NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for power
and transmission lines.
▪
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated properly.
▪
Paper pattern for installation
(upper part of packing) (accessory). When
selecting the installation location, use the paper pattern. It contains the
dimensions of the unit and the required ceiling opening.
▪
Air flow directions
. You can select different air flow directions. Choose the one
best suited for the room. For more information, see the installation manual of
the optional blocking pad kit.
Example:
1
2
3
4
1
2
3
4
1
2
3
a
b
c
a
All-round air flow
b
4-way air flow (with closed corners) (optional blocking pad kit required)
c
3-way air flow (optional blocking pad kit required)
▪
Ceiling insulation
. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
▪
Spacing
. Mind the following requirements:
(mm)
≥1500
≥2000
≥4000
≥1500
A
B
C
b
a
d
a
c
A
Minimum distance to the wall (see below)
B
Minimum and maximum distance to the floor (see below)
C
20~63 class:
≥
224 mm:
In case of installation with standard decoration panel
≥
266 mm:
In case of installation with design decoration panel
≥
304 mm:
In case of installation with self-cleaning decoration panel
≥
274 mm:
In case of installation with fresh air intake kit
80~100 class:
≥
266 mm:
In case of installation with standard decoration panel
≥
308 mm:
In case of installation with design decoration panel
≥
346 mm:
In case of installation with self-cleaning decoration panel
≥
316 mm:
In case of installation with fresh air intake kit
125 class:
≥
308 mm:
In case of installation with standard decoration panel