If the … decoration panel is used
Then
(1)
M
SW
—
Standard or self-cleaning
13 (23)
15
01
Design
02
Setting: Airflow direction range
This setting must correspond with the needs of the user.
If you want set the airflow direction range to…
Then
(1)
M
SW
—
Upper
13 (23)
4
01
Medium
02
Lower
03
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It determines the fan
speed of the indoor unit during thermostat OFF condition.
1
If you have set the fan to operate, set the air volume speed:
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
Monitoring 3
(2)
06
H
(2)
07
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
Monitoring 3
(2)
06
H
(2)
07
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
•
—: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
H:
High fan speed
•
Setup volume
: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
•
Monitoring 1, 2, 3
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1), by
L
(Monitoring 2) or by
H
(Monitoring 3).