: ...econds The remote controller will enter the FIELD SET MODE 3 Select the MODE No 00 with the button 4 Use the button to select the group No for each group Group numbers increase in the order of 1 00 1...

Page 32: ...al remote controller Except when connected to the central monitoring panel Description of Control Mode The following 5 operation control modes and 20 modes combined with temperature and operation mode...

Page 33: ...ample Rejection Acceptance 0 Rejection 10 Acceptance Example Acceptance example 1 example Rejection 11 Remote controller off only accepted Acceptance Rejection Acceptance 2 Rejection 12 Acceptance Acc...

Page 34: ...ual priority Last command priority Code No 6 7 16 17 OFF ON ON OFF OFF OFF OFF Off OFF ON ON ON ON On Off On Acceptance Rejection ON DCS302C71 Command Schedule Timer Operation by Central Remote Contro...

Page 35: ...It switches to the cord of Remote Controller Permission Timer Remote Controller Permission Timer Last command priority Acceptance Rejection On Off OFF ON ON ON OFF OFF Time OFF Time ON Time ON OFF ON...

Page 36: ...e setting switch SS3 This setting is required when up to 128 groups of indoor units are controlled by two central remote controller 3 Main Sub changeover switch Setting is required for central control...

Page 37: ...ore to set the system to FIELD SETTING mode 2 Use the TEMPERATURE ADJUSTMENT button to select a desired Mode No Press to increase the Mode No Press to decrease the Mode No 3 Press the CONTROL MODE COD...

Page 38: ...tral Remote Controller 3 indoor units registered into the zone 1 are operated by 68 F of heating Because priority is given to zone setting even if it sets up 2 02 with 77 F of heating on an individual...

Page 39: ...riction items from sub central remote controller while in double central control function While in double central control function no settings of zone interlock and operation code can be made from the...

Page 40: ...16 NOTE Suitable length of the electric wire is about 6 1 4 from electric parts box If it is difficult to contain a long wiring strip the sheathed part of the wiring screwdriver 2 locations PC board...

Page 41: ...ON OFF Controller cannot be used in conjunction with the optional Group Control Adapter For a maximum of 16 groups of indoor units max 128 units unified operation stop or individual operation stop ca...

Page 42: ...grounded in compliance with the applicable local and national codes Fit the power supply wiring with a fuse and a switch After wiring work check power to the equipment shuts OFF when switch is shut O...

Page 43: ...Type Wiring Can be branched up to 16 branches Example of 3 branches 3 Star Type Wiring Can be branched up to 16 branches Example of 3 branches Note 1 No branching is allowed after branching 2 Use a re...

Page 44: ...al strip If connected by mistake it may damage or burn electrical parts of optional controllers for centralized control and indoor unit It may result in serious danger Be sure to check wirings before...

Page 45: ...set When using 1 unified ON OFF controller do not disconnect the connector for setting master controller Use the unit with the connector in the state in which it was delivered When using multiple uni...

Page 46: ...rent locations In this kind of set up it is necessary to set the MAIN SUB changeover switch One of the two unified ON OFF controllers 1 2 is set to MAIN while the other is set to SUB 4 Setting of the...

Page 47: ...er OFF For normal operation set the switch to the normal side Control Mode Individual Centralized Timer Operation Possible by Remote Controller ON OFF Control Impossible by Remote Controller Content O...

Page 48: ...plified remote controller see the installation table For setting group No of HRV and wiring adaptor for other air conditioners etc refer to the instruction manual attached NOTICE Enter the group No an...

Page 49: ...wiring for control AWG 18 or 16 sheathed vinyl cord or cable 2 wire Max 3280 ft Total Max 6560 ft Transmission Wiring Connection Example 1 series wiring 2 bus wiring and 3 star wiring are the same as...

Page 50: ...EDUS391000 C Control Devices Controls 49 2 6 2 Names and Functions DST301BA61 3P124623 5C 1 2 3 6 4 9 7 8 10 11 5 DST301BA61 Fig 1 17 15 14 12 13 18 19 20 16 DST301BA61 Fig 2...

Page 51: ...Displays the present day of the week and time 10 DISPLAY PROGRAMMED TIME OF SYSTEM START Displays the time programmed to start 11 DISPLAY PROGRAMMED TIME OF SYSTEM OFF Displays the time programmed to...

Page 52: ...remote controller Insert a minus screwdriver 2 locations into the recess between the upper part and the lower part of the remote controller and twist the screwdriver lightly The PC board is attached w...

Page 53: ...e the factory setting 2 Control mode selector SS2 Set for individual use only By changing the switch setting mode of individual and centralized operation is available Note When used with other optiona...

Page 54: ...rammed operation of the indoor units set the address for central control by local remote controller 3 Transmission Wiring In case of individual use of schedule timer Connect terminals of the schedule...

Page 55: ...Check the contents of the display for the problem indicators and contact your DAIKIN dealer to report the source of the problem F1 F2 D1 D2 Wiring Sheathed wire 2 wire Sheathed wire 2 wire Gauge AWG...

Page 56: ...ed Setting Operations Up to 128 groups can be controlled with the intelligent Touch Controller More than one group can be consolidated into a zone which can be registered to allow the following settin...

Page 57: ...toring of air conditioner with personal computer by the Controller with the optional DCS004A71 A group of indoor units include Zone control with the intelligent Touch Controller Zone control which all...

Page 58: ...ontact the vendor you purchased the product from Central monitoring panel Collective start stop and error monitoring with contact Monitoring from PC is possible by Web E mail functions Optional intell...

Page 59: ...t the dealer you purchased the product from Front and Side View NOTE Terminals on the Back of intelligent Touch Controller LINE COM L0 Dil Pi3 COM Pi2 Pi1 F2 F1 24 VAC COM 24 VAC PHONE RS 232C LAN Mod...

Page 60: ...System Condition Displayed Domain Domain displaying system condition Compulsory Stop etc DisplayforCollectiveMonitoringofAir ConditionersConnectedtointelligentTouchController When operation is normal...

Page 61: ...nd any air conditioner is in operation Red Normal When operation is normal and all air conditioners are in stoppage Green Normal When there is any air conditioner generating an error Yellow Abnormal W...

Page 62: ...ge Green Normal When there is any air conditioner generating an error Yellow Abnormal When there is any air conditioner with communication error Blue Abnormal Change in color of Start Stop is possible...

Page 63: ...Control Devices EDUS391000 C 62 Controls 2 7 7 Electric Wiring Connection ground wire to ground terminal...

Page 64: ...EDUS391000 C Control Devices Controls 63...

Page 65: ...Control Devices EDUS391000 C 64 Controls...

Page 66: ...EDUS391000 C Control Devices Controls 65 1P167242A...

Page 67: ...s Privileges Given to Each Login Name There are two categories of login users General User who can perform basic operations via the web interface and Administrator who can setup the system and change...

Page 68: ...DUS391000 C Adapter Controls 67 3 Adapter 3 1 KRCS01 1B 4B Remote Sensor 39ft 4 1 2in 4 3 4 C 3K019189B FXMQ PVJU AHU type FXTQ PAVJU part 2 locations and remove the cover pushing up the nail to where...

Page 69: ...B 1 1 4 1 1 4 2 3 4 2 3 4 1 8 M4 7 8 1 5 8 4 3 4 1 8 M4 1 5 8 Break open the knockout hole in the sensor with wire cutters Pass the extension wires through the hold and fasten the wires to the termina...

Page 70: ...EDUS391000 C Adapter Controls 69 C 3K019189B...

Page 71: ...pter EDUS391000 C 70 Controls 3 2 DTA104A53 61 62 External Control Adapter for Outdoor Unit Must be Installed on Indoor Units FXHQ KRP1C93 FXMQ P KRP4A96 FXFQ KRP1C98 FXZQ FXDQ FXTQ KRP1B101 C 1PA6316...

Page 72: ...EDUS391000 C Adapter Controls 71 C 1PA63164E To adaptor power supply connector on indoor unit or Branch Selector unit...

Page 73: ...d cassette type Compact multi flow Ceiling mounted AHU type FXDQ FXZQ FXTQ C 1PA63164E DTA104A62 Option KRP1C98 Option KRP1C98 FXMQ M DTA104A61 DTA104A61 DTA104A61 If installing on a Branch Selector u...

Page 74: ...EDUS391000 C Adapter Controls 73 3 3 DTA109A51 DIII NET Expander Adapter 1P013360...

Page 75: ...Adapter EDUS391000 C 74 Controls 1P013360...

Page 76: ...EDUS391000 C Adapter Controls 75 1P013360...

Page 77: ...Adapter EDUS391000 C 76 Controls 3 4 KRP1C74 75 Wiring Adapter C 2P263038A...

Page 78: ...EDUS391000 C Adapter Controls 77 C 2P263038A...

Page 79: ...Adapter EDUS391000 C 78 Controls C 2P263038A KRP1C74 Compact multi flow...

Page 80: ...EDUS391000 C Adapter Controls 79 3 5 KRP4A71 72 73 74 Group Control Adapter BRC1E71 BRC1E71 BRC1E71 FXHQ KRP1C93 FXMQ P KRP4A96 FXFQ KRP1C98 FXZQ FXDQ FXTQ KRP1B101 FXAQ KRP4A93...

Page 81: ...Adapter EDUS391000 C 80 Controls C 1P161220 Ceiling mounted duct type Ceiling mounted cassette type Compact multi flow Ceiling mounted AHU type FXDQ FXZQ FXTQ C FXMQ M KRP4A71 KRP4A71...

Page 82: ...EDUS391000 C Adapter Controls 81...

Page 83: ...Adapter EDUS391000 C 82 Controls...

Page 84: ...EDUS391000 C Adapter Controls 83 C 1P161221...

Page 85: ...tor for Computerized Control 3 6 1 Function When connected to the central remote controller this kit enables unified display operation malfunction and unified control operation stop 1 Unified Display...

Page 86: ...or unit and remote controller Finally check operation is normal For details refer to the installation manuals for the indoor and outdoor units Next wire between the indoor unit and the central remote...

Page 87: ...wire Max length 490ft 1 Control Input Unified Operation Stop Wire as explained here following depending on whether input carries a voltage VOLT or not NON VOLT 1 Input with Voltage 2 Input with Non Vo...

Page 88: ...eration display W1 and W2 and malfunction display W3 and W4 signals The allowable current per contact is 10 mA 3A Output conditions are indicated as below C 1P127045 Position Input A 2 OFF ON Unified...

Page 89: ...Adapter EDUS391000 C 88 Controls...

Page 90: ...this product conforms tot he applicable standards and is suitable for use in the region where the product will be used This statement does not purport to exclude restrict or modify the application of...

Reviews: